Setting the Outlet Directions
• Select the setting values in the table below for using a 3-way
outlet. (The unit is factory-set to “00”.)
Setting Description
Function Number
Setting Value
4-way
22
00
3-way
01
Setting the Filter Sign
• The indoor unit has a sign to inform the user that it is time to
clean the filter.
• Select the time setting for the filter sign display interval in the
table below according to the amount of dust or debris in the
room. (The unit is factory-set to “00”.)
• If you do not wish the filter sign to be displayed, select the setting
value for “No indication”.
Setting Description
Function Number
Setting Value
Standard
(2,500 hours)
11
00
Long interval
(4,400 hours)
01
Short interval
(1,250 hours)
02
No indication
03
Setting the Cooler Room Temperature Correction
• Depending on the installed environment, the room temperature
sensor may require a correction. The settings may be selected
as shown in the table below. (The unit is factory-set to “00”.)
Setting Description
Function Number
Setting Value
Standard
30
00
Lower control
01
Setting the Heater Room Temperature Correction
• Depending on the installed environment, the room temperature
sensor may require a correction. The settings may be changed
as shown in the table below. (The unit is factoryset to “00”.)
Setting Description
Function Numbe
Setting Value
Standard
31
00
Lower control
01
Slightly warmer control
02
Warmer control
03
Setting Other Functions
• The following settings are also possible, depending on the
operating conditions. (The unit is factory-set to “00”.)
Auto Restart
Setting Description
Function Number
Setting Value
Yes
40
00
No
01
Indoor Room Temperature Sensor Switching Function
(Wired remote controller only)
Setting Description
Function Number
Setting Value
No
42
00
Yes
01
• If setting value is “00”, room temperature is controlled by the
indoor unit temperature sensor.
• If setting value is “01”, room temperature is controlled by either
indoor unit temperature sensor or remote control unit sensor.
Setting record
• Record any changes to the settings in the following table.
Setting
Setting Value
Ceiling height
Vertical direction adjusting
scope
Outlet directions
Filter sign
Cooler room temperature
correction
Heater room temperature
correction
Auto restart
Indoor room temperature
sensor switching function
After completing the FUNCTION SETTING, be sure to turn off the
power and turn it on again.
3. Setting the room temperature detection
location
The detection location of the room temperature can be selected
from the following two examples. Choose the detection location
that is best for the installation location.
A. Indoor unit setting (factory setting)
The room temperature is detected by the indoor unit temperature
sensor.
(1) When the THERMO SENSOR button is pressed, the lock
display flashes because the function is locked at the factory.
A
Indoor unit
B. Indoor unit/remote controller setting (room
temperature sensor selection)
The temperature sensor of the indoor unit or the remote controller
can be used to detect the room temperature.
(1) Enable the room temperature sensor selection in FUNCTION
SETTING, which will be described later.
(2) Press the THERMO SENSOR button for 5 seconds or more to
select the temperature sensor of the indoor unit or the remote
controller.
B
Indoor unit
NOTE
If the function to change the temperature sensor is used as
shown in examples A (other than example B), be sure to lock the
detection location.
If the function is locked, the lock display
will flash when the
THERMO SENSOR button is pressed.
Содержание AO*A30LBTL Series
Страница 2: ...1 INDOOR UNIT D2D_AU034E 04 2010 07 07 CASSETTE TYPE AU A30LBLU AU A36LBLU ...
Страница 12: ... 01 09 CASSETTE TYPE AU A30 36L CASSETTE TYPE AU A30 36L WIRING DIAGRAMS 555 MODEL AU A30L AU A36L ...
Страница 38: ...D2D_AO022E 02 2010 01 18 SINGLE TYPE AO A30LBTL AO A30LFTL AO A36LBTL AO A36LFTL 2 OUTDOOR UNIT ...
Страница 43: ... 02 04 OUTDOOR UNIT AO A30 36L OUTDOOR UNIT AO A30 36L REFRIGERANT CIRCUIT 333 MODEL AO A30LB AO A36LB ...
Страница 44: ... 02 05 OUTDOOR UNIT AO A30 36L OUTDOOR UNIT AO A30 36L MODEL AO A30LF AO A36LF ...
Страница 45: ... 02 06 OUTDOOR UNIT AO A30 36L OUTDOOR UNIT AO A30 36L WIRING DIAGRAMS 444 MODEL AO A30LB AO 36LB ...
Страница 46: ... 02 07 OUTDOOR UNIT AO A30 36L OUTDOOR UNIT AO A30 36L MODEL AO A30LF ...
Страница 47: ... 02 08 OUTDOOR UNIT AO A30 36L OUTDOOR UNIT AO A30 36L MODEL AO A36LF ...
Страница 54: ... 02 15 OUTDOOR UNIT AO A30 36L OUTDOOR UNIT AO A30 36L SOUND LEVEL CHECK POINT 88888 ...