![Fujitsu AO G36KBTB Series Скачать руководство пользователя страница 17](http://html.mh-extra.com/html/fujitsu/ao-g36kbtb-series/ao-g36kbtb-series_service-instruction_118232017.webp)
Operation flow chart
Start
Room temp. >
Ts+2°C?
Cooling operation
Heating operation
Auto change over is
second or more?
No
Yes
Ts: Setting temperarure
Thermostat remains
in off state for 6 minutes
or longer?
System stops
or operation command
other than auto changeover
operation?
Middle zone
Operation mode of
outdoor unit: Cooling?
Outdoor temp.
< 25
°C?
Operation mode before
the monitor mode
is cooling mode?
Monitor
mode
Room temp. <
Ts-2°C?
No
Yes
No
Yes
No
Yes
No
Yes
No
No
Operation mode of
outdoor unit: Heating?
Yes
Yes
No
System stops
or operation command
other than auto changeover
operation?
Yes
No
Yes
No
Thermostat remains
in off state for 6 minutes
or longer?
Yes
No
- (01-12) -
2. Auto changeover operation
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS