En-10

6.6  External input and external output (optional parts)

 CAUTION

Do not operate any switches other than prescribed, as it can cause the unit to operate 
improperly or malfunction.

Use an insulated screwdriver to set the DIP switches.

(CNA03)

(CNA01)

(CNA04)

(CNA02)

SW1
SW2
SW3
SW4

Apply voltage 
terminal

Dry contact 
terminal

Controller PCB

DIP switch 

(SET 2)

ON

OFF

Output terminal (CNB01) 

6.6.1. External 

input

•  Indoor unit can be Operation/Stop, Emergency stop or Forced stop by using indoor unit 

PCB CNA01 or CNA02.

•  “Operation/Stop” mode, “Emergency stop” mode or “Forced stop” mode can be selected 

with function setting of indoor unit.

•  Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04.
•  A twisted pair cable (22 AWG) should be used. Maximum length of cable is 492 ft. (150 m).
•  Use an external input and output cable with appropriate external dimension, depending on 

the number of cables to be installed.

•  The wire connection should be separate from the power cable line.

Input select

Use either one of these types of terminal according to the application. (Both types of termi-
nals cannot be used simultaneously.)

 Apply voltage terminal ([CNA01], [CNA03])

When a power supply must be provided at the input device you want to connect, use the 
Apply voltage terminal ([CNA01], [CNA03]).

Input

de

vic

e 1

Input

de

vic

e 2

Input

de

vic

e 3

Load 
resistance

Load 
resistance

Load 
resistance

*1

DC power supply
12 to 24V

Connected unit

*a

*a

*a

P.C.B

CNA01

CNA03

*b

*1  Make the power supply DC12 to 24V. Select a power supply capacity with an ample surplus 

for the connected load.

Do not impress a voltage exceeding 24V across pins 1-2, and 1-3.
*a  The allowable current is DC 5mA to 10mA. (Recommended: DC5mA)
 

Provide a load resistance such that the current becomes DC10mA or less.

 

Select very low current use contacts (usable at DC12V, DC1mA or less).

*b   The polarity is [+] for pin 1 and [-] for pin 2 and 3. Connect correctly.

When connected to Apply voltage terminals of multiple indoor units with a connected unit, be 
sure to make a branch outside the indoor unit using a pull box, etc. as shown on below example.

DC power supply 
12 to 24V

Connected unit

Load 

resistance

P.C.B

P.C.B

CNA01

P.C.B

Input

de

vic

e 1

Input

de

vic

e 2

Indo

or

 unit

Indo

or

 unit

Indo

or

 unit

Load 

resistance

CNA01

CNA01

 Dry contact terminal ([CNA02], [CNA04])

When a power supply is unnecessary at the input device you want to connect, use the Dry 
contact terminal ([CNA02], [CNA04]).

P.C.B

GND

Ch 1

Ch 3

*c

*c

*c

*d

Ch 2

CNA02

CNA04

Connected unit

*c  Select very low current use contacts (usable at DC12V, DC1mA or less).
*d  The wiring is different from Apply voltage terminals. Be suf

fi

 ciently careful when wiring.

When connected to Dry contact terminals of multiple indoor units with a connected unit, insu-
late each indoor unit with relay, etc. as shown on below example.

P

o

w

e

r s

u

p

p

ly

 f

o

r r

e

la

y

Indo

or

 unit

Indo

or

 unit

Indo

or

 unit

Input device 2

Input device 1

K1 - K6: Relay

(Device for DC Current)

P.C.B

K1

P.C.B

P.C.B

CNA02

K2

K3

K4

K5

K6

CNA02

CNA02

NOTE :

When connected to multiple indoor units directly, it will cause breakdown.

Operation behavior

 Input signal type

The input signal type can be selected.
It is switched by DIP switch on the indoor unit PCB. 

Pulse

The width of pulse 
must be longer than  
200msec.

Edge

DIP switch [Set 2 SW2]

Input signal type

OFF (factory setting)

Edge

ON

Pulse

Содержание Airstage VR-II ARUV12TLAV

Страница 1: ...9373870180 04 ARUV12TLAV ARUV18TLAV ARUV24TLAV ARUV30TLAV ARUV36TLAV ARUV48TLAV ARUV60TLAV TM Français Español MANUEL D INSTALLATION MANUAL DE INSTALACIÓN UNITÉ INTÉRIEURE type conduit UNIDAD INTERIOR Tipo conducto Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado ...

Страница 2: ... can cause dripping and water damage to walls and floors In an Area with High Winds Securely anchor the outdoor unit down with bolts and a metal frame Provide a suitable air baffle In a Snowy Area for Heat Pump type Systems Install the outdoor unit on a raised platform that is higher than drifting snow When Connecting Refrigerant Tubing Keep all tubing runs as short as possible Use the brazing met...

Страница 3: ... approximately 1 6 times higher than the R22 failure to use dedicated piping material or improper installation can cause rupture or injury Furthermore it can cause serious accidents such as water leakage electric shock or fire Tool name Changes Gauge manifold Pressure is huge and cannot be measured with a conventional R22 gauge To prevent erroneous mixing of other refrigerants the diameter of each...

Страница 4: ...follows 1 Install the indoor unit on a place having a sufficient strength so that it withstands against the weight of the indoor unit 2 The inlet and outlet ports should not be obstructed the air should be able to blow all over the room 3 Leave the space required to service the air conditioner 4 A place from where the air can be distributed evenly throughout the room by the unit 5 Install the unit...

Страница 5: ...e application All externally insulated duct work must have an adequate vapor seal for summer operation This is particularly important where the duct is exposed to highly humid conditions in such places as attics vented crawl spaces unconditioned basements and utility rooms The vapor seal prevents condensation of moisture in the insulating material and subsequent loss of its insulating value 4 PIPE...

Страница 6: ...d both the gas and liquid pipes Failure to do so may cause water leaks Use heat insulation with heat resistance above 248 F 120 C Reverse cycle model only In addition if the humidity level at the installation location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant piping If the expected humidity level is 70 to 80 use heat insulation that is 9 16 i...

Страница 7: ...made in the walls for wiring Otherwise a short circuit could result Use the included connection cables and power cables or ones specified by the manufacturer Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Do not modify the power cables use extension cables or use any branches in the wiring Improper connections insufficient insulatio...

Страница 8: ...d Technical Manual to calculate the total amount of units that can be connected on a given breaker 6 1 1 Transmission and remote controller wiring specifications Follow the specifications below for the transmission and remote controller cable Cable size Wire type Remarks Transmission cable 22 AWG 0 33 mm LEVEL 4 NEMA non polar 2core twisted pair solid core diameter 0 026 in 0 65mm LONWORKS compati...

Страница 9: ... supply L1 L2 N GND 11 to 16 lbf in 1 2 to 1 8 N m 6 3 2 Transmission and Remote controller cable Transmission cable 1 in 25 mm 1 3 8 in 35mm Shielded cable no film Remote controller cable 1 in 25 mm For 3 wire type 1 in 25 mm For 2 wire type When the 2 cables are attached Different diameter Connect to 1 side GOOD PROHIBITED WARNING Tighten the terminal screws to the specified torques otherwise ab...

Страница 10: ...nal parts bind each connection cable with the transmission and remote controller cables 6 6 External input and external output optional parts 6 7 Remote sensor optional parts 6 8 IR receiver unit optional parts Fix the conduit with the supporters as shown below Conduit Power supply cable Supporter Indoor unit 30 in 756 mm or less 54 in 1 361 mm or less 54 in 1 361 mm or less 54 in 1 361 mm or less...

Страница 11: ...ed load Do not impress a voltage exceeding 24V across pins 1 2 and 1 3 a The allowable current is DC 5mA to 10mA Recommended DC5mA Provide a load resistance such that the current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correctly When connected to Apply voltage terminals of multiple indoor unit...

Страница 12: ... Thermostat off ON OFF Normal 6 6 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 82 ft 25 m Use an external input and output cable with appropriate external dimension depending on the number of cables to be installed Output voltage Hi DC12V 2V Lo 0V Permissible current 50mA Output select When indicator etc are connected directly Indicator 1 Indicator 2 Indic...

Страница 13: ...umber to 02 Refer to 7 3 Function setting for details about Function Number and Setting Number 6 8 IR receiver unit optional parts For the installation method please refer to the installation manual of IR receiver unit Connection terminals IR receiver unit terminal CN18 Controller PCB Wiring arrangement Controller PCB Cable tie Medium Accessories Bind with the transmission and remote controller ca...

Страница 14: ... 1 0 1 2 0 2 2 0 2 3 0 3 3 0 3 4 0 4 4 0 4 5 0 5 5 0 5 6 0 6 6 0 6 7 0 7 7 0 7 8 0 8 8 0 8 9 0 9 9 0 9 10 1 0 10 1 0 11 1 1 11 1 1 12 1 2 12 1 2 99 9 9 63 6 3 Do not set the indoor unit address IU AD SW at 64 to 99 It may result in failure Remote controller address i 3 wire type Rotary switch RC AD SW Factory setting 0 When connecting multiple indoor units to 1 standard wired remote controller set...

Страница 15: ... and Start Stop by a remote controller is restricted 01 Emergency stop 02 Forced stop Error re port target 47 00 All Change the target for reporting errors Errors can either be reported in all locations or only on the central remote controller 01 Display only on central remote controller Fan set ting when cooling thermostat off 49 00 Follow the setting on the remote controller When set to 01 the f...

Страница 16: ...lamp Green Status contents Lit Lit when the power is turned on Flashing There is a fault with the communication board or the main board 0 1s ON 0 1s OFF Power indicator lamp green Controller PCB 11 ERROR CODES If you use a wired type remote controller error codes will appear on the remote controller display If you use a wireless remote controller the lamp on the photodetector unit will output erro...

Страница 17: ...the Status Touch the Error Information 2 digit numbers are corresponding to the error code in the preceding table For more information refer to the installation manual of the remote controller UTY RNKU 3 wire type UTY RNRU 2 wire type For details on marking the ERROR CODES please refer to the Manual of IR Receiver Unit or Wired Remote Controller ...

Отзывы: