1. Specifications
Type
Inverter heat pump
Model name
AOU24RGLX
AOU30RGLX
Power supply
208/230 V ~ 60 Hz
Power supply intake
Outdoor unit
Available voltage range
187—253 V
Starting current
A
9.6
11.5
Fan
Airflow rate
Cooling
CFM (m
3
/h)
2,119 (3,600)
Heating
2,119 (3,600)
Type × Q'ty
Propeller × 1
Motor output
W
100
Sound pressure level *
Cooling
dB (A)
53
Heating
55
Heat exchanger type
Dimensions
(H × W × D)
in
31-7/16 × 35-7/16 × 1-7/16
mm
798 × 900 × 36.4
Fin pitch
FPI
20
Rows × Stages
2 × 38
Pipe type
Copper
Fin
Type (Material)
Aluminum
Surface treatment
PC Fin
Compressor
Type × Q'ty
DC twin rotary × 1
Motor output
W
2,100
Refrigerant
Type
R410A
Charge
lb oz
4 lb 10 oz
g
2,100
Refrigerant oil
Type
POE (RB68)
Amount
in
3
(cm
3
)
48.8 (800)
Enclosure
Material
Steel
Color
Beige
Approximate color of Munsell 10YR 7.5/1.0
Dimensions
(H × W × D)
Net
in (mm)
32-11/16 × 35-7/16 × 13
(830 × 900 × 330)
Gross
in (mm)
39-3/8 × 41-5/16 × 17-1/2
(1,000 × 1,050 × 445)
Weight
Net
lb (kg)
134 (61)
Gross
152 (69)
Connection pipe
Size
Liquid
in (mm)
Ø3/8 (9.52)
Gas
Ø5/8 (15.88)
Method
Flare
Pre-charge length
ft (m)
66 (20)
Max. length
164 (50)
Max. height difference
98 (30)
Operation range
Cooling
°F (°C)
-4 to 115 (-20 to 46)
Heating
-4 to 75 (-20 to 24)
Drain hose
Material
LDPE
Size
in (mm)
Ø1/2 (13.0) [I.D.], Ø5/8 to Ø11/16 (16.0 to 16.7) [O.D.]
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 80 °FDB (26.67 °CDB) / 67 °FWB (19.44 °CWB), and outdoor temperature of 95 °FDB (35 °CDB) / 75 °FWB (23.9 °CWB).
– Heating: Indoor temperature of 70 °FDB (21.11 °CDB) / 59 °FWB (15 °CWB), and outdoor temperature of 47 °FDB (8.33 °CDB) / 43 °FWB (6.11 °CWB).
– Pipe length: 24 ft 6 in (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *: Sound pressure level
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
- 66 -
1. Specifications
OUTDOOR UNIT
AOU24-30RGLX,
AOUG36-48LMAS1
OUTDOOR UNIT
AOU24-30RGLX,
AOUG36-48LMAS1