CAPACITY COMPENSATION RATE FOR PIPE LENGTH
5.
AND HEIGHT DIFFERENCE
MODEL: AO
G07LLCC, AO
G09LLCC
H
H
Height difference H
1 Indoor unit is higher than outdoor unit.
2 Indoor unit is lower than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HEATING
Pipe length (m)
5
7.5
10
15
20
Height difference H
(m)
Û
1
Indoor unit is higher
than outdoor unit.
15
-
-
-
0.832
0.822
10
-
-
0.917
0.832
0.822
7.5
-
0.961
0.917
0.832
0.822
5
1.000
0.961
0.917
0.832
0.822
0
1.000
0.961
0.917
0.832
0.822
Û
2
Indoor unit is lower
than outdoor unit.
-5
0.995
0.956
0.912
0.828
0.818
-7.5
-
0.954
0.910
0.826
0.816
-10
-
-
0.908
0.824
0.814
-15
-
-
-
0.815
0.805
COOLING
Pipe length (m)
5
7.5
10
15
20
Height difference H
(m)
Û
1
Indoor unit is higher
than outdoor unit.
15
-
-
-
0.872
0.910
10
-
-
0.961
0.886
0.925
7.5
-
0.979
0.965
0.890
0.929
5
0.992
0.983
0.969
0.893
0.933
0
1.000
0.991
0.976
0.901
0.940
Û
2
Indoor unit is lower
than outdoor unit.
-5
1.000
0.991
0.976
0.901
0.940
-7.5
-
0.991
0.976
0.901
0.940
-10
-
-
0.976
0.901
0.940
-15
-
-
-
0.901
0.940
Содержание AOG07LLCC
Страница 2: ...1 INDOOR UNIT WALL MOUNTED TYPE AS G07LLCC AS G09LLCC AS G12LLCC DTR_AS087E_02 2014 02 10 ...
Страница 17: ... 01 14 WALL MOUNTED TYPE AS G07 12LLCC WALL MOUNTED TYPE AS G07 12LLCC SOUND LEVEL CHECK POINT 88888 ...
Страница 25: ...2 OUTDOOR UNIT SINGLE TYPE AO G07LLCC AO G09LLCC AO G12LLCC DTR_AO154E_01 2013 11 07 ...
Страница 37: ... 02 11 OUTDOOR UNIT AO G07 12LLCC OUTDOOR UNIT AO G07 12LLCC SOUND LEVEL CHECK POINT 88888 Airflow 1 m ...