Auxiliary heater control by outdoor temperature 1
This control selects heat pump or external heater according to the outdoor temperature. When out-
door temperature is high, the heating is performed by using heat pump only.
Operation
Condition
Heater on
Heater is on as shown in following diagram of heating temperature.
Heater off
• Heater is off as shown in following diagram of heating temperature.
• Other than heating mode
• Error occurred
• Forced thermostat off
• Heat pump only zone
• Temperature of heater on (Thon): Adjustable by function number 62 (Operating temperature
switching of external heaters).
• All control temperatures will shift by adjusting “Thon”.
• Outdoor temperature zone boundary A and B: Adjustable individually by function setting number
66 and 67.
•
External heater output
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
Off
On
Tr-Ts ≥ 0.5°C
Tr-Ts
Tr-Ts (=Thon) ≤ -0.5°C
•
Outdoor temperature zone
Heat pump only zone
(Heat pump)
Combination zone
(Heat pump + Heater)
Heat pump prohibition zone
(Heater)
B: 6°C*
A: -20°C*
B + 2°C: 8°C
A + 2°C: -18°C
Outdoor temp.
*: Adjustable by function setting 66 and 67
- 26 -