1. System design

1-1. Refrigerant system

¢

Connectable unit within 1 refrigerant system

Outdoor unit

Unit

Quantity

Outdoor unit

1 unit

Indoor unit

Outdoor unit

Connectable indoor unit conditions

Ton

Model name

Cooling

capacity

(Btu/h)

Cooling capacity range

Connectable number

6

AOU72RLAVL

72,000

50 to 150%

of outdoor unit cooling

capacity

1 to 18 units

8

AOU96RLAVL

96,000

1 to 24 units

10

AOU120RLAVL

120,000

1 to 30 units

CAUTION

• When all indoor units are operating at maximum capacity, individual indoor unit operates at a

slightly lower capacity. (When connecting more than 100%)

• Do not exceed both of connectable cooling capacity range and maximum connectable indoor

unit quantity, otherwise it may cause hinder the return of the refrigerant oil and cause a com-
pressor breakdown.

1-1. Refrigerant system

- (06-1) -

1. System design

SYSTEM

DESIGN

SYSTEM

DESIGN

Содержание AIRSTAGE J-IIIL

Страница 1: ...DESIGN TECHNICAL MANUAL ...

Страница 2: ...CONTENTS 1 GENERAL INFORMATION 2 MODEL SELECTION 3 OUTDOOR UNITS 4 INDOOR UNITS 5 CONTROL SYSTEM 6 SYSTEM DESIGN 7 FUNCTION SETTINGS 8 EXTERNAL INPUT AND OUTPUT 9 NOTES 10 OPTIONAL PARTS ...

Страница 3: ...1 GENERAL INFORMATION 2019 11 01 DV_CH01_J3LU061EF_02 ...

Страница 4: ...Outdoor unit and indoor unit lineup 01 1 1 1 Outdoor units 01 1 1 2 Indoor units 01 2 2 Optional parts 01 5 2 1 Controllers 01 5 2 2 Adapter Convertor Maintenance tool 01 8 2 3 Branch kit 01 9 2 4 Cassette grille 01 11 2 5 Others 01 12 ...

Страница 5: ...00 AOU96RLAVL 10 120 000 AOU120RLAVL Model designation Column 1 2 3 4 5 6 7 8 9 10 11 Code A O U 1 2 0 R L A V L Column Item Description 1 Type AO Outdoor unit 2 3 Brand U Fujitsu 4 Capacity 72 72 000 Btu h 96 96 000 Btu h 120 120 000 Btu h 5 6 7 Function R Heat pump 8 Function L Inverter 9 Function A J series B V series 230V C V series 460V 10 Function V VRF 11 Chassis code L 1 1 Outdoor units 01...

Страница 6: ... code 4 7 9 12 14 18 24 30 36 36 48 60 72 96 Compact cas sette Circular flow cassette Cassette Mini duct Slim duct Slim concealed floor Medium static pressure duct High static pressure duct Compact floor Floor Ceiling Ceiling Wall mounted 1 2 Indoor units 01 2 1 Outdoor unit and indoor unit lineup GENERAL INFORMATION GENERAL INFORMATION ...

Страница 7: ...ealed floor 7 500 9 500 ARUL7TLAV2 7 13 16 27 9 16 24 7 16 198 700 620 9 500 10 900 ARUL9TLAV2 12 000 13 500 ARUL12TLAV2 14 000 15 600 ARUL14TLAV2 18 000 20 000 ARUL18TLAV2 7 13 16 35 7 16 24 7 16 198 900 620 Medium static pressure duct 24 000 27 000 ARUM24TLAV2 10 5 16 44 11 16 27 9 16 270 1 135 700 30 000 34 000 ARUM30TLAV2 36 000 40 000 ARUM36TLAV2 High static pressure duct 36 000 40 000 ARUH36...

Страница 8: ...0 998 228 24 000 27 000 ASUB24TLAV Model designation Column 1 2 3 4 5 6 7 8 9 10 11 Code A U U A 1 2 T L A V 1 Column Item Description 1 Type AU Cassette type AR Duct type 2 AB Floor Ceiling or Ceiling type AS Wall mounted type 3 Brand U Fujitsu 4 Model A Standard AU AS B Large AU AS L Slim AR M Middle static pressure AR H High static pressure AR 5 Capacity 4 4 000 Btu h 7 7 500 Btu h 9 9 500 Btu ...

Страница 9: ...d equipment by their PC or tablet from anywhere Optional UTY PTGXA Central remote controller UTY DCGY Central control of small and medium sized buildings and tenants The operation status of all connected indoor units can be viewed at a glance on a large LCD monitor to simplify individual control to batched control Central remote controller UTY DCGYZ1 Central control of small and medium sized build...

Страница 10: ...ote controller concentrates on the basic functions such as Start Stop fan control temperature setting Wire type Non polar 2 wire Simple remote controller UTY RSKU Compact remote controller concentrates on the basic functions such as Start Stop fan control temperature setting and operation mode Wire type Polar 3 wire Simple remote controller Without operation mode UTY RHKU Compact remote controller...

Страница 11: ...ler ALG System controller lite DTG Touch panel controller 6 DCG Central remote controller CGG Group remote controller RNR RNK Wired remote controller 7 RSR RHR RSK RHK Simple remote controller LNH Wireless remote controller 8 Brand Y Fujitsu X Neutral brand 9 Version Z1 Z2 Z3 10 2 1 Controllers 01 7 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...

Страница 12: ...al products using a third party thermostat BACnet gateway Hardware UTY VBGX For connection between VRF network system to the BMS system using BACnet protocol Supports max 128 indoor units BACnet gateway Software UTY ABGXZ1 The central control of maximum 1600 indoor units can be realized by connecting the VRF network system to the BACnet a global standard for open network Wireless LAN adapter UTY T...

Страница 13: ...ring tool UTY AMGXZ1 Trouble free operation at all times by web monitoring system The operation status of the VRF network system within the building can be monitored in real time over the Internet 2 3 Branch kit Separation tube For 2 pipes Exterior Model name Liquid pipe Gas pipe UTP AX090A Liquid pipe Gas pipe UTP AX180A 2 2 Adapter Convertor Maintenance tool 01 9 2 Optional parts GENERAL INFORMA...

Страница 14: ... Model name Liquid Pipe Gas Pipe UTR H0906L Liquid Pipe Gas Pipe UTR H1806L Liquid Pipe Gas Pipe UTR H0908L Liquid Pipe Gas Pipe UTR H1808L 2 3 Branch kit 01 10 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...

Страница 15: ... cassette type UTG CCGVG Grid type grille For Compact cassette type UTG CCGV Standard type grille For Circular flow cassette type UTG LCGVCW UTG LCGVCB For Cassette type UTG LCGV 2 4 Cassette grille 01 11 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...

Страница 16: ...ir filter UTD LF25NA 2 pcs For High static pressure duct type Air filter UTD LF60KA For Medium static pressure duct type Drain pump unit UTZ PU1NBA For Ceiling type Drain pump unit UTZ PU1EBA For Compact cassette type Air outlet shutter plate UTR YDZB For Cassette type and Circular flow cassette type Air outlet shutter plate UTR YDZK 2 5 Others 01 12 2 Optional parts GENERAL INFORMATION GENERAL IN...

Страница 17: ...W For Compact floor type Half concealed kit UTR STA For all duct type IR receiver unit UTY TRHX For all duct type IR receiver unit UTB YWC For Cassette type IR receiver unit UTY LRHYB1 For Circular flow cassette type IR receiver unit UTY LBHXD For Circular flow cassette type Human sensor kit UTY SHZXC 2 5 Others 01 13 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...

Страница 18: ...e 2 For Compact cassette type Insulation kit for high humidity UTZ KXRA 1 For Compact cassette type Fresh air intake kit UTZ VXAA For Cassette type Fresh air intake kit UTZ VXRA For Mini duct and Slim duct type Auto louver grille kit UTD GXTA W For Slim duct type Auto louver grille kit UTD GXSA W UTD GXSB W External power supply unit UTZ GXXA 2 5 Others 01 14 2 Optional parts GENERAL INFORMATION G...

Страница 19: ...ontroller UTY XWZXZ8 For Outdoor unit UTY XWZXZ9 For Touch panel controller and Central remote controller UTY XWZXZA For Indoor unit and RB unit UTY XWZXZB For Indoor unit UTY XWZXZC For Indoor unit UTY XWZXZD For Indoor unit UTY XWZXZE For Outdoor unit UTY XWZXZF 2 5 Others 01 15 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...

Страница 20: ...2 5 Others 01 16 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...

Страница 21: ...2 MODEL SELECTION 2019 11 01 DV_CH02_J3LU061EF_02 ...

Страница 22: ...edium static pressure duct type 02 22 2 7 High static pressure duct type 02 23 2 8 Compact floor type 02 25 2 9 Floor Ceiling type 02 27 2 10 Ceiling type 02 28 2 11 Wall mounted type 02 29 3 Heating capacity table Indoor unit 02 33 3 1 Compact cassette type 02 33 3 2 Circular flow cassette type 02 35 3 3 Cassette type 02 37 3 4 Mini duct type 02 39 3 5 Slim duct Slim concealed floor type 02 40 3 ...

Страница 23: ...n of controllers Refer to Controllers of Optional parts in Chapter 1 GENERAL INFORMATION on page 01 5 Selection of adapter and convertor Refer to Adapter Convertor Maintenance tool of Option al parts in Chapter 1 GENERAL INFORMATION on page 01 5 Selection of branch kit Refer to following informations Outdoor unit branch kit of Optional parts in Chap ter 1 GENERAL INFORMATION on page 01 5 Separatio...

Страница 24: ...of indoor unit heat load Calculate the total capacity of indoor units at fol lowing conditions Calculated total capacity of indoor units A Rated condition Design temperature condition Select outdoor units to match the total capacity of indoor units Refer to Cooling capacity range of connectable indoor units on page 02 12 Confirm the following items Cooling capacity range of connectable in door uni...

Страница 25: ... 4 Confirm whether satisfy the following calculation If actual capacity of indoor unit is lower than heat load change to larger capacity of outdoor units and return to step marked If actual capacity of indoor unit is greater than heat load procedure is completing Actual capacity of indoor unit heat load End System capacity A Actual capacity of indoor unit capacity of in door unit at design tempera...

Страница 26: ...mpensated capacity of outdoor unit Estimated capacity of each indoor unit 1 Find TCin r and TCin d Refer to Cooling capacity table Indoor unit on page 02 14 or Heating capacity table In door unit on page 02 33 2 Find the following compensation coefficient Refer to Capacity compensation coefficient on page 02 13 Compensation coefficient of pipe length Compensation coefficient of frosting defrosting...

Страница 27: ...er satisfy the condition 5 Find TCout d using the value of previous step and Cooling capacity table Outdoor unit on page 02 54 or Heating capacity table Outdoor unit on page 02 63 6 Calculate TCout c Cooling calculation TCout c TCout d compensation coefficient of pipe length Heating calculation TCout c TCout d compensation coefficient of pipe length compensation coefficient of defrosting frosting ...

Страница 28: ... 4 20 4 20 4 6 8 5 1 A 2 Indoor unit models Example AU AUUB 24 AUUB 24 AUUB 24 AUUA 9 AUUA 7 A 3 TCin r kBtu h 24 0 24 0 24 0 9 5 7 5 Refer to Indoor units of Outdoor unit and indoor unit lineup in Chapter 1 GENERAL INFORMATION on page 01 1 A 4 TCin d kBtu h 25 1 25 1 25 1 9 9 7 8 Refer to Cooling capacity table Indoor unit on page 02 14 A 5 Compensation coefficient of pipe length 0 9 Refer to Cap...

Страница 29: ...ion coefficient of pipe length 0 9 Refer to Capacity compensation coefficient on page 02 13 B 6 TCout c kBtu h 77 6 B 4 B 5 Decision of system capacity No Item Value Remark C 1 System capacity 77 6 Smaller value of A 8 and B 6 Calculation of actual capacity of each indoor unit Item Room Remark 1 2 3 4 5 Actual capacity of each indoor unit kBtu h 20 9 20 9 20 9 8 3 6 5 C 1 A 3 A 7 Actual capacity o...

Страница 30: ...11 93 6 4 58 97 9 4 76 108 9 5 10 110 3 5 10 115 55 1 5 94 72 1 8 35 72 9 8 35 76 1 8 35 76 9 8 35 95 55 1 3 98 84 7 7 16 85 6 7 19 89 7 7 30 90 7 7 33 86 4 120 5 55 1 2 91 86 4 4 27 90 3 4 44 106 0 5 12 107 4 5 11 Cooling capacity at rated condition 72 kBtu h 6 ton Total rated capacity of indoor unit Outdoor temperature Indoor temperature 68 FDB 59 FWB 80 FDB 67 FWB 82 FDB 68 FWB 86 FDB 72 FWB 90...

Страница 31: ...6 2 7 2 7 A 2 Indoor unit models Example AU AUUB 30 AUUB 30 AUUB 30 AUUA 4 AUUA 4 A 3 TCin r kBtu h 30 0 30 0 30 0 4 0 4 0 Refer to Indoor units of Outdoor unit and indoor unit lineup in Chapter 1 GENERAL INFORMATION on page 01 1 A 4 TCin d kBtu h 31 4 31 4 31 4 4 2 4 2 Refer to Cooling capacity table Indoor unit on page 02 14 A 5 Compensation coefficient of pipe length 0 9 Refer to Capacity compe...

Страница 32: ...tion coefficient of pipe length 0 9 Refer to Capacity compensation coefficient on page 02 13 B 6 TCout c kBtu h 92 3 B 4 B 5 Decision of system capacity No Item Value Remark C 1 System capacity 92 3 Smaller value of A 8 and B 6 Calculation of actual capacity of each indoor unit Item Room Remark 1 2 3 4 5 Actual capacity of each indoor unit kBtu h 28 3 28 3 28 3 3 8 3 8 C 1 A 3 A 7 Actual capacity ...

Страница 33: ... unit Outdoor temperature Indoor temperature 68 FDB 59 FWB 80 FDB 67 FWB 82 FDB 68 FWB 86 FDB 72 FWB 90 FDB 73 FWB FDB TC IP TC IP TC IP TC IP TC IP 105 6 110 5 67 3 3 88 105 6 5 57 110 4 5 79 129 6 6 63 134 4 6 84 95 67 3 5 21 105 6 8 98 110 4 9 67 117 1 10 11 118 2 10 11 115 67 3 7 36 79 8 8 35 80 7 8 35 84 4 8 35 85 3 8 35 96 0 100 5 61 2 3 61 96 0 5 15 100 4 5 34 117 8 6 11 122 2 6 31 95 61 2 ...

Страница 34: ... capacity range Btu h 6 72 000 81 000 AOU72RLAVL 18 36 000 to 108 000 8 96 000 108 000 AOU96RLAVL 24 48 000 to 144 000 10 120 000 135 000 AOU120RLAVL 30 60 000 to 180 000 For conditions for cooling capacity of connectable indoor unit refer to Refrigerant system in Chapter 6 SYSTEM DESIGN on page 06 1 1 4 Cooling capacity range of connectable indoor units 02 12 1 Model selection and capacity calcul...

Страница 35: ... L Outdoor unit Higher Outdoor unit Lower 0 1 00 0 98 0 96 Height difference H 10 20 30 50 40 10 20 30 40 m 0 33 66 98 164 131 33 66 98 131 ft 0 394 33 66 98 131 164 197 230 262 295 328 361 ft 120 10 20 30 40 50 60 70 80 90 100 110 m Compensation coefficient of frosting defrosting Heating operation To take the effects of accumulated frost and defrosting operation on heating capacity into considera...

Страница 36: ... 5 2 6 5 6 0 7 5 5 7 7 8 6 0 9 2 6 3 9 5 7 0 77 4 8 4 1 5 4 5 0 6 1 5 2 6 5 6 0 7 5 5 7 7 8 6 0 9 2 6 3 9 4 6 9 81 4 8 4 1 5 4 5 0 6 1 5 2 6 5 6 0 7 5 5 7 7 8 6 0 9 1 6 2 9 2 6 9 86 4 8 4 1 5 4 5 0 6 1 5 2 6 5 6 0 7 5 5 7 7 8 6 0 8 9 6 1 9 0 6 8 91 4 8 4 1 5 4 5 0 6 1 5 2 6 5 6 0 7 5 5 7 7 8 6 0 8 7 6 1 8 8 6 7 95 4 8 4 1 5 4 5 0 6 1 5 2 6 5 6 0 7 5 5 7 7 8 6 0 8 6 6 0 8 7 6 7 99 4 8 4 1 5 4 5 0 6...

Страница 37: ...r temperature 68 FDB 59 FWB 73 FDB 61 FWB 75 FDB 63 FWB 79 FDB 64 FWB 80 FDB 67 FWB 82 FDB 68 FWB 86 FDB 72 FWB 90 FDB 73 FWB FDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 50 11 4 8 5 13 1 10 3 14 7 10 8 15 5 12 2 18 0 12 0 18 8 12 6 22 1 13 2 23 0 14 6 59 11 4 8 5 13 1 10 3 14 7 10 8 15 5 12 2 18 0 12 0 18 8 12 6 22 1 13 2 23 0 14 6 70 11 4 8 5 13 1 10 3 14 7 10 8 15 5 12 2 18 0 12 ...

Страница 38: ...6 14 8 20 7 16 8 23 6 16 3 23 8 16 7 24 9 16 3 25 2 17 9 Model AUUB30TLAV2 Outdoor tem perature Indoor temperature 68 FDB 59 FWB 73 FDB 61 FWB 75 FDB 63 FWB 79 FDB 64 FWB 80 FDB 67 FWB 82 FDB 68 FWB 86 FDB 72 FWB 90 FDB 73 FWB FDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 50 19 0 15 3 21 8 18 6 24 5 19 3 25 9 22 1 30 0 21 4 31 4 22 5 36 9 23 4 38 3 26 0 59 19 0 15 3 21 8 18 6 24 5 19...

Страница 39: ...0 33 0 50 2 34 7 59 0 36 2 59 9 39 6 81 30 4 23 5 34 8 28 5 39 2 29 7 41 4 33 9 48 0 33 0 50 2 34 7 58 4 36 0 58 9 39 2 86 30 4 23 5 34 8 28 5 39 2 29 7 41 4 33 9 48 0 33 0 50 2 34 7 57 1 35 5 57 7 38 7 91 30 4 23 5 34 8 28 5 39 2 29 7 41 4 33 9 48 0 33 0 50 2 34 7 55 9 35 0 56 5 38 3 95 30 4 23 5 34 8 28 5 39 2 29 7 41 4 33 9 48 0 33 0 50 2 34 7 54 9 34 7 55 5 37 9 99 30 4 23 5 34 8 28 5 39 2 29 ...

Страница 40: ...5 6 19 6 16 2 20 7 18 6 23 6 17 7 23 8 18 3 24 9 17 9 25 2 19 9 Model AUUB30TLAV Outdoor tem perature Indoor temperature 68 FDB 59 FWB 73 FDB 61 FWB 75 FDB 63 FWB 79 FDB 64 FWB 80 FDB 67 FWB 82 FDB 68 FWB 86 FDB 72 FWB 90 FDB 73 FWB FDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 50 19 0 16 0 21 8 19 5 24 5 20 2 25 9 23 3 30 0 22 4 31 4 23 5 36 9 24 4 38 3 27 3 59 19 0 16 0 21 8 19 5 2...

Страница 41: ... 5 1 3 5 77 2 5 2 0 2 9 2 5 3 3 2 6 3 5 3 0 4 0 2 9 4 2 3 0 4 9 3 1 5 0 3 5 81 2 5 2 0 2 9 2 5 3 3 2 6 3 5 3 0 4 0 2 9 4 2 3 0 4 9 3 1 4 9 3 4 86 2 5 2 0 2 9 2 5 3 3 2 6 3 5 3 0 4 0 2 9 4 2 3 0 4 8 3 1 4 8 3 4 91 2 5 2 0 2 9 2 5 3 3 2 6 3 5 3 0 4 0 2 9 4 2 3 0 4 7 3 0 4 7 3 3 95 2 5 2 0 2 9 2 5 3 3 2 6 3 5 3 0 4 0 2 9 4 2 3 0 4 6 3 0 4 6 3 3 99 2 5 2 0 2 9 2 5 3 3 2 6 3 5 3 0 4 0 2 9 4 2 3 0 4 5 3...

Страница 42: ...Indoor temperature 68 FDB 59 FWB 73 FDB 61 FWB 75 FDB 63 FWB 79 FDB 64 FWB 80 FDB 67 FWB 82 FDB 68 FWB 86 FDB 72 FWB 90 FDB 73 FWB FDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 50 7 6 6 0 8 7 7 3 9 8 7 6 10 4 8 7 12 0 8 5 12 6 8 9 14 7 9 3 15 3 10 3 59 7 6 6 0 8 7 7 3 9 8 7 6 10 4 8 7 12 0 8 5 12 6 8 9 14 7 9 3 15 3 10 3 70 7 6 6 0 8 7 7 3 9 8 7 6 10 4 8 7 12 0 8 5 12 6 8 9 14 7 9 3 ...

Страница 43: ...13 0 18 8 13 6 22 1 14 2 22 5 15 6 81 11 4 9 2 13 1 11 2 14 7 11 7 15 5 13 4 18 0 13 0 18 8 13 6 21 9 14 1 22 1 15 4 86 11 4 9 2 13 1 11 2 14 7 11 7 15 5 13 4 18 0 13 0 18 8 13 6 21 4 13 9 21 6 15 3 91 11 4 9 2 13 1 11 2 14 7 11 7 15 5 13 4 18 0 13 0 18 8 13 6 21 0 13 7 21 2 15 1 95 11 4 9 2 13 1 11 2 14 7 11 7 15 5 13 4 18 0 13 0 18 8 13 6 20 6 13 6 20 8 15 0 99 11 4 9 2 13 1 11 2 14 7 11 7 15 5 ...

Страница 44: ... 7 25 9 20 0 30 0 19 7 31 4 20 7 36 9 21 7 37 5 23 6 81 19 0 14 0 21 8 16 9 24 5 17 7 25 9 20 0 30 0 19 7 31 4 20 7 36 5 21 6 36 8 23 3 86 19 0 14 0 21 8 16 9 24 5 17 7 25 9 20 0 30 0 19 7 31 4 20 7 35 7 21 3 36 1 23 0 91 19 0 14 0 21 8 16 9 24 5 17 7 25 9 20 0 30 0 19 7 31 4 20 7 34 9 21 0 35 3 22 7 95 19 0 14 0 21 8 16 9 24 5 17 7 25 9 20 0 30 0 19 7 31 4 20 7 34 3 20 7 34 7 22 5 99 19 0 14 0 21...

Страница 45: ... 4 39 2 30 6 41 4 35 0 47 2 33 6 47 7 34 6 49 8 33 8 50 4 37 3 Model ARUH60TLAV Outdoor tem perature Indoor temperature 68 FDB 59 FWB 73 FDB 61 FWB 75 FDB 63 FWB 79 FDB 64 FWB 80 FDB 67 FWB 82 FDB 68 FWB 86 FDB 72 FWB 90 FDB 73 FWB FDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 50 38 1 31 6 43 5 38 6 49 0 40 0 51 8 46 0 60 0 44 3 62 8 46 6 73 7 48 4 76 5 53 9 59 38 1 31 6 43 5 38 6 49...

Страница 46: ...100 4 67 4 118 0 70 7 119 9 76 9 81 60 9 45 6 69 7 55 0 78 4 57 6 82 9 65 4 96 0 64 2 100 4 67 4 116 7 70 2 117 9 76 1 86 60 9 45 6 69 7 55 0 78 4 57 6 82 9 65 4 96 0 64 2 100 4 67 4 114 2 69 2 115 4 75 2 91 60 9 45 6 69 7 55 0 78 4 57 6 82 9 65 4 96 0 64 2 100 4 67 4 111 8 68 2 112 9 74 2 95 60 9 45 6 69 7 55 0 78 4 57 6 82 9 65 4 96 0 64 2 100 4 67 4 109 8 67 4 110 9 73 4 99 60 9 45 6 69 7 55 0 ...

Страница 47: ...8 5 1 7 9 5 6 Model AGUA9TLAV1 Outdoor tem perature Indoor temperature 68 FDB 59 FWB 73 FDB 61 FWB 75 FDB 63 FWB 79 FDB 64 FWB 80 FDB 67 FWB 82 FDB 68 FWB 86 FDB 72 FWB 90 FDB 73 FWB FDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 50 6 0 4 7 6 9 5 7 7 8 5 9 8 2 6 7 9 5 6 6 9 9 6 9 11 7 7 2 12 1 8 0 59 6 0 4 7 6 9 5 7 7 8 5 9 8 2 6 7 9 5 6 6 9 9 6 9 11 7 7 2 12 1 8 0 70 6 0 4 7 6 9 5 7 ...

Страница 48: ... 12 1 10 2 14 0 9 9 14 6 10 4 17 2 10 8 17 5 11 9 81 8 9 7 1 10 2 8 6 11 4 8 9 12 1 10 2 14 0 9 9 14 6 10 4 17 0 10 8 17 2 11 8 86 8 9 7 1 10 2 8 6 11 4 8 9 12 1 10 2 14 0 9 9 14 6 10 4 16 7 10 6 16 8 11 7 91 8 9 7 1 10 2 8 6 11 4 8 9 12 1 10 2 14 0 9 9 14 6 10 4 16 3 10 5 16 5 11 5 95 8 9 7 1 10 2 8 6 11 4 8 9 12 1 10 2 14 0 9 9 14 6 10 4 16 0 10 4 16 2 11 4 99 8 9 7 1 10 2 8 6 11 4 8 9 12 1 10 2...

Страница 49: ...door tem perature Indoor temperature 68 FDB 59 FWB 73 FDB 61 FWB 75 FDB 63 FWB 79 FDB 64 FWB 80 FDB 67 FWB 82 FDB 68 FWB 86 FDB 72 FWB 90 FDB 73 FWB FDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 50 11 4 9 8 13 1 12 0 14 7 12 4 15 5 14 3 18 0 13 7 18 8 14 4 22 1 14 9 23 0 16 7 59 11 4 9 8 13 1 12 0 14 7 12 4 15 5 14 3 18 0 13 7 18 8 14 4 22 1 14 9 23 0 16 7 70 11 4 9 8 13 1 12 0 14 7 ...

Страница 50: ...9 7 24 5 20 4 25 9 23 5 29 5 22 4 29 8 23 1 31 1 22 6 31 5 25 1 Model ABUA36TLAV2 Outdoor tem perature Indoor temperature 68 FDB 59 FWB 73 FDB 61 FWB 75 FDB 63 FWB 79 FDB 64 FWB 80 FDB 67 FWB 82 FDB 68 FWB 86 FDB 72 FWB 90 FDB 73 FWB FDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 50 22 8 18 1 26 1 22 0 29 4 22 9 31 1 26 1 36 0 25 4 37 7 26 6 44 2 27 8 45 9 30 8 59 22 8 18 1 26 1 22 0 ...

Страница 51: ... 5 8 7 9 6 4 Model ASUA9TLAV1 Outdoor tem perature Indoor temperature 68 FDB 59 FWB 73 FDB 61 FWB 75 FDB 63 FWB 79 FDB 64 FWB 80 FDB 67 FWB 82 FDB 68 FWB 86 FDB 72 FWB 90 FDB 73 FWB FDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 50 6 0 5 5 6 9 6 8 7 8 7 0 8 2 8 2 9 5 7 8 9 9 8 2 11 7 8 4 12 1 9 5 59 6 0 5 5 6 9 6 8 7 8 7 0 8 2 8 2 9 5 7 8 9 9 8 2 11 7 8 4 12 1 9 5 70 6 0 5 5 6 9 6 8 7...

Страница 52: ...18 7 12 9 18 9 14 2 Model ASUB24TLAV1 Outdoor tem perature Indoor temperature 68 FDB 59 FWB 73 FDB 61 FWB 75 FDB 63 FWB 79 FDB 64 FWB 80 FDB 67 FWB 82 FDB 68 FWB 86 FDB 72 FWB 90 FDB 73 FWB FDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 50 15 2 12 2 17 4 14 9 19 6 15 5 20 7 17 7 24 0 17 2 25 1 18 0 29 5 18 8 30 6 20 9 59 15 2 12 2 17 4 14 9 19 6 15 5 20 7 17 7 24 0 17 2 25 1 18 0 29 5...

Страница 53: ...7 5 6 0 7 8 5 9 7 9 6 5 Model ASUA12TLAV Outdoor tem perature Indoor temperature 68 FDB 59 FWB 73 FDB 61 FWB 75 FDB 63 FWB 79 FDB 64 FWB 80 FDB 67 FWB 82 FDB 68 FWB 86 FDB 72 FWB 90 FDB 73 FWB FDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC 50 7 6 6 0 8 7 7 3 9 8 7 6 10 4 8 7 12 0 8 4 12 6 8 9 14 7 9 2 15 3 10 2 59 7 6 6 0 8 7 7 3 9 8 7 6 10 4 8 7 12 0 8 4 12 6 8 9 14 7 9 2 15 3 10 2 7...

Страница 54: ... 24 0 17 1 25 1 18 0 29 5 18 7 30 0 20 6 81 15 2 12 2 17 4 14 9 19 6 15 4 20 7 17 7 24 0 17 1 25 1 18 0 29 2 18 6 29 5 20 4 86 15 2 12 2 17 4 14 9 19 6 15 4 20 7 17 7 24 0 17 1 25 1 18 0 28 6 18 4 28 9 20 2 91 15 2 12 2 17 4 14 9 19 6 15 4 20 7 17 7 24 0 17 1 25 1 18 0 27 9 18 2 28 2 20 0 95 15 2 12 2 17 4 14 9 19 6 15 4 20 7 17 7 24 0 17 1 25 1 18 0 27 5 18 0 27 7 19 8 99 15 2 12 2 17 4 14 9 19 6...

Страница 55: ... 8 17 0 15 0 7 1 7 1 7 0 7 0 7 0 7 0 7 0 23 0 21 2 7 9 7 9 7 8 7 8 7 8 7 7 7 7 26 6 24 8 8 3 8 3 8 2 8 2 8 2 8 2 7 8 30 2 28 4 8 7 8 7 8 6 8 6 8 6 8 5 7 8 32 0 30 2 9 0 8 9 8 8 8 8 8 8 8 5 7 8 35 6 33 8 9 4 9 3 9 3 9 2 9 0 8 5 7 8 41 0 39 2 10 1 10 1 9 9 9 5 9 1 8 6 7 9 47 0 43 0 10 6 10 5 9 9 9 5 9 1 8 6 7 9 48 2 46 0 10 9 10 6 9 9 9 5 9 1 8 6 7 9 53 6 51 1 11 1 10 6 9 9 9 5 9 1 8 6 7 9 59 0 56 3...

Страница 56: ...7 4 16 2 15 6 15 0 14 1 12 9 Model AUUA18TLAV2 Outdoor temperature Indoor temperature 61 FDB 64 FDB 68 FDB 70 FDB 72 FDB 75 FDB 79 FDB FDB FWB TC TC TC TC TC TC TC 2 7 4 0 10 4 10 4 10 4 10 3 10 3 10 3 10 3 5 0 3 2 12 1 12 0 12 0 11 9 11 9 11 9 11 9 10 4 8 6 13 4 13 4 13 3 13 3 13 2 13 2 13 2 15 8 14 0 14 7 14 6 14 6 14 6 14 5 14 4 14 4 17 0 15 0 15 0 14 9 14 8 14 8 14 8 14 7 14 6 23 0 21 2 16 6 1...

Страница 57: ... 19 9 19 8 19 8 23 0 21 2 22 4 22 3 22 2 22 1 22 1 22 0 21 9 26 6 24 8 23 6 23 5 23 3 23 3 23 3 23 2 22 1 30 2 28 4 24 8 24 7 24 5 24 4 24 4 24 1 22 1 32 0 30 2 25 5 25 3 25 1 25 0 25 0 24 1 22 1 35 6 33 8 26 7 26 5 26 3 26 2 25 6 24 1 22 1 41 0 39 2 28 7 28 6 28 0 27 0 25 9 24 4 22 3 47 0 43 0 30 1 29 9 28 0 27 0 25 9 24 4 22 3 48 2 46 0 31 1 30 1 28 0 27 0 25 9 24 4 22 3 53 6 51 1 31 6 30 1 28 0...

Страница 58: ... 1 59 0 56 3 46 8 44 5 41 5 40 0 38 4 36 1 33 1 Model AUUB48TLAV2 Outdoor temperature Indoor temperature 61 FDB 64 FDB 68 FDB 70 FDB 72 FDB 75 FDB 79 FDB FDB FWB TC TC TC TC TC TC TC 2 7 4 0 28 1 28 1 28 1 27 9 27 9 27 9 27 8 5 0 3 2 32 5 32 4 32 4 32 2 32 2 32 2 32 0 10 4 8 6 36 3 36 1 35 9 35 9 35 8 35 8 35 6 15 8 14 0 39 7 39 5 39 4 39 4 39 2 39 0 38 8 17 0 15 0 40 4 40 2 40 0 39 9 39 9 39 7 39...

Страница 59: ... 19 9 19 8 19 8 23 0 21 2 22 4 22 3 22 2 22 1 22 1 22 0 21 9 26 6 24 8 23 6 23 5 23 3 23 3 23 3 23 2 22 1 30 2 28 4 24 8 24 7 24 5 24 4 24 4 24 1 22 1 32 0 30 2 25 5 25 3 25 1 25 0 25 0 24 1 22 1 35 6 33 8 26 7 26 5 26 3 26 2 25 6 24 1 22 1 41 0 39 2 28 7 28 6 28 0 27 0 25 9 24 4 22 3 47 0 43 0 30 1 29 9 28 0 27 0 25 9 24 4 22 3 48 2 46 0 31 1 30 1 28 0 27 0 25 9 24 4 22 3 53 6 51 1 31 6 30 1 28 0...

Страница 60: ...4 29 3 23 0 21 2 33 2 33 1 32 9 32 8 32 7 32 6 32 4 26 6 24 8 35 0 34 8 34 6 34 6 34 4 34 3 32 7 30 2 28 4 36 7 36 6 36 3 36 2 36 2 35 7 32 7 32 0 30 2 37 7 37 5 37 2 37 1 37 0 35 7 32 7 35 6 33 8 39 5 39 2 39 0 38 9 38 0 35 7 32 7 41 0 39 2 42 5 42 4 41 5 40 0 38 4 36 1 33 1 47 0 43 0 44 5 44 3 41 5 40 0 38 4 36 1 33 1 48 2 46 0 46 1 44 5 41 5 40 0 38 4 36 1 33 1 53 6 51 1 46 8 44 5 41 5 40 0 38 ...

Страница 61: ...15 0 3 3 3 3 3 3 3 2 3 2 3 2 3 2 23 0 21 2 3 7 3 6 3 6 3 6 3 6 3 6 3 6 26 6 24 8 3 8 3 8 3 8 3 8 3 8 3 8 3 6 30 2 28 4 4 0 4 0 4 0 4 0 4 0 3 9 3 6 32 0 30 2 4 2 4 1 4 1 4 1 4 1 3 9 3 6 35 6 33 8 4 3 4 3 4 3 4 3 4 2 3 9 3 6 41 0 39 2 4 7 4 7 4 6 4 4 4 2 4 0 3 6 47 0 43 0 4 9 4 9 4 6 4 4 4 2 4 0 3 6 48 2 46 0 5 1 4 9 4 6 4 4 4 2 4 0 3 6 53 6 51 1 5 1 4 9 4 6 4 4 4 2 4 0 3 6 59 0 56 3 5 1 4 9 4 6 4 4...

Страница 62: ...9 0 8 9 8 9 8 9 8 8 26 6 24 8 9 5 9 5 9 4 9 4 9 4 9 4 8 9 30 2 28 4 10 0 10 0 9 9 9 9 9 9 9 7 8 9 32 0 30 2 10 3 10 2 10 1 10 1 10 1 9 7 8 9 35 6 33 8 10 8 10 7 10 6 10 6 10 3 9 7 8 9 41 0 39 2 11 6 11 6 11 3 10 9 10 5 9 8 9 0 47 0 43 0 12 1 12 1 11 3 10 9 10 5 9 8 9 0 48 2 46 0 12 6 12 1 11 3 10 9 10 5 9 8 9 0 53 6 51 1 12 8 12 1 11 3 10 9 10 5 9 8 9 0 59 0 56 3 12 8 12 1 11 3 10 9 10 5 9 8 9 0 M...

Страница 63: ...3 18 3 17 4 16 2 15 6 15 0 14 1 12 9 Model ARUL18TLAV2 Outdoor temperature Indoor temperature 61 FDB 64 FDB 68 FDB 70 FDB 72 FDB 75 FDB 79 FDB FDB FWB TC TC TC TC TC TC TC 2 7 4 0 10 4 10 4 10 4 10 3 10 3 10 3 10 3 5 0 3 2 12 1 12 0 12 0 11 9 11 9 11 9 11 9 10 4 8 6 13 4 13 4 13 3 13 3 13 2 13 2 13 2 15 8 14 0 14 7 14 6 14 6 14 6 14 5 14 4 14 4 17 0 15 0 15 0 14 9 14 8 14 8 14 8 14 7 14 6 23 0 21 ...

Страница 64: ... 25 1 25 0 24 9 23 0 21 2 28 2 28 1 28 0 27 9 27 8 27 7 27 6 26 6 24 8 29 7 29 6 29 4 29 4 29 3 29 2 27 8 30 2 28 4 31 2 31 1 30 9 30 8 30 8 30 4 27 8 32 0 30 2 32 1 31 9 31 6 31 5 31 4 30 4 27 8 35 6 33 8 33 6 33 4 33 1 33 0 32 3 30 4 27 8 41 0 39 2 36 1 36 0 35 3 34 0 32 6 30 7 28 1 47 0 43 0 37 9 37 6 35 3 34 0 32 6 30 7 28 1 48 2 46 0 39 1 37 9 35 3 34 0 32 6 30 7 28 1 53 6 51 1 39 8 37 9 35 3...

Страница 65: ... 39 9 39 7 39 5 23 0 21 2 44 8 44 6 44 5 44 3 44 1 43 9 43 8 26 6 24 8 47 2 47 0 46 7 46 7 46 5 46 3 44 1 30 2 28 4 49 6 49 4 49 1 48 9 48 9 48 2 44 1 32 0 30 2 50 9 50 6 50 3 50 1 49 9 48 2 44 1 35 6 33 8 53 3 53 0 52 6 52 5 51 3 48 2 44 1 41 0 39 2 57 4 57 2 56 0 54 0 51 8 48 7 44 6 47 0 43 0 60 1 59 8 56 0 54 0 51 8 48 7 44 6 48 2 46 0 62 2 60 1 56 0 54 0 51 8 48 7 44 6 53 6 51 1 63 2 60 1 56 0...

Страница 66: ...90 2 84 1 81 0 77 7 73 1 66 9 Model ARUH96TLAV2 Outdoor temperature Indoor temperature 61 FDB 64 FDB 68 FDB 70 FDB 72 FDB 75 FDB 79 FDB FDB FWB TC TC TC TC TC TC TC 2 7 4 0 56 2 56 2 56 2 55 9 55 9 55 9 55 5 5 0 3 2 65 1 64 7 64 7 64 4 64 4 64 4 64 1 10 4 8 6 72 6 72 2 71 9 71 9 71 5 71 5 71 2 15 8 14 0 79 4 79 0 78 7 78 7 78 4 78 0 77 7 17 0 15 0 80 7 80 4 80 1 79 7 79 7 79 4 79 0 23 0 21 2 89 6 ...

Страница 67: ...0 7 0 7 0 23 0 21 2 7 9 7 9 7 8 7 8 7 8 7 7 7 7 26 6 24 8 8 3 8 3 8 2 8 2 8 2 8 2 7 8 30 2 28 4 8 7 8 7 8 6 8 6 8 6 8 5 7 8 32 0 30 2 9 0 8 9 8 8 8 8 8 8 8 5 7 8 35 6 33 8 9 4 9 3 9 3 9 2 9 0 8 5 7 8 41 0 39 2 10 1 10 1 9 9 9 5 9 1 8 6 7 9 47 0 43 0 10 6 10 5 9 9 9 5 9 1 8 6 7 9 48 2 46 0 10 9 10 6 9 9 9 5 9 1 8 6 7 9 53 6 51 1 11 1 10 6 9 9 9 5 9 1 8 6 7 9 59 0 56 3 11 1 10 6 9 9 9 5 9 1 8 6 7 9 ...

Страница 68: ...59 0 56 3 15 8 15 0 14 0 13 5 12 9 12 2 11 2 Model AGUA14TLAV1 Outdoor temperature Indoor temperature 61 FDB 64 FDB 68 FDB 70 FDB 72 FDB 75 FDB 79 FDB FDB FWB TC TC TC TC TC TC TC 2 7 4 0 8 1 8 1 8 1 8 1 8 1 8 1 8 0 5 0 3 2 9 4 9 4 9 4 9 3 9 3 9 3 9 3 10 4 8 6 10 5 10 4 10 4 10 4 10 3 10 3 10 3 15 8 14 0 11 5 11 4 11 4 11 4 11 3 11 3 11 2 17 0 15 0 11 7 11 6 11 6 11 5 11 5 11 5 11 4 23 0 21 2 12 9...

Страница 69: ...1 2 12 9 12 9 12 8 12 8 12 7 12 7 12 6 26 6 24 8 13 6 13 6 13 5 13 5 13 4 13 4 12 7 30 2 28 4 14 3 14 3 14 2 14 1 14 1 13 9 12 7 32 0 30 2 14 7 14 6 14 5 14 5 14 4 13 9 12 7 35 6 33 8 15 4 15 3 15 2 15 2 14 8 13 9 12 7 41 0 39 2 16 6 16 5 16 2 15 6 15 0 14 1 12 9 47 0 43 0 17 4 17 3 16 2 15 6 15 0 14 1 12 9 48 2 46 0 18 0 17 4 16 2 15 6 15 0 14 1 12 9 53 6 51 1 18 3 17 4 16 2 15 6 15 0 14 1 12 9 5...

Страница 70: ...19 8 23 0 21 2 22 4 22 3 22 2 22 1 22 1 22 0 21 9 26 6 24 8 23 6 23 5 23 3 23 3 23 3 23 2 22 1 30 2 28 4 24 8 24 7 24 5 24 4 24 4 24 1 22 1 32 0 30 2 25 5 25 3 25 1 25 0 25 0 24 1 22 1 35 6 33 8 26 7 26 5 26 3 26 2 25 6 24 1 22 1 41 0 39 2 28 7 28 6 28 0 27 0 25 9 24 4 22 3 47 0 43 0 30 1 29 9 28 0 27 0 25 9 24 4 22 3 48 2 46 0 31 1 30 1 28 0 27 0 25 9 24 4 22 3 53 6 51 1 31 6 30 1 28 0 27 0 25 9 ...

Страница 71: ...4 0 32 6 30 7 28 1 59 0 56 3 39 8 37 9 35 3 34 0 32 6 30 7 28 1 Model ABUA36TLAV2 Outdoor temperature Indoor temperature 61 FDB 64 FDB 68 FDB 70 FDB 72 FDB 75 FDB 79 FDB FDB FWB TC TC TC TC TC TC TC 2 7 4 0 20 8 20 8 20 8 20 7 20 7 20 7 20 6 5 0 3 2 24 1 24 0 24 0 23 8 23 8 23 8 23 7 10 4 8 6 26 9 26 8 26 6 26 6 26 5 26 5 26 4 15 8 14 0 29 4 29 3 29 1 29 1 29 0 28 9 28 8 17 0 15 0 29 9 29 8 29 7 2...

Страница 72: ...0 7 0 7 0 23 0 21 2 7 9 7 9 7 8 7 8 7 8 7 7 7 7 26 6 24 8 8 3 8 3 8 2 8 2 8 2 8 2 7 8 30 2 28 4 8 7 8 7 8 6 8 6 8 6 8 5 7 8 32 0 30 2 9 0 8 9 8 8 8 8 8 8 8 5 7 8 35 6 33 8 9 4 9 3 9 3 9 2 9 0 8 5 7 8 41 0 39 2 10 1 10 1 9 9 9 5 9 1 8 6 7 9 47 0 43 0 10 6 10 5 9 9 9 5 9 1 8 6 7 9 48 2 46 0 10 9 10 6 9 9 9 5 9 1 8 6 7 9 53 6 51 1 11 1 10 6 9 9 9 5 9 1 8 6 7 9 59 0 56 3 11 1 10 6 9 9 9 5 9 1 8 6 7 9 ...

Страница 73: ... 17 4 16 2 15 6 15 0 14 1 12 9 Model ASUB18TLAV1 Outdoor temperature Indoor temperature 61 FDB 64 FDB 68 FDB 70 FDB 72 FDB 75 FDB 79 FDB FDB FWB TC TC TC TC TC TC TC 2 7 4 0 10 4 10 4 10 4 10 3 10 3 10 3 10 3 5 0 3 2 12 1 12 0 12 0 11 9 11 9 11 9 11 9 10 4 8 6 13 4 13 4 13 3 13 3 13 2 13 2 13 2 15 8 14 0 14 7 14 6 14 6 14 6 14 5 14 4 14 4 17 0 15 0 15 0 14 9 14 8 14 8 14 8 14 7 14 6 23 0 21 2 16 6...

Страница 74: ...7 5 27 3 17 0 15 0 28 4 28 3 28 2 28 1 28 1 27 9 27 8 23 0 21 2 31 5 31 4 31 3 31 2 31 0 30 9 30 8 26 6 24 8 33 2 33 1 32 8 32 8 32 7 32 6 31 0 30 2 28 4 34 9 34 8 34 5 34 4 34 4 33 9 31 0 32 0 30 2 35 8 35 6 35 4 35 2 35 1 33 9 31 0 35 6 33 8 37 5 37 3 37 0 36 9 36 1 33 9 31 0 41 0 39 2 40 4 40 3 39 4 38 0 36 4 34 3 31 4 47 0 43 0 42 3 42 1 39 4 38 0 36 4 34 3 31 4 48 2 46 0 43 8 42 3 39 4 38 0 3...

Страница 75: ...16 6 16 5 16 5 16 4 16 3 16 3 16 2 26 6 24 8 17 5 17 4 17 3 17 3 17 2 17 2 16 3 30 2 28 4 18 4 18 3 18 2 18 1 18 1 17 9 16 3 32 0 30 2 18 9 18 7 18 6 18 5 18 5 17 9 16 3 35 6 33 8 19 7 19 6 19 5 19 4 19 0 17 9 16 3 41 0 39 2 21 3 21 2 20 8 20 0 19 2 18 0 16 5 47 0 43 0 22 3 22 1 20 8 20 0 19 2 18 0 16 5 48 2 46 0 23 0 22 3 20 8 20 0 19 2 18 0 16 5 53 6 51 1 23 4 22 3 20 8 20 0 19 2 18 0 16 5 59 0 ...

Страница 76: ...9 5 08 50 64 2 3 31 73 4 3 70 82 5 4 10 87 1 4 30 100 8 4 89 105 4 5 09 111 5 5 09 112 9 5 08 59 64 2 3 42 73 4 3 83 82 5 4 24 87 1 4 45 100 8 5 06 104 9 5 24 110 5 5 21 112 0 5 21 70 64 2 3 64 73 4 4 08 82 5 4 52 87 1 4 74 100 8 5 57 102 1 5 60 106 8 5 69 108 0 5 71 73 64 2 3 71 73 4 4 16 82 5 4 62 87 1 4 85 99 4 5 77 100 6 5 79 105 2 5 88 106 4 5 90 77 64 2 3 83 73 4 4 30 82 5 4 77 87 1 5 11 97 ...

Страница 77: ...5 6 35 78 0 7 78 78 9 7 81 82 7 7 93 83 6 7 96 109 50 5 4 61 57 7 5 52 64 8 6 57 68 5 7 16 75 3 8 16 76 2 8 19 79 8 8 31 80 8 8 35 115 50 5 5 26 57 7 6 35 64 8 7 60 68 4 8 31 70 9 8 35 71 6 8 35 74 7 8 35 75 5 8 35 72 0 100 5 45 9 2 51 52 4 2 80 58 9 3 08 62 2 3 22 72 0 3 64 75 3 3 79 88 4 4 35 91 6 4 49 14 45 9 2 51 52 4 2 80 58 9 3 08 62 2 3 22 72 0 3 64 75 3 3 79 88 4 4 35 91 6 4 49 23 45 9 2 5...

Страница 78: ...12 52 7 4 37 61 8 5 45 64 1 5 75 109 32 1 3 02 36 7 3 37 41 3 3 72 43 6 3 90 50 4 4 60 52 7 4 88 61 8 6 12 64 1 6 47 115 32 1 3 31 36 7 3 70 41 3 4 10 43 6 4 35 50 4 5 25 52 7 5 59 61 8 7 06 64 1 7 47 43 2 60 5 27 5 1 72 31 4 1 89 35 4 2 06 37 3 2 14 43 2 2 40 45 2 2 48 53 0 2 82 55 0 2 91 14 27 5 1 72 31 4 1 89 35 4 2 06 37 3 2 14 43 2 2 40 45 2 2 48 53 0 2 82 55 0 2 91 23 27 5 1 72 31 4 1 89 35 ...

Страница 79: ... 5 8 35 91 6 8 35 92 6 8 35 95 7 8 35 96 8 8 35 101 0 8 35 102 0 8 35 109 82 0 8 35 84 0 8 35 85 9 8 35 86 9 8 35 89 9 8 35 90 9 8 35 94 9 8 35 96 0 8 35 115 75 7 8 35 77 5 8 35 79 4 8 35 80 3 8 35 83 2 8 35 84 1 8 35 88 0 8 35 89 0 8 35 124 8 130 5 79 5 4 42 90 9 4 92 102 2 5 42 107 9 5 67 124 8 6 42 130 5 6 67 147 5 7 29 149 4 7 28 14 79 5 4 42 90 9 4 92 102 2 5 42 107 9 5 67 124 8 6 42 130 5 6 ...

Страница 80: ... 5 35 69 9 6 10 78 6 7 12 83 0 7 68 89 7 8 35 90 6 8 35 94 5 8 35 95 5 8 35 109 61 2 5 75 69 9 6 79 78 6 7 95 81 6 8 35 84 4 8 35 85 3 8 35 89 0 8 35 90 0 8 35 115 61 2 6 51 69 9 7 73 74 8 8 35 75 7 8 35 78 3 8 35 79 2 8 35 82 8 8 35 83 7 8 35 86 4 90 5 55 1 3 35 62 9 3 69 70 7 4 04 74 7 4 21 86 4 4 73 90 4 4 90 106 0 5 59 110 0 5 77 14 55 1 3 35 62 9 3 69 70 7 4 04 74 7 4 21 86 4 4 73 90 4 4 90 1...

Страница 81: ...6 3 56 60 2 3 68 70 7 4 16 73 3 4 28 70 36 7 2 73 41 9 2 98 47 2 3 24 49 8 3 37 57 6 3 76 60 2 3 89 70 7 4 40 73 3 4 53 73 36 7 2 77 41 9 3 03 47 2 3 30 49 8 3 43 57 6 3 83 60 2 3 96 70 7 4 49 73 3 4 62 77 36 7 2 84 41 9 3 11 47 2 3 38 49 8 3 52 57 6 3 93 60 2 4 07 70 7 4 62 73 3 4 75 81 36 7 2 91 41 9 3 20 47 2 3 48 49 8 3 63 57 6 4 05 60 2 4 19 70 7 4 76 73 3 4 90 86 36 7 3 02 41 9 3 32 47 2 3 6...

Страница 82: ...61 102 7 8 61 104 0 8 61 107 6 8 61 108 8 8 61 113 7 8 61 115 0 8 61 109 91 6 8 61 93 8 8 61 96 0 8 61 97 2 8 61 100 7 8 61 101 9 8 61 106 6 8 61 107 7 8 61 115 84 1 8 61 86 3 8 61 88 5 8 61 89 5 8 61 92 8 8 61 93 9 8 61 98 4 8 61 99 5 8 61 156 0 130 5 99 4 5 54 113 6 6 15 127 7 6 76 134 8 7 07 156 0 7 98 163 1 8 29 183 4 8 98 185 8 8 97 14 99 4 5 54 113 6 6 15 127 7 6 76 134 8 7 07 156 0 7 98 163...

Страница 83: ... 67 87 4 7 58 96 7 8 61 97 9 8 61 101 2 8 61 102 3 8 61 106 8 8 61 108 0 8 61 109 76 5 7 16 87 4 8 42 90 7 8 61 91 8 8 61 95 0 8 61 96 0 8 61 100 3 8 61 101 4 8 61 115 76 5 8 09 81 7 8 61 83 7 8 61 84 7 8 61 87 8 8 61 88 8 8 61 92 9 8 61 94 0 8 61 108 0 90 5 68 8 4 22 78 6 4 64 88 4 5 06 93 4 5 28 108 0 5 91 112 9 6 12 132 5 6 97 137 5 7 18 14 68 8 4 22 78 6 4 64 88 4 5 06 93 4 5 28 108 0 5 91 112...

Страница 84: ...89 62 2 4 04 72 0 4 48 75 3 4 62 88 3 5 21 91 6 5 36 70 45 9 3 46 52 4 3 77 58 9 4 09 62 2 4 25 72 0 4 72 75 3 4 88 88 3 5 51 91 6 5 67 73 45 9 3 51 52 4 3 84 58 9 4 16 62 2 4 32 72 0 4 81 75 3 4 97 88 3 5 62 91 6 5 78 77 45 9 3 60 52 4 3 93 58 9 4 27 62 2 4 43 72 0 4 94 75 3 5 10 88 3 5 77 91 6 5 94 81 45 9 3 69 52 4 4 04 58 9 4 39 62 2 4 56 72 0 5 08 75 3 5 26 88 3 5 95 91 6 6 13 86 45 9 3 82 52...

Страница 85: ... 1 7 96 113 4 7 59 108 7 7 23 101 7 6 70 92 3 6 01 48 2 46 0 126 3 7 86 125 3 8 08 118 1 7 62 113 4 7 27 108 7 6 92 101 7 6 41 92 3 5 76 53 6 51 1 133 4 8 14 127 4 7 75 118 1 7 08 113 4 6 75 108 7 6 43 101 7 5 96 92 3 5 35 59 0 56 3 134 5 7 67 127 4 7 19 118 1 6 56 113 4 6 26 108 7 5 96 101 7 5 53 92 3 4 96 105 3 130 2 7 4 0 68 2 5 27 67 9 5 51 67 6 5 84 67 4 6 00 67 3 6 17 67 0 6 41 66 6 6 73 5 0...

Страница 86: ... 9 7 15 75 9 6 60 72 9 6 32 69 9 6 05 65 4 5 65 59 3 5 13 26 6 24 8 86 5 7 22 81 9 6 82 75 9 6 29 72 9 6 03 69 9 5 77 65 4 5 39 59 3 4 89 30 2 28 4 86 5 6 88 81 9 6 49 75 9 5 99 72 9 5 74 69 9 5 49 65 4 5 13 59 3 4 65 32 0 30 2 86 5 6 71 81 9 6 33 75 9 5 84 72 9 5 60 69 9 5 36 65 4 5 00 59 3 4 54 35 6 33 8 86 5 6 38 81 9 6 02 75 9 5 55 72 9 5 32 69 9 5 10 65 4 4 76 59 3 4 32 41 0 39 2 86 5 5 91 81...

Страница 87: ... 6 2 51 53 6 51 1 57 6 3 30 54 6 3 13 50 6 2 92 48 6 2 81 46 6 2 71 43 6 2 55 39 6 2 35 59 0 56 3 57 6 3 07 54 6 2 92 50 6 2 72 48 6 2 63 46 6 2 53 43 6 2 39 39 6 2 20 40 5 50 2 7 4 0 48 0 5 52 45 5 5 25 42 2 4 88 40 5 4 70 38 8 4 53 36 3 4 26 33 0 3 90 5 0 3 2 48 0 5 17 45 5 4 91 42 2 4 57 40 5 4 40 38 8 4 23 36 3 3 98 33 0 3 65 10 4 8 6 48 0 4 87 45 5 4 63 42 2 4 31 40 5 4 15 38 8 3 99 36 3 3 75...

Страница 88: ... 20 103 0 8 38 102 3 8 64 101 4 9 00 26 6 24 8 110 4 7 61 109 7 7 88 108 7 8 23 108 3 8 41 107 8 8 59 107 0 8 85 106 0 9 21 30 2 28 4 115 6 7 82 114 8 8 09 113 8 8 44 113 3 8 62 112 7 8 80 112 0 9 06 110 9 9 41 32 0 30 2 118 2 7 93 117 4 8 20 116 4 8 55 115 8 8 72 115 3 8 90 114 5 9 16 113 3 9 52 35 6 33 8 123 6 8 14 122 8 8 41 121 6 8 76 121 0 8 93 120 5 9 11 119 6 9 37 114 3 9 18 41 0 39 2 131 9...

Страница 89: ... 7 09 23 0 21 2 100 5 9 32 97 1 9 12 90 0 8 42 86 4 8 07 82 8 7 73 77 5 7 22 70 3 6 56 26 6 24 8 102 5 9 21 97 1 8 70 90 0 8 03 86 4 7 70 82 8 7 38 77 5 6 89 70 3 6 25 30 2 28 4 102 5 8 78 97 1 8 29 90 0 7 66 86 4 7 34 82 8 7 03 77 5 6 57 70 3 5 96 32 0 30 2 102 5 8 57 97 1 8 09 90 0 7 47 86 4 7 16 82 8 6 86 77 5 6 41 70 3 5 82 35 6 33 8 102 5 8 16 97 1 7 70 90 0 7 11 86 4 6 82 82 8 6 53 77 5 6 10...

Страница 90: ...56 2 5 27 54 0 5 07 51 8 4 88 48 4 4 58 44 0 4 19 26 6 24 8 64 0 5 70 60 7 5 41 56 2 5 03 54 0 4 84 51 8 4 66 48 4 4 38 44 0 4 01 30 2 28 4 64 0 5 44 60 7 5 16 56 2 4 80 54 0 4 62 51 8 4 44 48 4 4 17 44 0 3 83 32 0 30 2 64 0 5 31 60 7 5 04 56 2 4 68 54 0 4 51 51 8 4 34 48 4 4 08 44 0 3 74 35 6 33 8 64 0 5 05 60 7 4 80 56 2 4 46 54 0 4 30 51 8 4 13 48 4 3 89 44 0 3 57 41 0 39 2 64 0 4 70 60 7 4 46 ...

Страница 91: ... 2 10 52 26 6 24 8 130 7 9 01 129 8 9 30 128 5 9 68 127 9 9 87 127 2 10 07 126 3 10 36 124 9 10 74 30 2 28 4 137 0 9 23 136 0 9 52 134 6 9 91 133 9 10 10 133 2 10 29 132 2 10 58 130 8 10 96 32 0 30 2 140 2 9 35 139 2 9 63 137 8 10 02 137 0 10 21 136 3 10 40 135 3 10 69 133 8 11 07 35 6 33 8 146 8 9 57 145 6 9 86 144 1 10 24 143 4 10 43 142 6 10 62 141 5 10 91 139 9 11 29 41 0 39 2 156 8 9 90 155 6...

Страница 92: ...0 51 107 9 10 88 107 4 11 07 103 5 10 73 96 8 10 07 87 9 9 22 23 0 21 2 118 5 10 75 117 6 11 03 112 5 10 78 108 0 10 38 103 5 9 97 96 8 9 37 87 9 8 58 26 6 24 8 123 8 11 06 121 4 11 11 112 5 10 32 108 0 9 93 103 5 9 54 96 8 8 96 87 9 8 21 30 2 28 4 128 1 11 19 121 4 10 62 112 5 9 86 108 0 9 49 103 5 9 12 96 8 8 57 87 9 7 86 32 0 30 2 128 1 10 94 121 4 10 37 112 5 9 64 108 0 9 28 103 5 8 92 96 8 8 ...

Страница 93: ... 70 3 7 06 67 5 6 82 64 7 6 59 60 5 6 24 54 9 5 78 26 6 24 8 80 1 7 56 75 9 7 22 70 3 6 77 67 5 6 54 64 7 6 32 60 5 5 99 54 9 5 56 30 2 28 4 80 1 7 24 75 9 6 91 70 3 6 48 67 5 6 27 64 7 6 06 60 5 5 75 54 9 5 34 32 0 30 2 80 1 7 08 75 9 6 76 70 3 6 35 67 5 6 14 64 7 5 94 60 5 5 63 54 9 5 23 35 6 33 8 80 1 6 78 75 9 6 48 70 3 6 08 67 5 5 89 64 7 5 69 60 5 5 41 54 9 5 03 41 0 39 2 80 1 6 35 75 9 6 07...

Страница 94: ...5 1 Stand alone 02 72 5 Heating capacity table Outdoor unit MODEL SELECTION MODEL SELECTION ...

Страница 95: ...3 OUTDOOR UNITS 2019 03 07 DV_CH03_J3LU061EF_01 ...

Страница 96: ...2RLAVL and AOU96RLAVL 03 13 5 2 Model AOU120RLAVL 03 14 5 3 Symbol description 03 15 6 Wiring diagrams 03 16 6 1 Models AOU72RLAVL and AOU96RLAVL 03 16 6 2 Model AOU120RLAVL 03 17 7 Operation range 03 18 7 1 Outdoor unit 03 18 7 2 Indoor unit 03 18 8 Operation noise sound pressure 03 19 8 1 Noise level curve 03 19 8 2 Sound level check point 03 20 9 Electrical characteristics 03 21 9 1 Stand alone...

Страница 97: ...and alone Lineup from 6 ton to 10 ton in 2 ton increments Ton Cooling capacity Btu h Model name 6 72 000 AOU72RLAVL 8 96 000 AOU96RLAVL 10 120 000 AOU120RLAVL 1 1 Stand alone 03 1 1 Model lineup OUTDOOR UNITS OUTDOOR UNITS ...

Страница 98: ...59 62 Heating 55 60 63 Heat exchanger type Length in 50 9 16 mm 1 285 Fin pitch FPI 18 mm 1 45 Rows Stages 3 76 Face area ft2 22 m2 2 1 Pipe type Material Grooved H pin Copper Fin Type Corrugate Aluminum Surface treatment Corrosion resistance Blue fin Compressor Type Q ty Scroll 1 Motor output kW 4 7 6 2 Crankcase heater W 35 35 2 Refrigerant Type R410A Charge lb 24 25 kg 11 0 Refrigerant oil Type...

Страница 99: ...t 2 Refer to Power supply cable in Chapter 6 SYSTEM DESIGN on page 06 50 when selecting the circuit breaker 3 Sound pressure level Measured values in manufacturer s anechoic chamber Because of the surrounding sound environment the sound levels measured in actual installation conditions might be higher than the specified values here 4 Minimum Circuit Ampacity Calculation based on UL1995 5 Maximum C...

Страница 100: ...om view 64 1 2 1 638 A 44 1 8 1 121 47 11 16 1 212 B C Top view 27 1 16 688 7 11 16 196 1 9 16 39 1 5 8 40 5 20 5 16 515 5 7 11 16 196 Terminal blocks Power Terminal blocks Transmission 42 1 2 1 080 15 16 23 5 18 7 8 480 1 9 16 40 1 2 12 17 5 8 447 18 7 8 479 3 1 Stand alone 03 4 3 Dimensions OUTDOOR UNITS OUTDOOR UNITS ...

Страница 101: ...1 7 16 37 3 11 16 94 13 16 20 7 2 3 8 60 6 3 11 16 94 3 Liquid valve 9 9 16 242 6 Liquid valve 11 1 8 282 6 Pipe port Gas 1 11 16 43 1 Liquid 3 1 4 82 5 13 16 20 8 7 11 16 195 6 Cable port Ø1 3 8 34 5 2 3 8 60 6 3 15 16 100 Cable port Ø7 8 22 2 3 10 16 92 9 16 15 3 9 16 90 2 3 8 60 1 2 12 7 3 1 Stand alone 03 5 3 Dimensions OUTDOOR UNITS OUTDOOR UNITS ...

Страница 102: ...nter of gravity position Models AOU72RLAVL AOU96RLAVL and AOU120RLAVL Unit in mm Center of gravity 15 5 8 397 28 13 16 732 28 13 16 732 11 280 3 1 Stand alone 03 6 3 Dimensions OUTDOOR UNITS OUTDOOR UNITS ...

Страница 103: ...on with sufficient space for the refrigerant piping Observe the installation space specifications that are shown in the figures Provide the same space for the air intake at the rear of the outdoor unit If the installation is not performed according to the specifications it could cause a short circuit and result in a lack of operating performance As a result the outdoor unit might easily be stopped...

Страница 104: ...4 80 or more When there are obstacles at the front only When there are obstacles at the front and rear 40 1 000 or more 40 1 000 or more 4 100 or more When there is an obstruction in the upper space Unit in mm When there are obstacles at the rear and above When there are obstacles at the rear sides and above 4 100 or more Max 19 500 40 1 000 or more 60 1 500 or more 4 80 or more 8 200 or more 12 3...

Страница 105: ...he following ex ample when an obstruction is present also in the upward area When the upper space is open Unit in mm When there are obstacles at the rear only When there are obstacles at the front only 12 300 or more 60 1 500 or more When there are obstacles at the front and rear 20 500 or more 60 1 500 or more When there is an obstruction in the upper space Unit in mm When there are obstacles at ...

Страница 106: ... temperature is 32 F 0 C or less do not use the accessory drain pipe and drain cap If the drain pipe and drain cap are used the drain water in the pipe may freeze in extremely cold climate For reverse cycle model only In area with heavy snowfall if the inlet and outlet of the outdoor unit is blocked with snow it might become difficult to get warm and it is likely to cause product malfunction Const...

Страница 107: ...ed the panel cannot be opened for servicing Screw holes for installing the duct are placed on the front panel Fix the duct by using a Ø5 mm tapping screw Refer to following diagram for the location Models AOU72RLAVL AOU96RLAVL and AOU120RLAVL Unit in mm Front panel Top panel Service panel X1 X1 X1 X2 X2 X2 60 1 2 1 536 59 1 16 1 500 44 5 16 1 125 29 1 2 750 14 3 4 375 2 15 16 74 5 20 5 16 516 10 9...

Страница 108: ... example Models AOU72RLAVL AOU96RLAVL and AOU120RLAVL Detail A Front panel Detail A Do not cover the Service panel Service panel Service panel 4 2 Duct installation 03 12 4 Installation space OUTDOOR UNITS OUTDOOR UNITS ...

Страница 109: ...H23 TH23 TH21 TH22 Check valve Capillary Strainer 3 way valve Service port Pressure regulation valve Outdoor unit FAN1 FAN2 TH5 TH3 EEV1 EEV2 TH9 TH7 HPS LPS TH4 SV1 HPSW TH1 TH10 OS CMP INV ACM Liquid line Gas line SCHEX HEX FP Fuse plug FP 5 1 Models AOU72RLAVL and AOU96RLAVL 03 13 5 Refrigerant circuit OUTDOOR UNITS OUTDOOR UNITS ...

Страница 110: ...21 TH22 Check valve Capillary Strainer 3 way valve Service port Pressure regulation valve Outdoor unit FAN1 FAN2 TH5 TH3 EEV1 EEV2 TH9 TH7 HPS LPS TH4 SV1 HPSW TH1 TH10 OS CMP INV ACM Liquid line Gas line SCHEX HEX FP Fuse plug FP 5 2 Model AOU120RLAVL 03 14 5 Refrigerant circuit OUTDOOR UNITS OUTDOOR UNITS ...

Страница 111: ...d valve 1 TH1 Discharge temperature thermistor Blue TH3 Outdoor temperature thermistor TH4 Suction temperature thermistor Red TH5 Heat exchanger outlet thermistor Brown TH7 Liquid temperature thermistor Green TH9 Sub cool heat exchanger outlet thermistor White TH10 Compressor temperature thermistor Indoor unit Symbol Description HEX21 Heat exchanger FAN21 Fan EEV21 Electric expansion valve TH21 Ro...

Страница 112: ...6 Wiring diagrams 6 1 Models AOU72RLAVL and AOU96RLAVL 6 1 Models AOU72RLAVL and AOU96RLAVL 03 16 6 Wiring diagrams OUTDOOR UNITS OUTDOOR UNITS ...

Страница 113: ...6 2 Model AOU120RLAVL 6 2 Model AOU120RLAVL 03 17 6 Wiring diagrams OUTDOOR UNITS OUTDOOR UNITS ...

Страница 114: ...door unit the operation tempera ture range is 23 to 115 FDB 5 to 46 CDB 2 The cooling operation range of 5 to 115 FDB 15 to 46 CDB is allowed only when all of the connected indoor units are higher than capacity of 18 000 Btu h 5 3 kW 7 2 Indoor unit Operation mode Operation range Cooling Dry 64 to 90 FDB 18 to 32 CDB R H 80 or less Heating 50 to 86 FDB 10 to 30 CDB R H Relative humidity 7 1 Outdoo...

Страница 115: ...250 500 1 000 2 000 4 000 8 000 Rated Low noise mode level 2 Low noise mode level 1 Model AOU96RLAVL Cooling NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 Rated Low noise mode level 2 Low noise mode level 1 Heating NC 65 NC 60 NC ...

Страница 116: ...C 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 Rated Low noise mode level 2 Low noise mode level 1 8 2 Sound level check point Airflow Microphone Microphone Rear Rear view Side view 40 in 1 m NOTE Detailed shape of the actual outdoor unit might be slightly...

Страница 117: ...he standard condition MCA Minimum Circuit Ampacity Maximum operating current Full load MSC Maximum Starting Current TOCA Total Over Current Ampacity MAX CKT BKR Maximum Circuit Breaker GFEB Ground Fault Equipment Breaker 9 1 Stand alone Ton Model name Power supply 60 Hz 208 230 V Full load characteristics MCA A TOCA A MSC A 6 AOU72RLAVL 38 40 30 6 8 AOU96RLAVL 39 40 31 6 10 AOU120RLAVL 47 50 38 0 ...

Страница 118: ...tion Activate Reset Discharge pipe temperature protection Activate 248 F 120 C Compressor stop Reset 185 F 85 C Compressor restart Compressor temperature protection Activate 266 F 130 C Compressor stop Reset 194 F 90 C Compressor restart High pressure protection Activate 580 psi 4 0 MPa Compressor stop Reset 464 psi 3 2 MPa Compressor restart Low pressure protection Activate 7 25 psi 0 05 MPa Comp...

Страница 119: ...anual 1 9 For outdoor unit drain piping work 1 For outdoor unit drain piping work Joint pipe A 1 For connecting gas pipe L type For AOU72RLAVL AOU96RLAVL only Joint pipe B 1 For connecting gas pipe Straight type For AOU72RLAVL AOU96RLAVL only Joint pipe C 1 For connecting liquid pipe Straight type For AOU72RLAVL AOU96RLAVL only Joint pipe A L 1 For connecting gas pipe L type For AOU120RLAVL only J...

Страница 120: ...11 1 Stand alone 03 24 11 Accessories OUTDOOR UNITS OUTDOOR UNITS ...

Страница 121: ...4 INDOOR UNITS 2019 11 01 DV_CH04_J3LU061EF_02 ...

Страница 122: ... 04 30 4 3 Cassette type 04 33 4 4 Mini duct type 04 36 4 5 Slim duct Slim concealed floor type 04 38 4 6 Medium static pressure duct type 04 42 4 7 High static pressure duct type 04 44 4 8 Compact floor type 04 49 4 9 Floor Ceiling type 04 51 4 10 Ceiling type 04 53 4 11 Wall mounted type 04 55 5 Wiring diagrams 04 67 5 1 Compact cassette type 04 67 5 2 Circular flow cassette type 04 68 5 3 Casse...

Страница 123: ...m concealed floor type 04 170 8 6 Medium static pressure duct type 04 171 8 7 High static pressure duct type 04 171 8 8 Compact floor type 04 172 8 9 Floor Ceiling type 04 173 8 10 Ceiling type 04 174 8 11 Wall mounted type 04 174 9 Noise level curve 04 176 9 1 Compact cassette type 04 176 9 2 Circular flow cassette type 04 178 9 3 Cassette type 04 180 9 4 Mini duct type 04 181 9 5 Slim duct Slim ...

Страница 124: ...nted type 04 197 11 Accessories 04 198 11 1 Compact cassette type 04 198 11 2 Circular flow cassette type 04 199 11 3 Cassette type 04 200 11 4 Mini duct type 04 201 11 5 Slim duct Slim concealed floor type 04 202 11 6 Medium static pressure duct type 04 203 11 7 High static pressure duct type 04 204 11 8 Compact floor type 04 206 11 9 Floor Ceiling type 04 207 11 10 Ceiling type 04 208 11 11 Wall...

Страница 125: ...60 000 72 000 96 000 Model code 4 7 9 12 14 18 24 30 36 36 48 60 72 96 Compact cas sette Circular flow cassette Cassette Mini duct Slim duct Slim concealed floor Medium static pressure duct High static pressure duct Compact floor Floor Ceiling Ceiling Wall mounted 1 1 Indoor units 04 1 1 Model lineup INDOOR UNITS INDOOR UNITS ...

Страница 126: ...Slim duct Slim concealed floor 7 500 9 500 ARUL7TLAV2 7 13 16 27 9 16 24 7 16 198 700 620 9 500 10 900 ARUL9TLAV2 12 000 13 500 ARUL12TLAV2 14 000 15 600 ARUL14TLAV2 18 000 20 000 ARUL18TLAV2 7 13 16 35 7 16 24 7 16 198 900 620 Medium static pressure duct 24 000 27 000 ARUM24TLAV2 10 5 16 44 11 16 27 9 16 270 1 135 700 30 000 34 000 ARUM30TLAV2 36 000 40 000 ARUM36TLAV2 High static pressure duct 3...

Страница 127: ... 16 8 268 840 203 14 000 15 600 ASUA14TLAV1 18 000 20 000 ASUB18TLAV1 12 5 8 39 5 16 9 3 8 320 998 238 24 000 27 000 ASUB24TLAV1 30 000 34 000 ASUA30TLAV2 13 3 8 45 1 4 11 340 1 150 280 34 000 38 000 ASUA36TLAV2 7 500 9 500 ASUA7TLAV 10 13 16 31 1 8 8 7 16 275 790 215 12 000 13 500 ASUA12TLAV 18 000 20 000 ASUB18TLAV 12 5 8 39 5 16 9 320 998 228 24 000 27 000 ASUB24TLAV 1 1 Indoor units 04 3 1 Mod...

Страница 128: ...pe diameter Liquid Flare in mm Ø 1 4 6 35 Gas Flare Ø 3 8 9 52 Drain hose I D Ø 3 4 19 05 O D Ø 1 1 16 26 6 Cassette grille Grid type Option Model name UTG CCGVG Color White Approximate color of Munsell 9PB 9 1 0 2 Dimensions H W D Net in mm 1 15 16 24 7 16 24 7 16 50 620 620 Gross 4 3 4 30 1 8 29 3 4 120 765 755 Weight Net lb kg 5 2 3 Gross 10 4 5 Cassette grille Standard type Option Model name U...

Страница 129: ... 19 44 20 Connection pipe diameter Liquid Flare in mm Ø 1 4 6 35 Ø 3 8 9 52 Gas Flare Ø 1 2 12 70 Ø 5 8 15 88 Drain hose VP25 I D Ø 3 4 19 05 O D Ø 1 1 16 26 6 Cassette grille Grid type Option Model name UTG CCGVG Color White Approximate color of Munsell 9PB 9 1 0 2 Dimensions H W D Net in mm 1 15 16 24 7 16 24 7 16 50 620 620 Gross 4 3 4 30 1 8 29 3 4 120 765 755 Weight Net lb kg 5 2 3 Gross 10 4...

Страница 130: ...40 Gross 11 3 4 37 13 16 37 3 8 298 960 950 Weight Net lb kg 53 24 54 24 5 Gross 64 29 65 29 5 Connection pipe diameter Liquid Flare in mm Ø 1 4 6 35 Ø 3 8 9 52 Gas Flare Ø 1 2 12 70 Ø 5 8 15 88 Drain hose I D Ø 3 4 19 05 O D Ø 1 1 16 26 6 Cassette grille Option Model name UTG LCGVCW Color White Approximate color of Munsell N9 25 Dimensions H W D Net in mm 2 1 16 37 3 8 37 3 8 53 950 950 Gross 4 5...

Страница 131: ...0 Weight Net lb kg 65 29 5 Gross 75 34 Connection pipe diameter Liquid Flare in mm Ø 3 8 9 52 Gas Flare Ø 5 8 15 88 Drain hose VP25 I D Ø 3 4 19 05 O D Ø 1 1 16 26 6 Cassette grille Option Model name UTG LCGVCW Color White Approximate color of Munsell N9 25 Dimensions H W D Net in mm 2 1 16 37 3 8 37 3 8 53 950 950 Gross 4 5 16 39 3 8 39 3 4 110 1 000 1 010 Weight Net lb kg 13 6 0 Gross 22 10 NOTE...

Страница 132: ...ipe diameter Liquid Flare in mm Ø 3 8 9 52 Gas Flare Ø 5 8 15 88 Drain hose I D Ø 3 4 19 05 O D Ø 1 1 16 26 6 Cassette grille Option Model name UTG LCGV Color WhiteApproximate color of Munsell N9 25 Dimensions H W D Net in mm 1 15 16 37 3 8 37 3 8 50 950 950 Gross 4 1 2 40 3 16 39 3 8 115 1 020 1 000 Weight Net lb kg 13 5 5 Gross 19 8 5 NOTES Specifications are based on the following conditions Co...

Страница 133: ...pe diameter Liquid Flare in mm Ø 3 8 9 52 Gas Flare Ø 5 8 15 88 Drain hose VP25 I D Ø 3 4 19 05 O D Ø 1 1 16 26 6 Cassette grille Option Model name UTG LCGV Color WhiteApproximate color of Munsell N9 25 Dimensions H W D Net in mm 1 15 16 37 3 8 37 3 8 50 950 950 Gross 4 1 2 40 3 16 39 3 8 115 1 020 1 000 Weight Net lb kg 13 5 5 Gross 19 8 5 NOTES Specifications are based on the following condition...

Страница 134: ...n Color Dimensions H W D Net in mm 7 13 16 27 9 16 17 11 16 198 700 450 Gross 9 13 16 36 5 8 22 13 16 250 930 580 Weight Net lb kg 32 14 5 Gross 40 18 Connection pipe diameter Liquid Flare in mm Ø 1 4 6 35 Gas Flare Ø 3 8 9 52 Drain hose I D Ø 3 4 19 05 O D Ø 1 1 16 26 6 NOTES Specifications are based on the following conditions Cooling Indoor temperature of 80 FDB 67 FWB 26 7 CDB 19 4 CWB and out...

Страница 135: ... Slit Aluminum Surface treatment Hydrophilic coating Air filter Type Fungicide type Net material PP honeycomb Enclosure Material Galvanized sheet iron Color Dimensions H W D Net in mm 7 13 16 27 9 16 24 7 16 198 700 620 Gross 10 7 8 38 1 8 30 3 8 276 968 772 Weight Net lb kg 37 17 40 18 Gross 46 21 51 23 Connection pipe diameter Liquid Flare in mm Ø 1 4 6 35 Gas Flare Ø 3 8 9 52 Ø 1 2 12 70 Drain ...

Страница 136: ...s H W D Net in mm 7 13 16 35 7 16 24 7 16 198 900 620 Gross 10 7 8 46 30 3 8 276 1 168 772 Weight Net lb kg 49 22 Gross 60 27 Connection pipe diameter Liquid Flare in mm Ø 1 4 6 35 Gas Flare Ø 1 2 12 70 Drain hose VP25 I D Ø 3 4 19 05 O D Ø 1 1 16 26 6 NOTES Specifications are based on the following conditions Cooling Indoor temperature of 80 FDB 67 FWB 26 7 CDB 19 4 CWB and outdoor temperature of...

Страница 137: ...rophilic coating Air filter Option Model name UTD LF25NA Type Fungicide type Net material PP honeycomb Enclosure Material Galvanized sheet iron Color Dimensions H W D Net in mm 10 5 16 44 11 16 27 9 16 270 1 135 700 Gross 11 13 16 51 15 16 31 1 8 300 1 320 790 Weight Net lb kg 86 39 Gross 104 47 Connection pipe diameter Liquid Flare in mm Ø 3 8 9 52 Gas Flare Ø 5 8 15 88 Drain hose I D Ø 3 4 19 05...

Страница 138: ...b Enclosure Material Galvanized sheet iron Color Dimensions H W D Net in mm 15 3 4 41 5 16 19 11 16 400 1 050 500 Gross 18 1 8 48 7 16 25 3 16 460 1 230 640 Weight Net lb kg 97 44 101 46 Gross 108 49 112 51 Connection pipe diameter Liquid Flare in mm Ø 3 8 9 52 Gas Flare Ø 3 4 19 05 Drain hose I D Ø 3 4 19 05 O D Ø 1 1 16 26 6 NOTES Specifications are based on the following conditions Cooling Indo...

Страница 139: ... 1 2 27 9 16 450 1 587 700 Gross 20 1 2 68 7 8 32 1 2 520 1 750 825 Weight Net lb kg 203 92 231 105 Gross 238 108 276 125 Connection pipe Size Liquid in mm Ø 3 8 9 52 Gas Ø 3 4 19 05 Ø 7 8 22 22 Connection method Flare Brazing Drain hose Size in mm I D Ø 3 4 19 05 O D Ø 1 1 16 26 6 NOTES Specifications are based on the following conditions Cooling Indoor temperature of 80 FDB 67 FWB 26 7 CDB 19 4 ...

Страница 140: ...astic Color White Approximate color of Munsell 5Y 9 0 5NN Dimensions H W D Net in mm 23 5 8 29 1 8 7 7 8 600 740 200 Gross 27 9 16 32 5 16 12 3 16 700 820 310 Weight Net lb kg 33 15 Gross 41 18 5 42 19 Connection pipe diameter Liquid Flare in mm Ø 1 4 6 35 Gas Flare Ø 3 8 9 52 Drain hose I D Ø 9 16 13 8 O D Ø 5 8 to 11 16 15 8 to 16 7 NOTES Specifications are based on the following conditions Cool...

Страница 141: ...nsell 5Y 9 0 5NN Dimensions H W D Net in mm 23 5 8 29 1 8 7 7 8 600 740 200 Gross 27 9 16 32 5 16 12 3 16 700 820 310 Weight Net lb kg 33 15 Gross 42 19 Connection pipe diameter Liquid Flare in mm Ø 1 4 6 35 Gas Flare Ø 1 2 12 70 Drain hose I D Ø 9 16 13 8 O D Ø 5 8 to 11 16 15 8 to 16 7 NOTES Specifications are based on the following conditions Cooling Indoor temperature of 80 FDB 67 FWB 26 7 CDB...

Страница 142: ...Type Anti mold Net material PP monofilament net Enclosure Material Plastic Color White Approximate color of Munsell N9 25 Dimensions H W D Net in mm 7 13 16 39 25 13 16 199 990 655 Gross 12 5 8 45 1 4 31 1 8 320 1 150 790 Weight Net lb kg 55 25 57 26 60 27 Gross 77 35 79 36 84 38 Connection pipe diameter Liquid Flare in mm Ø 1 4 6 35 Ø 3 8 9 52 Gas Flare Ø 1 2 12 70 Ø 5 8 15 88 Drain hose I D Ø 3 ...

Страница 143: ...or WhiteApproximate color of Munsell N9 25 Dimensions H W D Net in mm 9 7 16 65 3 8 27 9 16 240 1 660 700 Gross 12 1 2 70 7 8 31 1 8 318 1 800 790 Weight Net lb kg 101 46 106 48 Gross 130 59 134 61 Connection pipe diameter Liquid Flare in mm Ø 3 8 9 52 Gas Flare Ø 5 8 15 88 Drain hose I D Ø 3 4 19 05 O D Ø 1 1 16 26 6 NOTES Specifications are based on the following conditions Cooling Indoor temper...

Страница 144: ...closure Material Plastic Color White Approximate color of Munsell N9 25 Dimensions H W D Net in mm 10 5 16 32 5 16 8 1 8 262 820 206 Gross 10 3 8 34 1 4 12 15 16 263 870 328 Weight Net lb kg 17 7 5 Gross 22 10 Connection pipe diameter Liquid Flare in mm Ø 1 4 6 35 Gas Flare Ø 3 8 9 52 Drain hose I D Ø 9 16 13 8 O D Ø 5 8 to 11 16 15 8 to 16 7 NOTES Specifications are based on the following conditi...

Страница 145: ...ite Approximate color of Munsell N9 25 Dimensions H W D Net in mm 10 9 16 33 1 16 8 268 840 203 Gross 10 3 8 34 13 16 13 1 4 270 884 336 Weight Net lb kg 20 9 Gross 24 11 Connection pipe diameter Liquid Flare in mm Ø 1 4 6 35 Gas Flare Ø 1 2 12 70 Drain hose I D Ø 9 16 13 8 O D Ø 5 8 to 11 16 15 8 to 16 7 NOTES Specifications are based on the following conditions Cooling Indoor temperature of 80 F...

Страница 146: ...mensions H W D Net in mm 12 5 8 39 5 16 9 3 8 320 998 238 Gross 12 5 16 42 15 16 16 7 8 329 1 090 429 Weight Net lb kg 33 15 Gross 42 19 Connection pipe diameter Liquid Flare in mm Ø 1 4 6 35 Ø 3 8 9 52 Gas Flare Ø 1 2 12 70 Ø 5 8 15 88 Drain hose I D Ø 9 16 13 8 O D Ø 5 8 to 11 16 15 8 to 16 7 NOTES Specifications are based on the following conditions Cooling Indoor temperature of 80 FDB 67 FWB 2...

Страница 147: ... Color White Approximate color of Munsell N9 25 Dimensions H W D Net in mm 13 3 8 45 1 4 11 340 1 150 280 Gross 15 5 16 50 17 11 16 405 1 270 450 Weight Net lb kg 40 18 Gross 53 24 Connection pipe diameter Liquid Flare in mm Ø 3 8 9 52 Gas Flare Ø 5 8 15 88 Drain hose I D Ø 9 16 13 8 O D Ø 5 8 to 11 16 15 8 to 16 7 NOTES Specifications are based on the following conditions Cooling Indoor temperatu...

Страница 148: ... 7 16 275 790 215 Gross 11 7 16 32 7 8 13 9 16 290 835 345 Weight Net lb kg 20 9 Gross 26 12 Connection pipe diameter Liquid Flare in mm Ø 1 4 6 35 Gas Flare Ø 1 2 12 70 Drain hose I D Ø 9 16 13 8 O D Ø 5 8 to 11 16 15 8 to 16 7 NOTES Specifications are based on the following conditions Cooling Indoor temperature of 80 FDB 67 FWB 26 7 CDB 19 4 CWB and outdoor temperature of 95 FDB 75 FWB 35 CDB 23...

Страница 149: ...lor of Munsell N9 25 Dimensions H W D Net in mm 12 5 8 39 5 16 9 320 998 228 Gross 12 9 16 42 15 16 16 7 8 319 1 090 429 Weight Net lb kg 33 15 Gross 42 19 Connection pipe diameter Liquid Flare in mm Ø 3 8 9 52 Gas Flare Ø 5 8 15 88 Drain hose I D Ø 1 2 12 O D Ø 5 8 16 NOTES Specifications are based on the following conditions Cooling Indoor temperature of 80 FDB 67 FWB 26 7 CDB 19 4 CWB and outdo...

Страница 150: ...0 21 0 28 Slim duct Slim concealed floor ARUL7TLAV2 0 71 15 44 0 31 0 57 ARUL9TLAV2 0 71 50 0 35 0 57 ARUL12TLAV2 0 71 50 0 38 0 57 ARUL14TLAV2 0 76 92 0 61 0 61 ARUL18TLAV2 0 76 83 0 55 0 61 Medium static pressure duct ARUM24TLAV2 1 10 15 125 0 75 0 88 ARUM30TLAV2 1 40 190 1 12 1 12 ARUM36TLAV2 1 74 222 1 29 1 39 High static pressure duct ARUH36TLAV 2 70 15 496 2 16 2 16 ARUH48TLAV 4 83 752 3 27 ...

Страница 151: ... ASUB18TLAV1 0 53 32 0 33 0 42 ASUB24TLAV1 0 65 60 0 52 0 52 ASUA30TLAV2 0 90 74 0 55 0 72 ASUA36TLAV2 1 18 103 0 72 0 94 ASUA7TLAV 0 51 17 0 17 0 41 ASUA12TLAV 0 51 22 0 20 0 41 ASUB18TLAV 0 53 32 0 33 0 42 ASUB24TLAV 0 65 60 0 52 0 52 MCA Minimum Circuit Ampacity Maximum operating current Full load MAX CKT BKR Maximum Circuit Breaker FLA Full Load Amperes Fan motor This value is Cooling operatio...

Страница 152: ...olt position a Ceiling openings 20 7 8 530 20 7 8 530 Hanging bolt position Drain hose A 8 7 162 215 3 4 19 1 3 16 30 4 13 16 123 1 3 16 30 10 5 16 262 7 3 16 183 Control Box 5 13 16 146 1 9 16 40 C 24 7 16 620 24 7 16 620 IR receiver Grid type grille Standard type grille View B View C 4 1 2 114 a Ceiling openings Cassette grille Standard type in mm 22 13 16 to 26 580 to 660 Grid type 22 13 16 to ...

Страница 153: ...aintenance space To set 3 direction Air outlet shutter plate option must be installed and the outlet direction need to be switched to 3 way by the remote controller 4 100 or more 4 directions 3 directions Piping position In 3 way outlet mode changing of ceiling height setting by function setting 20 is prohibited Ceil ing height setting function setting 20 is allowed to be changed only in 4 way out...

Страница 154: ...ng bolt position Hanging bolt position Indoor unit Drain hose B C Ceiling 7 7 8 to 8 1 16 200 to 205 7 7 8 200 13 7 16 342 1 3 4 45 1 9 16 40 5 8 16 140 10 1 16 256 Wire hole View B View C A Fresh air inlet cut out 9 5 16 237 1 9 16 40 6 7 16 163 3 15 16 100 3 1 4 83 13 7 8 352 6 7 16 163 3 9 16 90 4 Ø1 8 3 2 hole Ø3 3 4 95 3 1 8 80 1 9 16 40 3 1 8 80 3 15 16 100 3 1 4 83 4 2 Circular flow cassett...

Страница 155: ...42 1 9 16 40 5 8 16 140 11 3 4 298 7 7 8 to 8 1 16 200 to 205 3 8 10 1 9 16 39 7 7 8 to 8 1 16 200 to 205 7 7 8 200 37 3 8 950 11 9 16 293 1 3 4 45 View B View C A 9 5 16 237 1 9 16 40 6 7 16 164 Fresh air inlet cut out 3 15 16 100 3 1 4 83 13 7 8 352 4 5 16 109 6 7 16 164 3 9 16 90 4 Ø1 8 3 2 hole Ø3 3 4 95 3 1 8 80 1 9 16 40 3 1 8 80 3 15 16 100 3 1 4 83 4 2 Circular flow cassette type 04 31 4 D...

Страница 156: ...en installing the indoor unit be careful about the maintenance space To set 3 direction Air outlet shutter plate option must be installed and the outlet direction need to be switched to 3 way by the remote controller 4 100 or more 4 directions 3 directions Piping position In 3 way outlet mode changing of ceiling height setting by function setting 20 is prohibited Ceil ing height setting function s...

Страница 157: ...60 to 910 Ceiling opening 9 13 16 250 1 1 4 31 1 1 4 31 5 5 8 143 Fresh air inlet cut out A 5 9 16 142 5 9 16 142 Ceiling B Control box 7 7 8 200 3 8 10 14 1 8 358 10 15 16 278 2 3 8 60 1 3 4 44 1 9 16 40 Wire hole 5 1 2 140 10 1 16 256 4 5 16 109 3 9 16 90 13 7 8 352 3 1 4 83 3 1 4 83 3 15 16 100 3 15 16 100 5 5 8 143 C View B View C Drain hose 4 Ø1 8 2 5 hole Ø2 3 4 70 2 7 16 62 2 7 16 62 4 3 Ca...

Страница 158: ...ing bolt position 33 7 8 to 35 13 16 860 to 910 Ceiling opening Drain hose 5 9 16 142 5 9 16 142 7 7 8 200 3 8 10 14 1 8 358 10 15 16 278 2 3 8 60 1 3 4 44 1 9 16 40 5 1 2 140 11 3 4 298 9 13 16 250 1 1 4 31 1 1 4 31 Fresh air inlet cut out 4 5 16 109 3 9 16 90 13 7 8 352 3 1 4 83 3 1 4 83 3 15 16 100 3 15 16 100 7 5 16 185 View C View B 4 Ø1 8 2 5 hole Ø2 3 4 70 2 7 16 62 2 7 16 62 4 3 Cassette t...

Страница 159: ...ion notices When installing the indoor unit be careful about the maintenance space To set 3 direction Air outlet shutter plate option must be installed and the outlet direction need to be switched to 3 way by the remote controller 4 100 or more 4 directions 3 directions Piping position In 3 way outlet mode changing of ceiling height setting by function setting 20 is prohibited Ceil ing height sett...

Страница 160: ...6 49 3 5 8 92 3 1 16 78 6 5 8 169 2 3 16 56 2 5 8 66 3 3 8 85 P 3 15 16 6 23 5 8 P 100 6 600 A 11 5 8 295 7 13 16 198 6 5 8 168 5 7 8 150 3 1 16 78 2 1 4 57 3 8 10 1 3 16 30 5 7 8 150 7 3 16 182 7 5 8 193 17 11 16 450 1 3 16 30 6 153 2 13 16 72 2 1 16 52 Rear view Top view Front view Bottom view Side view View A 4 4 Mini duct type 04 36 4 Dimensions INDOOR UNITS INDOOR UNITS ...

Страница 161: ...6 5 or more 13 16 20 or more 11 13 16 300 or more Air When intaking air from bottom 3 15 16 100 or more Air Maintenance space requirement For future maintenance and service access provide sufficient maintenance space NOTE Do not place any wiring or illumination in the maintenance space as they will impede ser vice Unit in mm Top view Service access Air Air Control box 15 3 4 400 or more 3 15 16 10...

Страница 162: ... 6 152 3 15 16 100 x 6 23 5 8 600 3 7 32 82 1 7 8 48 25 9 16 650 28 7 8 734 1 3 16 30 14 13 16 377 6 9 16 167 4 11 16 119 3 1 2 89 3 1 16 78 2 3 16 55 1 7 8 47 3 8 10 24 7 16 620 14 5 8 371 10 3 8 264 5 11 16 144 2 11 16 69 25 9 16 650 26 1 8 664 27 9 16 700 1 11 16 43 13 16 20 7 13 16 198 6 5 8 168 5 15 16 151 3 1 16 78 2 3 16 55 4 5 Slim duct Slim concealed floor type 04 38 4 Dimensions INDOOR U...

Страница 163: ... 36 3 4 934 3 15 16 100 8 31 1 2 800 1 3 16 30 14 13 16 377 6 9 16 167 4 11 16 119 3 1 2 89 3 1 16 78 2 3 16 55 1 7 8 47 3 8 10 24 7 16 620 14 5 8 371 10 3 8 264 5 11 16 144 2 11 16 69 33 7 16 850 34 864 35 7 16 900 1 11 16 43 13 16 20 7 13 16 198 6 5 8 168 5 15 16 151 3 1 16 78 2 3 16 55 A 4 5 Slim duct Slim concealed floor type 04 39 4 Dimensions INDOOR UNITS INDOOR UNITS ...

Страница 164: ...cealed installations 1 10 or less 1 10 or less Left side Strong and durable floor Right side Pipe side Grille Inlet air Strong and durable floor 6 150 or more 6 150 or more 16 400 or more 6 150 or more 1 20 or more 1 20 or more Left side Strong and durable floor Right side Pipe side Duct Grille Inlet air Strong and durable floor 6 150 or more 6 150 or more 6 150 or more 16 400 or more 1 20 or more...

Страница 165: ...e space NOTE Do not place any wiring or illumination in the maintenance space as they will impede ser vice Unit in mm Top view 12 300 or more Service space 4 100 or more 16 400 or more Service access Air Indoor unit Air 4 5 Slim duct Slim concealed floor type 04 41 4 Dimensions INDOOR UNITS INDOOR UNITS ...

Страница 166: ...le 4 Ø1 8 3 2 P C D Ø8 7 8 225 3 1 8 80 3 1 8 80 4 3 4 121 Bolt pitch 46 5 16 1 177 Bolt pitch 18 3 4 477 6 13 16 173 Hole 8 Ø3 16 5 P4 15 16 125 3 14 3 4 375 P4 15 16 125 3 14 3 4 375 4 3 4 120 2 3 16 107 39 15 16 1 015 44 11 16 1 135 1 9 16 39 2 1 8 54 4 1 2 114 2 5 8 66 1 1 4 32 7 8 21 8 27 9 16 700 7 8 21 8 1 9 16 40 6 5 8 168 9 7 16 240 11 1 16 281 11 1 8 283 6 11 16 170 1 5 16 34 9 7 16 240 ...

Страница 167: ...maintenance space NOTE Do not place any wiring or illumination in the maintenance space as they will impede ser vice Unit in mm It shall be possible to install and remove the con trol box Top view 20 500 or more Air Air 4 100 20 500 or more Service access Indoor unit 12 300 or more It shall be possible to install and remove the con trol box fan units and filter Top view 12 300 or more 62 1 550 or ...

Страница 168: ...3 8 1 000 Inlet dimension 33 15 16 862 Outlet dimension 33 1 2 851 Drain port 12 Ø1 8 3 4 15 16 126 P4 3 4 120 5 23 5 8 600 41 5 16 1 050 3 3 8 85 19 11 16 500 23 1 16 585 Air Outlet dimension 11 5 8 295 14 5 8 371 14 356 8 3 16 208 4 1 4 108 1 5 8 41 4 13 16 123 5 1 2 139 15 3 4 400 12 3 4 324 9 16 14 Inlet dimension 6 1 8 155 4 15 16 125 4 7 High static pressure duct type 04 44 4 Dimensions INDO...

Страница 169: ...ess provide sufficient maintenance space NOTE Do not place any wiring or illumination in the maintenance space as they will impede ser vice Unit in mm Service access Service space 20 500 12 300 or more Air Air 20 500 or more 2 30 or more Indoor unit Top view 12 300 or more 4 7 High static pressure duct type 04 45 4 Dimensions INDOOR UNITS INDOOR UNITS ...

Страница 170: ...1 250 P5 7 8 150 7 41 5 16 1 050 Outlet dimension 47 1 4 1 200 57 1 16 1 450 2 15 16 75 4 15 16 125 4 5 8 117 5 7 8 149 Ø1 8 3 1 1 2 38 1 5 8 42 8 15 16 227 12 1 4 311 15 7 8 404 16 13 16 427 27 9 16 700 Bolt pitch 25 11 16 653 1 25 1 25 1 15 16 50 1 15 16 50 5 16 8 1 1 8 29 Rear view Side view L Top view Side view R Front view Airflow Main drain port Safety drain port 4 7 High static pressure duc...

Страница 171: ...1 250 P5 7 8 150 7 41 5 16 1 050 Outlet dimension 47 1 4 1 200 57 1 16 1 450 2 15 16 75 4 15 16 125 4 5 8 117 5 7 8 149 Ø1 8 3 1 1 2 38 1 5 8 42 8 15 16 227 12 1 4 311 15 7 8 404 16 13 16 427 27 9 16 700 Bolt pitch 25 11 16 653 1 25 1 25 1 15 16 50 1 15 16 50 5 16 8 1 1 8 29 Rear view Side view L Top view Side view R Front view Airflow Main drain port Safety drain port 4 7 High static pressure duc...

Страница 172: ...ong and durable ceiling Maintenance hole Service space 18 450 or more 1 20 or more Maintenance space requirement For future maintenance and service access provide sufficient maintenance space NOTE Do not place any wiring or illumination in the maintenance space as they will impede ser vice Unit in mm 36 890 or more 28 700 or more 2 30 or more 59 1 490 20 500 or more 8 200 or more Control box Air A...

Страница 173: ...Unit in mm 29 1 8 740 21 5 8 550 7 7 8 200 23 5 8 600 8 11 16 220 6 5 16 160 5 1 16 129 3 7 8 98 29 1 8 740 21 5 8 550 23 5 8 600 2 5 16 59 9 9 16 243 9 9 16 243 Ø2 9 16 65 Ø 2 9 16 65 15 16 24 Ø11 16 16 7 1 7 8 48 2 5 16 59 4 8 Compact floor type 04 49 4 Dimensions INDOOR UNITS INDOOR UNITS ...

Страница 174: ...tlet Lower air outlet 1 to 2 20 to 30 Indoor unit Grating Wall cap 2 50 or more 4 80 or more 4 100 or more 4 80 or more 6 150 or below from the floor 4 100 or more 4 80 or more 4 80 or more 4 8 Compact floor type 04 50 4 Dimensions INDOOR UNITS INDOOR UNITS ...

Страница 175: ...7 8 175 7 7 8 200 20 7 8 530 25 13 16 655 3 15 16 100 1 1 8 28 7 13 16 199 29 3 16 742 4 7 8 124 2 1 2 63 1 5 8 42 1 1 16 27 3 15 16 100 6 3 8 162 3 7 8 98 3 1 8 80 2 5 8 67 2 13 16 72 2 5 16 58 2 3 16 56 1 13 16 46 13 16 20 3 15 16 100 3 15 16 100 Side view Rear view Bottom view Hole Ø1 3 4 45 Hole for lifting bolt Use M10 screw bolt 4 9 Floor Ceiling type 04 51 4 Dimensions INDOOR UNITS INDOOR U...

Страница 176: ...655 20 7 8 530 1 3 4 45 2 9 16 65 19 11 16 500 9 5 8 245 39 990 2 9 16 65 Wall bracket Side of set Ceiling Left Indoor unit Right 6 150 or more 12 300 or more Left Right 12 300 or more 12 300 or more Ceiling Floor 91 2 300 or more 1 20 or more 4 9 Floor Ceiling type 04 52 4 Dimensions INDOOR UNITS INDOOR UNITS ...

Страница 177: ...6 100 3 7 16 88 6 1 2 165 3 1 4 82 5 5 16 135 6 5 16 160 5 7 8 150 5 3 8 137 2 9 16 65 6 5 16 160 4 5 8 118 7 15 16 202 11 11 16 300 5 1 8 130 3 3 4 96 27 9 16 700 6 5 16 160 7 9 16 192 Knock out hole fresh air Ø7 7 8 200 Knock out hole refrigerant pipe Knock out hole drain outlet Ø1 15 16 50 Hole for lifting bolt Use M10 screw bolt 4 10 Ceiling type 04 53 4 Dimensions INDOOR UNITS INDOOR UNITS ...

Страница 178: ... 1 3 16 30 Suspension bolt pitch 63 1 600 Indoot unit Top view Dimensions Space required for Installation 3 8 10 6 1 8 155 11 13 16 300 Indoor unit Suspension bolt should extend outward 1 3 16 to 2 15 16 30 to 75 Floor 1 10 or more Floor 99 2 500 or more 99 2 500 or more 6 150 or more 4 80 or more 4 10 Ceiling type 04 54 4 Dimensions INDOOR UNITS INDOOR UNITS ...

Страница 179: ...6 5 12 5 16 312 12 5 8 321 3 9 16 91 3 3 4 96 1 7 8 48 14 355 13 9 16 345 2 13 16 72 32 5 16 820 10 5 16 262 32 5 16 820 10 5 16 262 8 1 8 206 1 8 3 16 15 16 431 19 3 16 487 26 9 16 675 15 16 24 Ø11 16 16 7 1 2 12 1 3 4 44 1 15 16 49 1 15 16 49 3 8 10 4 11 Wall mounted type 04 55 4 Dimensions INDOOR UNITS INDOOR UNITS ...

Страница 180: ... Installation space requirement Unit in mm 4 80 or more 3 70 or more Outline of unit 8 200 or more 60 1 500 or more 71 1 800 or more 4 11 Wall mounted type 04 56 4 Dimensions INDOOR UNITS INDOOR UNITS ...

Страница 181: ...6 840 16 1 8 410 16 15 16 430 12 3 16 310 11 5 8 295 10 9 16 268 8 1 2 216 1 5 16 34 8 1 4 209 2 15 16 74 for pipe inlet Ø2 9 16 65 12 5 8 321 12 3 8 315 7 178 9 3 16 233 5 11 16 144 6 1 2 165 Liquid pipe 15 381 for pipe inlet Ø2 9 16 65 4 11 Wall mounted type 04 57 4 Dimensions INDOOR UNITS INDOOR UNITS ...

Страница 182: ... requirement Unit in mm 1 25 or more 3 70 or more 5 122 or more 8 200 or more 3 62 or more 4 80 or more 60 1 500 or more 71 1 800 or more Outline of unit 4 11 Wall mounted type 04 58 4 Dimensions INDOOR UNITS INDOOR UNITS ...

Страница 183: ...6 46 17 1 4 438 2 3 8 61 4 102 15 5 8 397 17 432 2 3 16 56 2 3 16 56 3 8 10 12 5 8 320 11 16 17 Ø3 1 8 80 hole Piping inlet Ø3 1 8 80 hole Piping inlet 39 5 16 998 9 238 12 5 8 320 20 1 2 520 23 1 4 590 28 3 8 721 1 25 Ø1 1 4 32 Ø5 8 16 Ø1 2 12 4 11 Wall mounted type 04 59 4 Dimensions INDOOR UNITS INDOOR UNITS ...

Страница 184: ... requirement Unit in mm 2 43 or more 3 60 or more 6 133 or more 1 22 or more 2 50 or more Outline of unit 8 200 or more 60 1 500 or more 71 1 800 or more 4 11 Wall mounted type 04 60 4 Dimensions INDOOR UNITS INDOOR UNITS ...

Страница 185: ...4 1 4 108 19 3 4 502 1 15 16 50 7 16 11 13 3 8 340 Ø 3 1 8 8 0 20 1 2 520 3 9 16 90 13 16 21 2 1 2 64 5 8 16 2 3 8 61 1 15 16 50 Ø 3 1 8 8 0 45 1 4 1 150 11 280 1 8 3 13 3 8 340 24 7 16 621 26 9 16 674 28 9 16 725 Ø11 16 16 7 7 8 22 4 11 Wall mounted type 04 61 4 Dimensions INDOOR UNITS INDOOR UNITS ...

Страница 186: ... requirement Unit in mm 3 63 or more 4 80 or more 5 120 or more 3 59 or more 3 70 or more Outline of unit 8 200 or more 60 1 500 or more 71 1 800 or more 4 11 Wall mounted type 04 62 4 Dimensions INDOOR UNITS INDOOR UNITS ...

Страница 187: ... 470 26 660 20 7 8 530 18 1 2 470 15 16 24 11 16 16 7 8 7 16 215 14 7 16 366 5 14 7 16 366 5 14 7 8 378 16 1 4 412 12 1 2 318 13 1 2 343 10 5 8 270 10 13 16 275 for pipe inlet Ø4 80 or more for pipe inlet Ø4 80 or more 4 11 Wall mounted type 04 63 4 Dimensions INDOOR UNITS INDOOR UNITS ...

Страница 188: ...quirement Unit in mm Outline of indoor unit 2 49 or more 3 60 or more 2 44 or more 4 90 or more 2 45 or more 2 50 or more 71 1 800 or more 60 1 500 or more 4 11 Wall mounted type 04 64 4 Dimensions INDOOR UNITS INDOOR UNITS ...

Страница 189: ...00 Unit size Piping inlet for tapping screw 11 16 x 7 16 18 x 11 hole 11 16 x 7 16 18 x 11 hole 4 13 16 122 6 3 4 172 2 15 16 75 15 1 4 387 6 11 16 170 5 8 16 15 3 4 400 Unit center 4 15 16 126 5 1 4 133 5 1 8 130 4 7 16 113 2 15 16 75 9 9 16 243 9 228 12 5 8 320 20 1 2 520 23 1 4 590 28 3 8 721 ø3 1 8 80 hole Piping inlet 1 3 16 30 1 3 16 30 5 7 8 149 7 3 4 197 10 11 16 272 1 1 8 44 1 2 12 1 2 13...

Страница 190: ...ld belongings under the product Condensa tion dripping from the product might get them wet and may cause damage or malfunction to the property Unit in mm 2 43 or more 3 67 or more 1 22 or more 6 153 or more 2 50 or more Outline of unit 8 200 or more 60 1 500 or more 71 1 800 or more 4 11 Wall mounted type 04 66 4 Dimensions INDOOR UNITS INDOOR UNITS ...

Страница 191: ...ing diagrams 5 1 Compact cassette type Models AUUA4TLAV2 AUUA7TLAV2 AUUA9TLAV2 AUUA12TLAV2 AUUA14TLAV2 AUUA18TLAV2 and AUUA24TLAV2 5 1 Compact cassette type 04 67 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...

Страница 192: ...5 2 Circular flow cassette type Models AUUB18TLAV2 AUUB24TLAV2 AUUB30TLAV2 AUUB36TLAV2 and AUUB48TLAV2 5 2 Circular flow cassette type 04 68 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...

Страница 193: ...5 3 Cassette type Models AUUB18TLAV AUUB24TLAV AUUB30TLAV and AUUB36TLAV 5 3 Cassette type 04 69 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...

Страница 194: ...5 4 Mini duct type Model ARUL4TLAV1 5 4 Mini duct type 04 70 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...

Страница 195: ...5 5 Slim duct Slim concealed floor type Models ARUL7TLAV2 ARUL9TLAV2 ARUL12TLAV2 ARUL14TLAV2 and ARUL18TLAV2 5 5 Slim duct Slim concealed floor type 04 71 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...

Страница 196: ...5 6 Medium static pressure duct type Models ARUM24TLAV2 ARUM30TLAV2 and ARUM36TLAV2 5 6 Medium static pressure duct type 04 72 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...

Страница 197: ...5 7 High static pressure duct type Models ARUH36TLAV ARUH48TLAV and ARUH60TLAV 5 7 High static pressure duct type 04 73 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...

Страница 198: ... Models ARUH72TLAV2 and ARUH96TLAV2 5 7 High static pressure duct type 04 74 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...

Страница 199: ...5 8 Compact floor type Models AGUA4TLAV1 AGUA7TLAV1 AGUA9TLAV1 AGUA12TLAV1 and AGUA14TLAV1 5 8 Compact floor type 04 75 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...

Страница 200: ...5 9 Floor Ceiling type Models ABUA12TLAV2 ABUA14TLAV2 ABUA18TLAV2 and ABUA24TLAV2 5 9 Floor Ceiling type 04 76 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...

Страница 201: ...5 10 Ceiling type Models AUUA4TLAV2 AUUA7TLAV2 AUUA9TLAV2 AUUA12TLAV2 AUUA14TLAV2 AUUA18TLAV2 and AUUA24TLAV2 5 10 Ceiling type 04 77 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...

Страница 202: ...5 11 Wall mounted type Models ASUA4TLAV1 ASUA7TLAV1 and ASUA9TLAV1 5 11 Wall mounted type 04 78 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...

Страница 203: ... Models ASUA12TLAV1 and ASUA14TLAV1 5 11 Wall mounted type 04 79 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...

Страница 204: ... Models ASUB18TLAV1 ASUB24TLAV1 ASUB18TLAV and ASUB24TLAV 5 11 Wall mounted type 04 80 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...

Страница 205: ... Models ASUA30TLAV2 and ASUA36TLAV2 5 11 Wall mounted type 04 81 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...

Страница 206: ... Models ASUA7TLAV and ASUA12TLAV 5 11 Wall mounted type 04 82 5 Wiring diagrams INDOOR UNITS INDOOR UNITS ...

Страница 207: ...0 3 1 0 7 2 0 0 1 2 3 3 1 2 4 4 3 4 2 1 0 1 2 3 4 Unit ft s m s 2 0 5 1 0 25 2 0 5 2 0 5 1 0 25 1 0 25 2 0 5 1 0 25 m 0 3 7 10 10 3 7 13 13 ft m 10 13 7 3 0 3 7 10 13 ft Side view Vertical airflow direction louver Up 0 0 1 1 2 2 3 3 1 2 2 7 4 4 3 1 0 3 1 0 7 2 0 7 2 0 Unit ft s m s 1 0 25 2 0 5 2 0 5 1 0 25 m 0 3 3 7 7 10 10 13 13 ft m 0 3 7 9 ft 6 1 Compact cassette type 04 83 6 Air velocity and ...

Страница 208: ...0 1 2 3 4 1 2 3 4 1 0 25 2 0 5 3 1 0 5 1 5 7 2 0 ft 0 3 7 10 13 3 7 10 13 m 9 8 7 3 0 ft Air temperature distribution Side view Vertical airflow direction louver Down Unit F C m 0 1 2 3 4 1 2 3 4 72 22 75 24 79 26 82 28 86 30 2 7 2 5 m 2 1 0 9 8 ft 7 3 0 ft 0 3 7 10 13 3 7 10 13 6 1 Compact cassette type 04 84 6 Air velocity and temperature distributions INDOOR UNITS INDOOR UNITS ...

Страница 209: ...ft 10 13 7 3 0 3 7 10 13 m m 4 3 2 1 0 2 1 3 4 ft 13 10 7 3 0 7 3 10 13 Unit ft s m s 2 0 5 1 0 25 2 0 5 1 0 25 1 0 25 2 0 5 1 0 25 2 0 5 Side view Vertical airflow direction louver Up m 0 1 1 2 2 3 3 4 4 ft 0 3 3 7 7 10 10 13 13 3 1 0 3 1 0 7 2 0 m 2 0 1 ft 7 0 3 9 2 7 Unit ft s m s 1 0 25 2 0 5 2 0 5 1 0 25 6 1 Compact cassette type 04 85 6 Air velocity and temperature distributions INDOOR UNITS...

Страница 210: ...2 0 m 0 1 1 2 2 3 3 4 4 ft 0 3 3 7 7 10 10 13 13 m 2 7 2 1 ft 8 7 3 0 0 Unit ft s m s Air temperature distribution Side view Vertical airflow direction louver Down 72 22 75 24 79 26 82 28 86 30 m 0 1 1 2 2 3 3 4 4 ft 0 3 3 7 7 10 10 13 13 m 2 5 2 1 0 ft 8 7 3 0 9 2 7 Unit F C 6 1 Compact cassette type 04 86 6 Air velocity and temperature distributions INDOOR UNITS INDOOR UNITS ...

Страница 211: ...1 0 25 2 0 5 1 0 25 2 0 5 2 0 5 1 0 25 1 0 25 2 0 5 4 3 2 1 0 1 2 3 4 Unit ft s m s m 10 13 7 3 0 3 7 10 13 ft m 13 10 7 3 0 3 7 10 13 ft Side view Vertical airflow direction louver Up 3 1 0 3 1 0 7 2 0 2 7 2 1 0 m 9 7 3 0 ft 3 4 2 1 0 1 2 3 4 m 10 13 7 3 0 3 7 10 13 ft Unit ft s m s 1 0 25 1 0 25 2 0 5 2 0 5 6 1 Compact cassette type 04 87 6 Air velocity and temperature distributions INDOOR UNITS...

Страница 212: ... 4 2 1 0 1 2 3 4 m 10 13 7 3 0 3 7 10 13 ft Unit ft s m s 1 0 25 2 0 5 3 1 0 5 1 5 7 2 0 Air temperature distribution Side view Vertical airflow direction louver Down 2 7 2 5 2 1 0 m 9 8 7 3 0 ft 3 4 2 1 0 1 2 3 4 m 10 13 7 3 0 3 7 10 13 ft 72 22 75 24 79 26 82 28 86 30 Unit F C 6 1 Compact cassette type 04 88 6 Air velocity and temperature distributions INDOOR UNITS INDOOR UNITS ...

Страница 213: ...5 2 0 5 2 0 5 1 0 25 1 0 25 2 0 5 Unit ft s m s 3 4 2 1 0 1 2 3 4 m 10 13 7 3 0 3 7 10 13 ft 7 3 0 3 7 4 3 2 1 0 1 2 3 4 m 13 10 10 13 ft Side view Vertical airflow direction louver Up 2 7 2 1 0 m 9 7 3 0 ft 3 4 2 1 0 1 2 3 4 m 10 13 7 3 0 3 7 10 13 ft Unit ft s m s 3 1 0 3 1 0 7 2 0 1 0 25 1 0 25 2 0 5 2 0 5 6 1 Compact cassette type 04 89 6 Air velocity and temperature distributions INDOOR UNITS...

Страница 214: ...7 2 5 2 1 0 m 9 8 7 3 0 ft 3 4 2 1 0 1 2 3 4 m 10 13 7 3 0 3 7 10 13 ft Unit ft s m s Air temperature distribution Side view Vertical airflow direction louver Down 72 22 75 24 79 26 82 28 86 30 2 7 2 5 2 1 0 m 9 8 7 3 0 ft 3 4 2 1 0 1 2 3 4 m 10 13 7 3 0 3 7 10 13 ft Unit F C 6 1 Compact cassette type 04 90 6 Air velocity and temperature distributions INDOOR UNITS INDOOR UNITS ...

Страница 215: ...5 2 0 5 2 0 5 1 0 25 1 0 25 2 0 5 3 4 2 1 0 1 2 3 4 4 3 2 1 0 1 2 3 4 Unit ft s m s m 10 13 7 3 0 3 7 10 13 ft m 13 10 7 3 0 3 7 10 13 ft Side view Vertical airflow direction louver Up 2 7 2 1 0 m 9 7 3 0 ft 3 4 2 1 0 1 2 3 4 m 10 13 7 3 0 3 7 10 13 ft Unit ft s m s 3 1 0 3 1 0 7 2 0 1 0 25 1 0 25 2 0 5 2 0 5 6 1 Compact cassette type 04 91 6 Air velocity and temperature distributions INDOOR UNITS...

Страница 216: ... 2 7 2 5 2 1 0 m 9 8 7 3 0 ft 3 4 2 1 0 1 2 3 4 m 10 13 7 3 0 3 7 10 13 ft Unit ft s m s Air temperature distribution Side view Vertical airflow direction louver Down 72 22 75 24 79 26 82 28 86 30 2 7 2 5 2 1 0 m 9 8 7 3 0 ft 3 4 2 1 0 1 2 3 4 m 10 13 7 3 0 3 7 10 13 ft Unit F C 6 1 Compact cassette type 04 92 6 Air velocity and temperature distributions INDOOR UNITS INDOOR UNITS ...

Страница 217: ...5 2 0 5 2 0 5 1 0 25 1 0 25 2 0 5 3 4 2 1 0 1 2 3 4 4 3 2 1 0 1 2 3 4 Unit ft s m s m 10 13 7 3 0 3 7 10 13 ft m 13 10 7 3 0 3 7 10 13 ft Side view Vertical airflow direction louver Up 2 7 2 1 0 m 9 7 3 0 ft 3 4 2 1 0 1 2 3 4 m 10 13 7 3 0 3 7 10 13 ft Unit ft s m s 3 1 0 3 1 0 7 2 0 1 0 25 1 0 25 2 0 5 2 0 5 6 1 Compact cassette type 04 93 6 Air velocity and temperature distributions INDOOR UNITS...

Страница 218: ... 2 7 2 5 2 1 0 m 9 8 7 3 0 ft 3 4 2 1 0 1 2 3 4 m 10 13 7 3 0 3 7 10 13 ft Unit ft s m s Air temperature distribution Side view Vertical airflow direction louver Down 72 22 75 24 79 26 82 28 86 30 2 7 2 5 2 1 0 m 9 8 7 3 0 ft 3 4 2 1 0 1 2 3 4 m 10 13 7 3 0 3 7 10 13 ft Unit F C 6 1 Compact cassette type 04 94 6 Air velocity and temperature distributions INDOOR UNITS INDOOR UNITS ...

Страница 219: ...7 10 13 ft m 13 10 7 3 0 3 7 10 13 ft 3 1 0 3 1 0 3 1 0 3 1 0 7 2 0 7 2 0 7 2 0 7 2 0 1 0 25 1 0 25 1 0 25 1 0 25 2 0 5 2 0 5 2 0 5 2 0 5 Side view Vertical airflow direction louver Up 2 7 2 1 0 m 9 7 3 0 ft 3 4 2 1 0 1 2 3 4 m 10 13 7 3 0 3 7 10 13 ft Unit ft s m s 3 1 0 3 1 0 7 2 0 1 0 25 1 0 25 2 0 5 2 0 5 6 1 Compact cassette type 04 95 6 Air velocity and temperature distributions INDOOR UNITS...

Страница 220: ... 2 7 2 5 2 1 0 m 9 8 7 3 0 ft 3 4 2 1 0 1 2 3 4 m 10 13 7 3 0 3 7 10 13 ft Unit ft s m s Air temperature distribution Side view Vertical airflow direction louver Down 2 7 2 5 2 1 0 m 9 8 7 3 0 ft 3 4 2 1 0 1 2 3 4 m 10 13 7 3 0 3 7 10 13 ft Unit F C 72 22 75 24 79 26 82 28 86 30 6 1 Compact cassette type 04 96 6 Air velocity and temperature distributions INDOOR UNITS INDOOR UNITS ...

Страница 221: ... 2 0 7 2 0 0 3 7 10 ft 3 7 10 13 20 16 22 22 20 16 13 0 3 7 ft 10 2 0 5 2 0 5 Measuring conditions NOTE Reference data Fan speed Operation mode HIGH HEAT Air velocity distribution Side view Vertical airflow direction louver Position 2 Unit ft s m s 3 1 0 3 1 0 m 3 2 2 1 0 m 1 1 2 2 0 3 3 5 4 4 5 6 6 7 7 7 2 0 7 2 0 0 3 7 10 ft 3 7 10 13 20 16 22 22 20 16 13 0 3 7 ft 10 2 0 5 2 0 5 1 0 25 1 0 25 Si...

Страница 222: ... 0 3 7 ft 10 1 0 25 1 0 25 2 0 5 2 0 5 3 1 0 7 2 0 7 2 0 3 1 0 Measuring conditions NOTE Reference data Fan speed Operation mode HIGH HEAT Air velocity distribution Side view Vertical airflow direction louver Position 2 Unit ft s m s m 3 2 2 1 0 m 1 1 2 2 0 3 3 5 4 4 5 6 6 7 7 0 3 7 10 ft 3 7 10 13 20 16 22 22 20 16 13 0 3 7 ft 10 7 2 0 7 2 0 3 1 0 3 1 0 2 0 5 2 0 5 1 0 25 1 0 25 Side view Vertica...

Страница 223: ...6 6 7 7 0 3 7 10 ft 3 7 10 13 20 16 22 22 20 16 13 0 3 7 ft 10 Measuring conditions NOTE Reference data Fan speed Operation mode HIGH HEAT Air velocity distribution Side view Vertical airflow direction louver Position 2 7 2 0 3 1 0 2 0 5 1 0 25 2 0 5 3 1 0 7 2 0 1 0 25 Unit ft s m s m 3 2 2 1 0 m 1 1 2 2 0 3 3 5 4 4 5 6 6 7 7 0 3 7 10 ft 3 7 10 13 20 16 22 22 20 16 13 0 3 7 ft 10 Side view Vertica...

Страница 224: ... 10 ft 3 7 10 13 20 16 22 22 20 16 13 m 3 2 2 1 0 0 3 7 ft 10 Measuring conditions NOTE Reference data Fan speed Operation mode HIGH HEAT Air velocity distribution Side view Vertical airflow direction louver Position 2 7 2 0 3 1 0 2 0 5 2 0 5 3 1 0 7 2 0 1 0 25 1 0 25 Unit ft s m s m 1 1 2 2 0 3 3 5 4 4 5 6 6 7 7 0 3 7 10 ft 3 7 10 13 20 16 22 22 20 16 13 m 3 2 2 1 0 0 3 7 ft 10 Side view Vertical...

Страница 225: ... 0 0 3 7 ft 10 1 0 25 2 0 5 3 1 0 7 2 0 7 2 0 3 1 0 2 0 5 1 0 25 Measuring conditions NOTE Reference data Fan speed Operation mode HIGH HEAT Air velocity distribution Side view Vertical airflow direction louver Position 2 7 2 0 3 1 0 2 0 5 1 0 25 7 2 0 3 1 0 2 0 5 1 0 25 Unit ft s m s m 1 1 2 2 0 3 3 5 4 4 5 6 6 7 7 0 3 7 10 ft 3 7 10 13 20 16 22 22 20 16 13 m 3 2 2 1 0 0 3 7 ft 10 Side view Verti...

Страница 226: ... 6 8 8 4 4 2 2 0 m m 2 1 0 ft 10 7 3 0 3 1 0 7 2 0 1 0 25 1 0 25 2 0 5 2 0 5 Measuring conditions NOTE Reference data Fan speed Operation mode HIGH HEAT Air velocity distribution Side view Vertical airflow direction louver Down 1 0 25 2 0 5 3 1 0 5 1 5 7 2 0 m 0 1 2 3 ft 0 3 7 10 m 0 1 1 2 2 3 3 4 4 ft 0 3 3 7 7 10 10 13 13 Unit ft s m s Air temperature distribution Side view Vertical airflow dire...

Страница 227: ...t s m s m m 2 1 0 ft 10 7 3 0 3 1 0 7 2 0 1 0 25 1 0 25 2 0 5 2 0 5 Measuring conditions NOTE Reference data Fan speed Operation mode HIGH HEAT Air velocity distribution Side view Vertical airflow direction louver Down m m 0 1 1 2 2 3 3 0 1 2 3 ft 0 3 7 10 4 4 ft 0 3 3 7 7 10 10 13 13 Unit ft s m s 1 0 25 2 0 5 3 1 0 5 1 5 7 2 0 Air temperature distribution Side view Vertical airflow direction lou...

Страница 228: ... 1 0 25 2 0 5 2 0 5 6 6 8 10 10 8 4 4 2 2 0 20 20 26 33 33 26 13 13 7 7 ft 0 m Measuring conditions NOTE Reference data Fan speed Operation mode HIGH HEAT Air velocity distribution Side view Vertical airflow direction louver Down 3 2 m 2 1 0 ft 10 7 3 0 m 0 1 1 2 2 3 3 4 4 ft 0 3 3 7 7 10 10 13 13 Unit ft s m s 1 0 25 2 0 5 3 1 0 5 1 5 7 2 0 Air temperature distribution Side view Vertical airflow ...

Страница 229: ... m 3 2 m 2 1 0 ft 10 7 3 0 Unit ft s m s 3 1 0 7 2 0 1 0 25 1 0 25 2 0 5 2 0 5 Measuring conditions NOTE Reference data Fan speed Operation mode HIGH HEAT Air velocity distribution Side view Vertical airflow direction louver Down 3 2 m 2 1 0 ft 10 7 3 0 m 0 1 1 2 2 3 3 4 4 ft 0 3 3 7 7 10 10 13 13 Unit ft s m s 1 0 25 2 0 5 3 1 0 5 1 5 7 2 0 Air temperature distribution Side view Vertical airflow ...

Страница 230: ... 13 10 7 3 0 ft Top view Vertical airflow direction louver Up Horizontal airflow direction louver Left Right 10 9 8 7 6 5 4 3 2 1 0 m Unit ft s m s 0 1 1 2 2 3 3 4 4 5 m 5 0 3 3 7 7 10 10 13 13 16 ft 16 33 30 26 23 20 16 13 10 7 3 0 ft 2 0 5 2 0 5 3 1 0 3 1 0 7 2 0 7 2 0 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 10 9 8 7 6 5 4 3 2 1 0 m 0 1 2 2 5 3 m...

Страница 231: ...0 26 23 20 16 13 10 7 3 0 ft 10 9 8 7 6 5 4 3 2 1 0 m 0 1 2 2 5 3 m 2 0 5 3 1 0 7 2 0 Air temperature distribution Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center Unit F C 33 30 26 23 20 16 13 10 7 3 0 ft 0 3 7 8 10 ft 10 9 8 7 6 5 4 3 2 1 0 m 0 1 2 2 5 3 m 86 30 82 28 79 26 75 24 72 22 6 4 Mini duct type 04 107 6 Air velocity and temperature distributio...

Страница 232: ...16 20 23 26 30 33 9 10 Top view Vertical airflow direction louver Up Horizontal airflow direction louver Left Right Unit ft s m s ft 0 3 3 7 16 16 13 13 10 10 7 m 0 1 1 2 5 5 4 4 3 3 2 ft 0 3 7 10 13 16 20 23 26 30 33 m 0 1 2 3 4 5 6 7 8 9 10 2 0 5 2 0 5 3 1 0 3 1 0 7 2 0 7 2 0 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center Unit ft s m s 2 0 5 3 1 0 7 2 0...

Страница 233: ...20 23 26 30 33 9 10 ft 0 3 7 8 m 0 1 2 2 5 Unit ft s m s 2 0 5 3 1 0 7 2 0 Air temperature distribution Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center Unit F C 86 30 82 28 79 26 75 24 72 22 m 0 1 2 3 4 5 6 7 8 ft 0 3 7 10 13 16 20 23 26 30 33 9 10 m 0 ft 0 3 7 8 1 2 2 5 6 5 Slim duct Slim concealed floor type 04 109 6 Air velocity and temperature distri...

Страница 234: ...rection louver Up Horizontal airflow direction louver Left Right 2 0 5 2 0 5 3 1 0 3 1 0 7 2 0 7 2 0 Unit ft s m s ft 0 3 3 7 16 16 13 13 10 10 7 m 0 1 1 2 5 5 4 4 3 3 2 ft 0 3 7 10 13 16 20 23 26 30 33 m 0 1 2 3 4 5 6 7 8 9 10 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center Unit ft s m s m 0 1 2 3 4 5 6 7 8 ft 0 3 7 10 13 16 20 23 26 30 33 9 10 ft 0 3 7 8...

Страница 235: ...ft 0 3 7 10 13 16 20 23 26 30 33 9 10 ft 0 3 7 8 m 0 1 2 2 5 Unit ft s m s Air temperature distribution Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 86 30 82 28 79 26 75 24 72 22 Unit F C m 0 1 2 3 4 5 6 7 8 ft 0 3 7 10 13 16 20 23 26 30 33 9 10 m ft 0 3 7 8 0 1 2 2 5 6 5 Slim duct Slim concealed floor type 04 111 6 Air velocity and temperature distri...

Страница 236: ...irection louver Up Horizontal airflow direction louver Left Right 2 0 5 2 0 5 3 1 0 3 1 0 7 2 0 7 2 0 Unit ft s m s ft 0 3 3 7 16 16 13 13 10 10 7 m 0 1 1 2 5 5 4 4 3 3 2 ft 0 3 7 10 13 16 20 23 26 30 33 m 0 1 2 3 4 5 6 7 8 9 10 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 0 5 3 1 0 7 2 0 Unit ft s m s m 0 1 2 3 4 5 6 7 8 ft 0 3 7 10 13 16 20 23 26 30...

Страница 237: ...ft 0 3 7 10 13 16 20 23 26 30 33 9 10 ft 0 3 7 8 m 0 1 2 2 5 Unit ft s m s Air temperature distribution Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 86 30 82 28 79 26 75 24 72 22 Unit F C m 0 1 2 3 4 5 6 7 8 ft 0 3 7 10 13 16 20 23 26 30 33 9 10 ft 0 3 7 8 m 0 1 2 2 5 6 5 Slim duct Slim concealed floor type 04 113 6 Air velocity and temperature distri...

Страница 238: ...irection louver Up Horizontal airflow direction louver Left Right Unit ft s m s ft 0 3 3 7 16 16 13 13 10 10 7 m 0 1 1 2 5 5 4 4 3 3 2 ft 0 3 7 10 13 16 20 23 26 30 33 m 0 1 2 3 4 5 6 7 8 9 10 2 0 5 2 0 5 3 1 0 3 1 0 7 2 0 7 2 0 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 0 5 3 1 0 7 2 0 Unit ft s m s m 0 1 2 3 4 5 6 7 8 ft 0 3 7 10 13 16 20 23 26 30...

Страница 239: ...ft 0 3 7 10 13 16 20 23 26 30 33 9 10 ft 0 3 7 8 m 0 1 2 2 5 Unit ft s m s Air temperature distribution Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center Unit F C ft 0 3 7 10 13 16 20 23 26 30 33 m 0 1 2 3 4 5 6 7 8 9 10 ft 0 3 7 8 m 0 1 2 2 5 86 30 82 28 79 26 75 24 72 22 6 5 Slim duct Slim concealed floor type 04 115 6 Air velocity and temperature distri...

Страница 240: ...irection louver Up Horizontal airflow direction louver Left Right 2 0 5 2 0 5 3 1 0 3 1 0 7 2 0 7 2 0 Unit ft s m s ft 0 3 3 7 16 16 13 13 10 10 7 m 0 1 1 2 5 5 4 4 3 3 2 ft 0 3 7 10 13 16 20 23 26 30 33 m 0 1 2 3 4 5 6 7 8 9 10 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center Unit ft s m s m 0 1 2 3 4 5 6 7 8 ft 0 3 7 10 13 16 20 23 26 30 33 9 10 ft 0 3 7 ...

Страница 241: ...ft 0 3 7 10 13 16 20 23 26 30 33 9 10 ft 0 3 7 8 m 0 1 2 2 5 Unit ft s m s Air temperature distribution Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center Unit F C m 0 1 2 3 4 5 6 7 8 ft 0 3 7 10 13 16 20 23 26 30 33 9 10 ft 0 3 7 8 m 0 1 2 2 5 86 30 82 28 79 26 75 24 72 22 6 5 Slim duct Slim concealed floor type 04 117 6 Air velocity and temperature distri...

Страница 242: ...Horizontal airflow direction louver Left Right Unit ft s m s m 1 2 0 1 2 7 3 0 3 ft 7 m 0 3 1 2 4 ft 3 7 10 13 0 3 1 0 3 1 0 2 0 5 2 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center Unit ft s m s m 2 0 1 3 7 3 0 ft 10 m 0 3 1 2 4 ft 3 7 10 13 0 2 0 5 3 1 0 Side view Vertical airflow direction louver Center Horizontal airflow direction louver Center Unit...

Страница 243: ...izontal airflow direction louver Left Right 3 1 0 2 0 5 2 0 5 3 1 0 Unit ft s m s m 1 2 0 1 2 ft 7 3 0 3 7 m 0 3 1 2 4 ft 3 7 10 13 0 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 0 5 3 1 0 Unit ft s m s m 2 0 1 3 ft 7 3 0 10 m 0 3 1 2 4 ft 3 7 10 13 0 Side view Vertical airflow direction louver Center Horizontal airflow direction louver Center 3 1 0 2...

Страница 244: ...airflow direction louver Left Right 2 0 5 3 1 0 2 0 5 3 1 0 Unit ft s m s m 1 2 0 1 2 7 3 0 3 ft 7 m 0 3 1 2 4 ft 3 7 10 13 0 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 0 5 3 1 0 Unit ft s m s m 2 0 1 3 7 3 0 ft 10 m 0 3 1 2 4 ft 3 7 10 13 0 Side view Vertical airflow direction louver Center Horizontal airflow direction louver Center 2 0 5 3 1 0 Uni...

Страница 245: ...airflow direction louver Left Right 2 0 5 3 1 0 2 0 5 3 1 0 Unit ft s m s m 1 2 0 1 2 7 3 0 3 ft 7 m 0 3 1 2 4 ft 3 7 10 13 0 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 3 1 0 2 0 5 Unit ft s m s m 2 0 1 3 7 3 0 ft 10 m 0 3 1 2 4 ft 3 7 10 13 0 Side view Vertical airflow direction louver Center Horizontal airflow direction louver Center 3 1 0 2 0 5 Uni...

Страница 246: ... 2 3 4 5 6 7 8 9 10 Unit ft s m s 2 0 5 2 0 5 3 1 0 3 1 0 1 0 25 1 0 25 7 2 0 Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center ft 0 3 7 10 m 0 1 2 3 ft 0 3 7 10 13 16 20 23 26 30 33 m 0 1 2 3 4 5 6 7 8 9 10 Unit ft s m s 2 0 5 3 1 0 1 0 25 7 2 0 ft 0 3 7 10 m 0 1 2 3 Unit ft s m s ft 0 3 7 10 13 16 20 m 0 1 2 3 4 5 6 2 0 5 3 1 0 1 0 25 7 2 0 ft 0 3 7 10 m...

Страница 247: ...3 7 10 13 16 20 23 26 30 33 m 0 1 2 3 4 5 6 7 8 9 10 Unit ft s m s Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 0 5 3 1 0 1 0 25 7 2 0 ft 0 3 7 10 m 0 1 2 3 ft 0 3 7 10 13 16 20 23 26 30 33 m 0 1 2 3 4 5 6 7 8 9 10 Unit ft s m s 2 0 5 3 1 0 1 0 25 7 2 0 ft 0 3 7 10 m 0 1 2 3 Unit ft s m s ft 0 3 7 10 13 16 20 m 0 1 2 3 4 5 6 2 0 5 3 1 0 1 0 25 7 2 0...

Страница 248: ...m 0 1 2 3 4 5 6 7 8 9 10 Unit ft s m s ft 0 3 3 7 7 10 10 Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 0 5 3 1 0 1 0 25 7 2 0 ft 0 3 7 10 m 0 1 2 3 ft 0 3 7 10 13 16 20 23 26 30 33 m 0 1 2 3 4 5 6 7 8 9 10 Unit ft s m s 2 0 5 3 1 0 1 0 25 7 2 0 ft 0 3 7 10 m 0 1 2 3 Unit ft s m s ft 0 3 7 10 13 16 20 m 0 1 2 3 4 5 6 2 0 5 3 1 0 1 0 25 7 2 0 ft 0 3 7...

Страница 249: ...Unit ft s m s 2 0 5 2 0 5 3 1 0 3 1 0 1 0 25 1 0 25 7 2 0 Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center m ft 0 0 3 7 10 1 2 3 m ft 0 0 1 3 7 10 13 16 20 23 26 2 3 4 5 6 7 8 30 33 9 10 Unit ft s m s 2 0 5 3 1 0 1 0 25 7 2 0 m ft 0 0 3 7 10 1 2 3 Unit ft s m s m ft 0 0 1 3 7 10 13 16 20 2 3 4 5 6 2 0 5 3 1 0 1 0 25 7 2 0 m ft 0 0 3 7 10 1 2 3 Unit ft s m...

Страница 250: ... 16 20 23 26 30 33 m 0 1 2 3 4 5 6 7 8 9 10 Unit ft s m s Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 0 5 3 1 0 1 0 25 7 2 0 ft 0 3 7 10 m 0 1 2 3 ft 0 3 7 10 13 16 20 23 26 30 33 m 0 1 2 3 4 5 6 7 8 9 10 Unit ft s m s 2 0 5 3 1 0 1 0 25 7 2 0 ft 0 3 7 10 m 0 1 2 3 Unit ft s m s ft 0 3 7 10 13 16 20 m 0 1 2 3 4 5 6 2 0 5 3 1 0 1 0 25 7 2 0 ft 0 3 7...

Страница 251: ... 16 20 23 26 30 33 m 0 1 2 3 4 5 6 7 8 9 10 Unit ft s m s Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 2 0 5 3 1 0 1 0 25 7 2 0 ft 0 3 7 10 m 0 1 2 3 ft 0 3 7 10 13 16 20 23 26 30 33 m 0 1 2 3 4 5 6 7 8 9 10 Unit ft s m s 2 0 5 3 1 0 1 0 25 7 2 0 ft 0 3 7 10 m 0 1 2 3 Unit ft s m s ft 0 3 7 10 13 16 20 m 0 1 2 3 4 5 6 2 0 5 3 1 0 1 0 25 7 2 0 ft 0 3 7...

Страница 252: ...12 14 16 18 Unit ft s m s 3 1 0 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 0 5 1 0 25 7 2 0 ft 0 7 10 3 m 0 2 3 1 ft 0 7 13 20 26 33 39 46 52 59 m 0 2 4 6 8 10 12 14 16 18 Unit ft s m s 3 1 0 ft 0 7 10 3 m 0 2 3 1 ft 0 7 13 20 26 33 39 46 m 0 2 4 6 8 10 12 14 2 0 5 1 0 25 7 2 0 3 1 0 Unit ft s m s 2 0 5 1 0 25 7 2 0 3 1 0 ft 0 7 10 3 m 0 2 3 1 ft 0 ...

Страница 253: ... 14 16 18 Unit ft s m s Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 0 5 1 0 25 7 2 0 3 1 0 ft 0 7 10 3 m 0 2 3 1 ft 0 7 13 20 26 33 39 46 52 59 m 0 2 4 6 8 10 12 14 16 18 Unit ft s m s 2 0 5 1 0 25 7 2 0 3 1 0 ft 0 7 10 3 m 0 2 3 1 ft 0 7 13 20 26 33 39 46 m 0 2 4 6 8 10 12 14 Unit ft s m s 2 0 5 1 0 25 7 2 0 3 1 0 m 0 2 3 1 ft 0 7 13 20 26 33 39 46 ...

Страница 254: ... 1 0 7 2 0 1 0 5 1 0 5 Unit ft s m s 2 1 0 2 3 1 3 7 3 0 3 7 10 10 ft m 3 1 0 7 3 0 10 13 20 16 23 26 ft 2 1 0 3 4 6 5 7 8 m Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center Unit ft s m s 7 3 0 10 ft 7 3 0 10 13 20 16 23 26 ft 6 2 1 0 3 4 5 7 8 m 2 1 0 3 m 3 1 0 7 2 0 1 0 5 Side view Vertical airflow direction louver Down Horizontal airflow direction louver...

Страница 255: ... 1 0 5 3 1 0 1 0 5 Unit ft s m s 2 1 0 1 2 3 3 7 3 0 3 7 10 10 ft m 7 3 0 10 13 20 16 23 26 ft 2 1 0 3 4 6 5 7 8 m Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 3 1 0 7 2 0 1 0 5 Unit ft s m s 2 1 0 3 7 3 0 10 ft 7 3 0 10 13 20 16 23 26 ft 2 1 0 3 4 6 5 7 8 m m Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 3 ...

Страница 256: ... 3 Unit ft s m s 7 3 0 3 7 10 10 ft m 7 3 0 10 13 20 16 23 26 ft 2 1 0 3 4 6 5 7 8 m 2 1 0 7 2 0 1 0 5 2 1 0 1 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center Unit ft s m s 7 3 0 10 ft 2 1 0 3 m 3 1 0 7 2 0 1 0 5 7 3 0 10 13 20 16 23 26 ft 2 1 3 4 6 5 7 8 m 0 Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 3 ...

Страница 257: ...5 1 0 5 3 1 0 Unit ft s m s 2 1 0 1 2 3 3 7 3 0 3 7 10 10 ft m 7 3 0 10 13 20 16 23 30 26 ft 2 1 0 3 4 6 5 7 9 8 m Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 7 2 0 3 1 0 1 0 5 Unit ft s m s 2 1 0 3 7 3 0 10 ft 7 3 0 10 13 20 16 23 30 26 ft 2 1 0 3 4 6 5 7 9 8 m m Side view Vertical airflow direction louver Down Horizontal airflow direction louver Cent...

Страница 258: ...5 1 0 5 3 1 0 Unit ft s m s 2 1 0 1 2 3 3 7 3 0 3 7 10 10 ft m 7 3 0 10 13 20 16 23 30 26 ft 2 1 0 3 4 6 5 7 9 8 m Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 7 2 0 3 1 0 1 0 5 2 1 0 3 Unit ft s m s 7 3 0 10 ft 7 3 0 10 13 20 16 23 30 26 ft 2 1 0 3 4 6 5 7 9 8 m m Side view Vertical airflow direction louver Down Horizontal airflow direction louver Cent...

Страница 259: ...t ft s m s ft 7 3 0 3 7 10 10 2 1 0 1 2 3 3 m 7 3 0 10 13 20 16 23 26 ft 2 1 0 3 4 6 5 7 8 m 7 2 0 3 1 0 3 1 0 1 0 5 1 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 7 2 0 3 1 0 1 0 5 Unit ft s m s 7 3 0 10 13 20 16 23 26 ft 2 1 0 3 4 6 5 7 8 m ft 7 3 0 10 2 1 0 3 m Side view Vertical airflow direction louver Down Horizontal airflow direction louver C...

Страница 260: ...t ft s m s ft 7 3 0 3 7 10 10 2 1 0 1 2 3 3 m 7 3 0 10 13 20 16 23 26 ft 2 1 0 3 4 6 5 7 8 m 7 2 0 3 1 0 3 1 0 1 0 5 1 0 5 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 7 2 0 3 1 0 1 0 5 Unit ft s m s 7 3 0 10 13 20 16 23 26 ft 2 1 0 3 4 6 5 7 8 m ft 7 3 0 10 2 1 0 3 m Side view Vertical airflow direction louver Down Horizontal airflow direction louver C...

Страница 261: ...ection louver Up Horizontal airflow direction louver Left Right 1 0 5 1 0 5 3 1 0 3 1 0 7 2 0 4 1 5 4 1 5 Unit ft s m s 1 2 3 4 0 1 2 3 4 0 3 7 10 13 3 7 10 13 ft m 0 3 7 10 13 16 20 23 26 30 33 36 39 42 45 49 ft 0 1 2 3 4 5 6 7 8 9 10 11 12 13 15 m 14 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 7 2 0 4 1 5 3 1 0 1 0 5 Unit ft s m s 2 1 0 3 7 3 0 10 ft...

Страница 262: ...ection louver Up Horizontal airflow direction louver Left Right 3 1 0 4 1 5 7 2 0 3 1 0 4 1 5 1 0 5 1 0 5 Unit ft s m s 1 2 3 4 0 1 2 3 4 0 3 7 10 13 3 7 10 13 ft m 0 3 7 10 13 16 20 23 26 30 33 36 39 42 45 49 ft 0 1 2 3 4 5 6 7 8 9 10 11 12 13 15 m 14 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 4 1 5 3 1 0 7 2 0 1 0 5 Unit ft s m s 2 1 0 3 7 3 0 10 ft...

Страница 263: ... 25 7 2 0 2 0 5 3 1 0 1 0 25 Unit ft s m s 2 1 0 1 2 7 3 0 3 7 ft m 2 1 0 3 4 6 5 7 8 7 3 0 10 13 20 16 23 26 ft m Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center m 0 ft 0 3 7 8 10 1 2 2 4 3 Unit ft s m s 7 2 0 2 0 5 3 1 0 1 0 25 2 1 0 3 4 6 5 7 8 7 3 0 10 13 20 16 23 26 ft m Side view Vertical airflow direction louver Down Horizontal airflow direction lou...

Страница 264: ... 25 7 2 0 2 0 5 3 1 0 1 0 25 2 1 0 3 4 6 5 7 8 Unit ft s m s 2 1 0 1 2 7 3 0 3 7 ft m 7 3 0 10 13 20 16 23 26 ft m Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 7 2 0 2 0 5 3 1 0 1 0 25 ft 0 3 7 8 10 m 0 1 2 2 4 3 Unit ft s m s 2 1 0 3 4 6 5 7 8 7 3 0 10 13 20 16 23 26 ft m Side view Vertical airflow direction louver Down Horizontal airflow direction lou...

Страница 265: ... lower limit Hi Normal SP Normal SP lower limit Hi SP mode00 Airflow CFM m h 177 235 294 353 External static pressure inWG Pa Available airflow rate range Hi speed 1 0 24 60 0 20 50 0 16 40 0 12 30 0 08 20 0 04 10 0 0 300 400 500 600 Airflow CMF m h Hi SP mode03 Hi SP mode02 Hi Normal SP Hi SP mode00 1 Available airflow rate range when Auto louver grille kit option is installed Fan speed HIGH Vert...

Страница 266: ...ting Capacity 235 294 353 177 300 400 500 600 Airflow CMF m h 0 140 120 100 80 60 40 20 Capacity 177 235 294 353 External static pressure inWG Pa 0 0 0 24 60 0 20 50 0 16 40 0 12 30 0 08 20 0 04 10 300 400 500 600 Airflow CFM m h 7 1 Mini duct type 04 142 7 Fan performance curve INDOOR UNITS INDOOR UNITS ...

Страница 267: ...it Normal SP lower limit Hi SP mode09 Hi Normal SP 1 External static pressure inWG Pa 0 24 60 0 40 100 0 20 50 0 36 90 0 16 40 0 32 80 0 08 20 0 04 10 0 12 30 0 28 70 0 0 0 44 110 700 600 300 400 500 412 353 177 235 294 Available air flow rate range Hi speed Airflow CFM m h Hi SP mode03 Hi SP mode04 Hi SP mode00 Hi SP mode05 Hi SP mode01 Hi SP mode 06 Hi SP mode02 Hi SP mode07 Hi SP mode08 Hi SP m...

Страница 268: ... CFM m h Capacity 60 100 40 80 20 0 120 140 Capacity Heating Capacity 700 600 300 400 500 412 353 177 235 294 Airflow CFM m h Capacity 60 100 40 80 20 0 120 140 7 2 Slim duct Slim concealed floor type 04 144 7 Fan performance curve INDOOR UNITS INDOOR UNITS ...

Страница 269: ...r limit Hi SP mode03 Hi SP mode04 Hi SP mode00 Hi SP mode05 Hi SP mode01 Hi SP mode06 Hi SP mode02 Hi SP mode07 Hi SP mode08 Hi SP mode09 Hi Normal SP 0 24 60 0 40 100 0 20 50 0 36 90 0 16 40 0 32 80 0 08 20 0 04 10 0 12 30 0 28 70 0 0 0 44 110 700 600 300 400 500 800 412 353 177 235 294 471 External static pressure inWG Pa Available air flow rate range Hi speed Airflow CFM m h 1 1 Available airfl...

Страница 270: ...800 412 353 177 235 294 471 Airflow CFM m h Capacity Heating Capacity 700 600 300 400 500 800 412 353 177 235 294 471 Airflow CFM m h 60 100 40 80 20 0 120 140 Capacity 7 2 Slim duct Slim concealed floor type 04 146 7 Fan performance curve INDOOR UNITS INDOOR UNITS ...

Страница 271: ... inWG Pa Hi SP mode03 Hi SP mode04 Hi SP mode00 Hi SP mode05 Hi SP mode01 Hi SP mode06 Hi SP mode02 Hi SP mode07 Hi SP mode08 Hi SP mode09 Hi Normal SP 1 700 600 300 400 500 800 412 353 177 235 294 471 0 24 60 0 40 100 0 20 50 0 36 90 0 16 40 0 32 80 0 08 20 0 04 10 0 12 30 0 28 70 0 0 0 44 110 0 48 120 Available air flow rate range Hi speed External static pressure inWG Pa Airflow CFM m h 1 Avail...

Страница 272: ...800 412 353 177 235 294 471 Airflow CFM m h Capacity Heating 60 100 40 80 20 0 120 140 Capacity 700 600 300 400 500 800 412 353 177 235 294 471 Airflow CFM m h Capacity 7 2 Slim duct Slim concealed floor type 04 148 7 Fan performance curve INDOOR UNITS INDOOR UNITS ...

Страница 273: ...r limit Hi SP mode03 Hi SP mode04 Hi SP mode00 Hi SP mode05 Hi SP mode01 Hi SP mode06 Hi SP mode02 Hi SP mode07 Hi SP mode08 Hi SP mode09 Hi Normal SP 700 600 300 400 500 800 900 1 000 412 353 177 235 294 471 530 589 0 24 60 0 40 100 0 20 50 0 36 90 0 16 40 0 32 80 0 08 20 0 04 10 0 12 30 0 28 70 0 0 0 44 110 0 48 120 External static pressure inWG Pa Airflow CFM m h 1 Available air flow rate range...

Страница 274: ...9 60 100 40 80 20 0 120 140 Capacity Airflow CFM m h Heating Capacity 700 600 300 400 500 800 900 1 000 412 353 177 235 294 471 530 589 60 100 40 80 20 0 120 140 Capacity Airflow CFM m h 7 2 Slim duct Slim concealed floor type 04 150 7 Fan performance curve INDOOR UNITS INDOOR UNITS ...

Страница 275: ...er limit Hi SP mode03 Hi SP mode04 Hi SP mode00 Hi SP mode05 Hi SP mode01 Hi SP mode06 Hi SP mode02 Hi SP mode07 Hi SP mode08 Hi SP mode09 Hi Normal SP 700 600 300 400 500 800 900 1 000 1 100 1 200 412 353 177 235 294 471 530 589 647 706 0 24 60 0 40 100 0 20 50 0 36 90 0 16 40 0 32 80 0 08 20 0 04 10 0 12 30 0 28 70 0 0 0 44 110 0 48 120 External static pressure inWG Pa 1 Available air flow rate ...

Страница 276: ...6 60 100 40 80 20 0 120 140 Capacity Airflow CFM m h Heating Capacity 700 600 300 400 500 800 900 1 000 1 100 1 200 412 353 177 235 294 471 530 589 647 706 60 100 40 80 20 0 120 140 Capacity Airflow CFM m h 7 2 Slim duct Slim concealed floor type 04 152 7 Fan performance curve INDOOR UNITS INDOOR UNITS ...

Страница 277: ...00 1 200 1 300 1 400 1 600 1 500 1 700 471 530 589 647 706 765 824 942 883 1 001 External static pressure inWG Pa 800 900 1 000 1 100 1 200 1 300 1 400 1 600 1 500 1 700 471 530 589 647 706 765 824 942 883 1 001 Airflow CFM m h 0 24 60 0 40 100 0 16 40 0 32 80 0 08 20 0 0 0 48 120 0 56 140 0 64 160 Hi SP mode14 Hi SP mode00 Hi SP mode01 Hi SP mode02 Hi SP mode03 Hi SP mode07 Hi SP mode05 and 06 Hi...

Страница 278: ...47 706 765 824 942 883 1 001 Airflow CFM m h Capacity Heating Capacity Capacity 70 100 110 80 90 120 800 900 1 000 1 100 1 200 1 300 1 400 1 600 1 500 1 700 471 530 589 647 706 765 824 942 883 1 001 Airflow CFM m h 7 3 Medium static pressure duct type 04 154 7 Fan performance curve INDOOR UNITS INDOOR UNITS ...

Страница 279: ...P Normal SP lower limit Airflow CFM m h External static pressure inWG Pa Hi SP mode00 Hi SP mode01 Hi SP mode02 and 03 Hi SP mode07 Hi SP mode06 Hi SP mode05 Hi SP mode08 Hi SP mode09 Hi SP mode10 Hi SP mode11 Hi Normal SP 0 24 60 0 40 100 0 16 40 0 32 80 0 08 20 0 0 0 48 120 0 56 140 0 64 160 External static pressure inWG Pa 1 000 900 700 800 600 1 100 1 200 1 300 1 400 1 600 1 500 1 700 1 800 2 ...

Страница 280: ...942 883 1 001 1 059 1 177 1 118 1 236 Airflow CFM m h Heating Capacity Capacity 70 100 80 90 120 110 1 000 900 700 800 600 1 100 1 200 1 300 1 400 1 600 1 500 1 700 1 800 2 000 1 900 2 100 589 530 412 471 353 647 706 765 824 942 883 1 001 1 059 1 177 1 118 1 236 Airflow CFM m h 7 3 Medium static pressure duct type 04 156 7 Fan performance curve INDOOR UNITS INDOOR UNITS ...

Страница 281: ...89 530 412 471 647 706 765 824 942 883 1 001 1 059 1 177 1 118 1 236 1 295 Airflow CFM m h 0 24 60 0 40 100 0 16 40 0 32 80 0 08 20 0 0 0 48 120 0 56 140 0 64 160 External static pressure inWG Pa Hi SP mode00 Hi SP mode01 Hi SP mode02 Hi SP mode03 Hi SP mode07 Hi SP mode06 Hi SP mode05 Hi SP mode08 Hi SP mode09 Hi Normal SP 1 000 900 700 800 1 100 1 200 1 300 1 400 1 600 1 500 1 700 1 800 2 000 1 ...

Страница 282: ...3 1 001 1 059 1 177 1 118 1 236 1 295 Airflow CFM m h Heating Capacity Capacity 70 60 100 80 90 120 110 1 000 900 700 800 1 100 1 200 1 300 1 400 1 600 1 500 1 700 1 800 2 000 1 900 2 100 2 200 589 530 412 471 647 706 765 824 942 883 1 001 1 059 1 177 1 118 1 236 1 295 Airflow CFM m h 7 3 Medium static pressure duct type 04 158 7 Fan performance curve INDOOR UNITS INDOOR UNITS ...

Страница 283: ...ow CFM m h Cooling Capacity Capacity 2 300 2 500 1 700 1 100 1 300 1 900 2 100 1 500 1 354 1 472 1 001 647 765 1 236 1 118 883 100 110 120 130 140 80 90 50 70 60 Airflow CFM m h Heating Capacity Capacity 2 300 2 500 1 700 1 100 1 300 1 900 2 100 1 500 1 354 1 472 1 001 647 765 1 236 1 118 883 100 110 120 130 140 80 90 50 70 60 Airflow CFM m h 7 4 High static pressure duct type 04 159 7 Fan perform...

Страница 284: ... Cooling Capacity Capacity 2 300 2 500 2 700 2 900 3 100 1 900 2 100 1 354 1 472 1 589 1 707 1 825 1 236 1 118 100 110 120 130 140 80 90 50 70 60 Airflow CFM m h Heating Capacity Capacity 2 300 2 500 2 700 2 900 3 100 1 900 2 100 1 354 1 472 1 589 1 707 1 825 1 236 1 118 100 110 120 130 140 80 90 50 70 60 Airflow CFM m h 7 4 High static pressure duct type 04 160 7 Fan performance curve INDOOR UNIT...

Страница 285: ... Cooling Capacity 2 200 2 400 2 800 2 600 3 000 3 200 3 400 1 295 1 413 1 648 1 530 1 766 1 884 2 001 Capacity 100 110 120 130 140 80 90 50 70 60 Airflow CFM m h Heating Capacity 2 200 2 400 2 800 2 600 3 000 3 200 3 400 1 295 1 413 1 648 1 530 1 766 1 884 2 001 Capacity 100 110 120 130 140 80 90 50 70 60 Airflow CFM m h 7 4 High static pressure duct type 04 161 7 Fan performance curve INDOOR UNIT...

Страница 286: ...lower limit SP mode30 upper limit Normal SP lower limit SP mode05 upper limit Normal SP upper limit 12 23 19 17 21 08 06 09 07 Hi SP mode05 10 11 13 14 24 26 27 29 28 Hi SP mode30 26 25 22 22 22 22 20 18 16 Normal SP External static pressure inWG Pa 0 80 200 1 00 250 1 20 300 1 40 350 0 60 150 0 40 100 0 20 50 0 0 1 400 2 378 1 600 2 548 1 800 3 058 2 000 3 398 2 200 3 738 2 400 4 078 2 600 4 417 ...

Страница 287: ...4 078 2 600 4 417 2 800 4 757 Airflow CFM m h Capacity Heating Capacity 70 100 80 90 120 110 1 400 2 378 1 600 2 548 1 800 3 058 2 000 3 398 2 200 3 738 2 400 4 078 2 600 4 417 2 800 4 757 Airflow CFM m h Capacity 7 4 High static pressure duct type 04 163 7 Fan performance curve INDOOR UNITS INDOOR UNITS ...

Страница 288: ...ormal SP upper limit SP mode29 lower limit Normal SP lower limit SP mode05 upper limit SP mode29 upper limit External static pressure inWG Pa 0 80 200 1 00 250 1 20 300 0 60 150 0 40 100 0 20 50 0 0 1 800 3 058 2 000 3 398 2 200 3 738 2 400 4 078 2 600 4 417 2 800 4 757 3 000 5 096 3 200 5 436 3 400 5 775 11 24 20 18 22 07 10 08 06 Hi SP mode05 09 12 13 16 14 25 27 Hi SP mode28 26 23 21 19 17 Norm...

Страница 289: ...57 3 000 5 096 3 200 5 436 3 400 5 775 Airflow CFM m h Heating Capacity 70 100 80 90 120 110 1 800 3 058 2 000 3 398 2 200 3 738 2 400 4 078 2 600 4 417 2 800 4 757 3 000 5 096 3 200 5 436 3 400 5 775 Airflow CFM m h Capacity 7 4 High static pressure duct type 04 165 7 Fan performance curve INDOOR UNITS INDOOR UNITS ...

Страница 290: ...ette type Ø2 3 4 in 70 mm Static pressure required to take in fresh air Duct Fan Pa 0 39 0 20 0 inWG 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 m min CFM Installation Duct flange 2 Flexible duct 2 Fan 2 Flexible duct 2 Insulation 1 1 In case of fresh air intake remove the insulation 2 Locally purchased parts Fresh air inlet position For the fresh air inlet position refer to Circular flow cassette type on page ...

Страница 291: ...77 CFM Pa inWG 0 0 004 0 008 0 012 0 016 0 020 1 ABUA30TLAV2 2 ABUA36TLAV2 Installation For half concealed installation Fresh air inlet position Locally purchased parts Flexible duct UTD RF204 Optional parts For the fresh air inlet position refer to Ceiling type on page 04 53 7 5 Fresh air characteristics 04 167 7 Fan performance curve INDOOR UNITS INDOOR UNITS ...

Страница 292: ...GH 520 144 306 MED 480 133 283 MED LOW 440 122 259 LOW 400 111 236 QUIET 350 97 206 AUUA12TLAV2 HIGH 600 167 353 MED HIGH 560 156 330 MED 520 144 306 MED LOW 480 133 283 LOW 430 119 253 QUIET 390 108 230 AUUA14TLAV2 HIGH 680 189 401 MED HIGH 620 172 365 MED 560 156 330 MED LOW 500 139 295 LOW 440 122 259 QUIET 390 108 230 AUUA18TLAV2 HIGH 710 197 418 MED HIGH 660 183 389 MED 590 164 348 MED LOW 52...

Страница 293: ...LAV2 HIGH 1 620 450 954 MED HIGH 1 500 417 883 MED 1 400 389 824 LOW HIGH 1 340 372 789 LOW 1 280 356 753 QUIET 1 150 319 677 AUUB48TLAV2 HIGH 2 040 567 1 201 MED HIGH 1 800 500 1 059 MED 1 590 442 936 LOW HIGH 1 440 400 848 LOW 1 300 361 765 QUIET 1 150 319 677 8 3 Cassette type Model Mode Airflow m3 h l s CFM AUUB18TLAV HIGH 1 150 319 677 MED 940 261 553 LOW 870 242 512 AUUB24TLAV HIGH 1 280 356...

Страница 294: ... 320 89 188 ARUL9TLAV2 HIGH 600 167 353 MED HIGH 510 142 300 MED 460 128 271 MED LOW 420 117 247 LOW 370 103 218 QUIET 320 89 188 ARUL12TLAV2 HIGH 600 167 353 MED HIGH 530 147 312 MED 490 136 289 MED LOW 450 125 265 LOW 410 114 241 QUIET 340 94 200 ARUL14TLAV2 HIGH 800 222 471 MED HIGH 680 189 401 MED 600 167 353 MED LOW 520 144 306 LOW 440 122 259 QUIET 340 94 200 ARUL18TLAV2 HIGH 940 261 554 MED...

Страница 295: ... MED 1 620 450 954 MED LOW 1 450 403 854 LOW 1 300 361 766 QUIET 1 150 319 677 8 7 High static pressure duct type Model Mode Airflow m3 h l s CFM ARUH36TLAV HIGH 2 250 625 1 324 MED 1 750 486 1 030 LOW 1 400 389 824 ARUH48TLAV HIGH 3 000 833 1 766 MED 2 700 750 1 589 LOW 2 300 639 1 354 ARUH60TLAV HIGH 3 350 931 1 972 MED 2 850 792 1 678 LOW 2 550 708 1 501 ARUH72TLAV2 HIGH 3 900 1 083 2 296 MED 3...

Страница 296: ...ET 270 75 159 AGUA9TLAV1 HIGH 500 139 294 MED HIGH 450 125 265 MED 400 111 235 LOW HIGH 360 100 212 LOW 330 92 194 QUIET 270 75 159 AGUA12TLAV1 HIGH 590 164 347 MED HIGH 520 144 306 MED 470 131 277 LOW HIGH 420 117 247 LOW 390 108 230 QUIET 340 94 200 AGUA14TLAV1 HIGH 670 186 394 MED HIGH 590 164 347 MED 520 144 306 LOW HIGH 450 125 265 LOW 390 108 230 QUIET 340 94 200 1 This value is Cooling oper...

Страница 297: ...59 MED HIGH 740 206 436 MED 690 192 406 MED LOW 640 178 377 LOW 600 167 353 QUIET 550 153 324 ABUA18TLAV2 HIGH 1 000 278 589 MED HIGH 910 253 536 MED 830 231 489 MED LOW 750 208 442 LOW 660 183 389 QUIET 580 161 342 ABUA24TLAV2 HIGH 1 000 278 589 MED HIGH 930 258 548 MED 870 242 512 MED LOW 800 222 471 LOW 740 206 436 QUIET 680 189 401 8 9 Floor Ceiling type 04 173 8 Airflow INDOOR UNITS INDOOR UN...

Страница 298: ...380 106 224 LOW 360 100 212 QUIET 330 92 194 ASUA7TLAV1 HIGH 550 153 324 MED HIGH 460 128 271 MED 420 117 247 LOW HIGH 390 108 230 LOW 360 100 212 QUIET 330 92 194 ASUA9TLAV1 HIGH 720 200 424 MED HIGH 570 158 336 MED 500 139 294 LOW HIGH 410 114 241 LOW 360 100 212 QUIET 330 92 194 ASUA12TLAV1 HIGH 690 192 406 MED HIGH 610 169 359 MED 560 156 330 LOW HIGH 530 147 312 LOW 470 131 277 QUIET 330 92 1...

Страница 299: ... MED HIGH 1 300 361 765 MED 1 120 311 659 LOW HIGH 980 272 577 LOW 890 247 524 QUIET 700 194 412 ASUA7TLAV HIGH 490 136 288 MED 450 125 265 LOW 1 420 370 117 103 247 218 ASUA12TLAV HIGH 560 156 330 MED 480 133 283 LOW 420 117 247 ASUB18TLAV HIGH 840 233 494 MED 770 214 453 LOW 690 192 406 ASUB24TLAV HIGH 1 100 306 647 MED 910 253 536 LOW 730 203 430 1 This value is Cooling operation Heating operat...

Страница 300: ...00 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET MED Model AUUA7TLAV2 Model AUUA9TLAV2 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET MED Octave band sound pressure level dB 0 dB 0 0002 µba...

Страница 301: ...C 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET MED Model AUUA18TLAV2 Model AUUA24TLAV2 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET MED Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center...

Страница 302: ...vel dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH LOW Model AUUB30TLAV2 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 ...

Страница 303: ...0 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH LOW Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH LOW 9 2 Circular flow cassette type 04 179 9 Noise level curve INDOOR UNITS INDOOR UNITS ...

Страница 304: ...5 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH LOW MED Model AUUB30TLAV Model AUUB36TLAV Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH LOW MED Octave band sound pressure level dB 0 dB 0 0002 µbar Octave ba...

Страница 305: ...vel dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH LOW 9 4 Mini duct type 04 181 9 Noise level curve INDOOR UNITS INDOOR UNITS ...

Страница 306: ...65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET Model ARUL12TLAV2 Model ARUL14TLAV2 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET Octave band sound pressure level dB 0 dB 0 0002 µbar Octave ban...

Страница 307: ...bar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET 9 5 Slim duct Slim concealed floor type 04 183 9 Noise level curve INDOOR UNITS INDOOR UNITS ...

Страница 308: ... dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET MED Model ARUM36TLAV2 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC ...

Страница 309: ...l dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH LOW MED Model ARUH60TLAV Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40...

Страница 310: ...65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH LOW MED Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH LOW MED 9 7 High static pressure duct type 04 186 9 Noise level curve INDOOR UNITS INDOOR UNITS ...

Страница 311: ...C 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH LOW Model AGUA9TLAV1 Model AGUA12TLAV1 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH LOW Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band c...

Страница 312: ... 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH LOW 9 8 Compact floor type 04 188 9 Noise level curve INDOOR UNITS INDOOR UNITS ...

Страница 313: ... 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET Model ABUA18TLAV2 Model ABUA24TLAV2 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET Octave band sound pressure level dB 0 dB 0 0002 µbar Octave ba...

Страница 314: ...000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET 9 10 Ceiling type 04 190 9 Noise level curve INDOOR UNITS INDOOR UNITS ...

Страница 315: ...C 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH LOW Model ASUA9TLAV1 Model ASUA12TLAV1 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH LOW Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band c...

Страница 316: ...0 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH LOW C C 2 C 2 N N N N N N Models ASUB24TLAV1 and ASUB24TLAV Model ASUA30TLAV2 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH LOW Octave band sound pressure level dB 0 dB 0 0002 ...

Страница 317: ...002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH LOW MED Model ASUA12TLAV Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 ...

Страница 318: ... pressure duct type 60 in 1 5 m Microphone Microphone 60 in 1 5 m 40 in 1 0 m 79 in 2 0 m Air Air Compact floor type Floor Ceiling type Ceiling type Microphone 40 in 1 0 m 40 in 1 0 m Airflow Airflow Microphone 40 in 1 0 m 40 in 1 0 m Wall mounted type Microphone 40 in 1 0 m 40 in 1 0 m 9 12 Sound level check point 04 194 9 Noise level curve INDOOR UNITS INDOOR UNITS ...

Страница 319: ... A 257 18 F 125 10 C Fan motor stop 248 18 F 120 10 C Fan motor restart AUUB24TLAV2 AUUB30TLAV2 AUUB36TLAV2 AUUB48TLAV2 10 3 Cassette type Model Fuse Fan motor thermal protector Terminal thermal fuse Float switch Active Reset AUUB18TLAV 250 V 3 15 A 230 27 18 F 110 15 10 C Fan motor stop 221 27 18 F 105 15 10 C Fan motor Restart AUUB24TLAV AUUB30TLAV AUUB36TLAV 10 4 Mini duct type Model Fuse Fan m...

Страница 320: ...start ARUM36TLAV2 Including in Drain pump unit Optional parts 10 7 High static pressure duct type Model Fuse Fan motor thermal protector Terminal thermal fuse Float switch Active Reset ARUH36TLAV 250 V 3 15 A 250 V 10 A 293 9 F 145 5 C Fan motor stop ARUH48TLAV ARUH60TLAV ARUH72TLAV2 250 V 3 15 A 250 V 20 A 212 27 18 F 100 15 10 C Fan motor stop 203 27 18 F 95 15 10 C Fan motor stop ARUH96TLAV2 Fu...

Страница 321: ... type Model Fuse Fan motor thermal protector Terminal thermal fuse Float switch Active Reset ASUA4TLAV1 250 V 3 15 A 221 18 F 105 10 C Fan motor stop 194 18 F 90 10 C Fan motor restart ASUA7TLAV1 ASUA9TLAV1 ASUA12TLAV1 ASUA14TLAV1 ASUB18TLAV1 302 27 F 150 15 C Fan motor stop 248 27 F 120 15 C Fan motor stop Active at 215 6 F 102 C ASUB24TLAV1 ASUA30TLAV2 302 27 F 150 15 C Fan motor stop Less than ...

Страница 322: ...r 4 For installing indoor unit Cable tie Large 4 For fixing the connection pipe Large and small Template Carton top 1 For cutting opening Also used as packing Cable tie Medium 2 For transmission cable and remote controller cable binding Drain hose 1 For connecting drain hose Coupler heat insulation Small 1 For indoor side pipe joint Liquid pipe Hose band 1 For installing drain hose Coupler heat in...

Страница 323: ... and small Insulation 1 For installing drain pipe Push mount cable tie 1 For transmission cable and remote controller cable binding Drain hose 1 For installing drain hose Coupler heat insulation Small 1 For indoor side pipe joint Liquid pipe Hose band 1 For installing drain hose Coupler heat insulation Large 1 For indoor side pipe joint Gas pipe Drain pipe insulation 1 For installing drain pipe 11...

Страница 324: ...ge and small Insulation 1 For installing drain pipe Cable tie Medium 2 For transmission cable and remote controller cable binding Drain hose 1 For installing drain hose Coupler heat insulation Small 1 For indoor side pipe joint Liquid pipe Hose band 1 For installing drain hose Coupler heat insulation Large 1 For indoor side pipe joint Gas pipe Drain pipe insulation 1 For installing drain pipe 11 3...

Страница 325: ...ding Template Carton top 1 For cutting ceiling opening Also used as packing Filter 2 Washer 8 For installing indoor unit Drain hose 1 For installing drain hose Coupler heat insulation Small 1 For indoor side pipe joint Liquid pipe Hose band 1 For installing drain hose Coupler heat insulation Large 1 For indoor side pipe joint Gas pipe Drain hose installation B 1 Insulates the drain hose 11 4 Mini ...

Страница 326: ...n hose Coupler heat insulation Small 1 For indoor side pipe joint Liquid pipe Hose band 1 For installing drain hose Coupler heat insulation Large 1 For indoor side pipe joint Gas pipe Drain hose installation B 1 Insulates the drain hose Cable tie Large 4 For fixing the coupler heat insulation Installation template 1 For positioning the indoor unit Cable tie Medium 2 For transmission cable and remo...

Страница 327: ...tion pipe large and small and drain cap Hanger 4 For suspending the indoor unit from ceiling Cable tie Medium 3 For transmission cable and remote controller cable binding Drain hose 1 For installing drain hose Coupler heat insulation Small 1 For indoor side pipe joint Liquid pipe Hose band 1 For installing drain hose Coupler heat insulation Large 1 For indoor side pipe joint Gas pipe Drain hose in...

Страница 328: ...or unit from ceiling Cable tie Large 4 For fixing the connection pipe large and small Drain hose 2 For installing drain hose Cable tie Medium 2 For transmission cable and remote controller cable binding Hose band 2 For installing drain hose Coupler heat insulation Small 1 For indoor side pipe joint Liquid pipe Drain hose insulation 2 For installing drain hose Coupler heat insulation Large 1 For in...

Страница 329: ...hose For main drain port Cable tie Medium 2 For transmission cable and remote controller cable binding Drain hose Small 1 For installing drain hose For safety drain port Coupler heat insulation Small 1 For indoor side pipe joint Liquid pipe Hose band Large 1 For installing drain hose Large Coupler heat insulation Large 1 For indoor side pipe joint Gas pipe Hose band Small 1 For installing drain ho...

Страница 330: ...ation manual 1 Push mount cable tie 1 For transmission cable and remote controller cable binding Wall bracket 1 For indoor unit installation Air cleaning filter 2 For installation refer to the CLEANING AND CARE in the operating manual Tapping screw 8 For wall hook bracket installation 11 8 Compact floor type 04 206 11 Accessories INDOOR UNITS INDOOR UNITS ...

Страница 331: ...ng type Hose band 1 For installing drain hose Bracket Left 1 For suspending the indoor unit from ceiling Drain hose insulation 1 Adhesive type 3 15 16 8 11 16 in 100 220 mm Bracket Right 1 For suspending the indoor unit from ceiling VT wire 1 For fixing the drain hose L 11 in 280 mm M10 nut A with flange 4 For suspending the indoor unit from ceiling Insulation pipe 1 Adhesive type 6 5 16 4 5 16 in...

Страница 332: ...ie 4 For transmission cable and remote controller cable binding Drain hose insulation 1 Adhesive type 3 15 16 8 11 16 in 100 220 mm M10 nut A with flange 4 For installing the indoor unit VT wire 1 For fixing the drain hose L 11 in 280 mm M10 nut B with spring lock washer 4 For installing the indoor unit Coupler heat insulation Small 1 For indoor side pipe joint Liquid pipe Installation template 1 ...

Страница 333: ...nd shape Q ty Application Operating manual 1 Cloth tape 1 For indoor unit installation Installation manual 1 Air cleaning filter 2 For installation refer to the CLEANING AND CARE in the operating manual Wall hook bracket 1 For indoor unit installation Air cleaning filter frame 2 For installation refer to the CLEANING AND CARE in the operating manual Tapping screw 5 For wall hook bracket installati...

Страница 334: ...tape 1 For indoor unit installation Connecting cable 1 For wired remote controller installation Models ASUA30TLAV2 and ASUA36TLAV2 Name and shape Q ty Application Name and shape Q ty Application Operating manual 1 Cloth tape 1 For indoor unit installation Installation manual 1 Cable tie 2 For transmission and remote controller cable binding Wall hook bracket 1 For indoor unit installation Air clea...

Страница 335: ...r installation Wall hook bracket 1 For indoor unit installation Air cleaning filter 2 For installation refer to the CLEANING AND CARE in the operating manual Cable tie 1 For remote controller cable binding Air cleaning filter frame 2 For installation refer to the CLEANING AND CARE in the operating manual Cloth tape 1 For indoor unit installation Seal A 1 For indoor unit installation 11 11 Wall mou...

Страница 336: ... For installation refer to the CLEANING AND CARE in the operating manual Wall hook bracket 1 For indoor unit installation Drain hose insulation 1 For installing drain hose Cloth tape 1 For indoor unit installation Connecting cable 1 For wired remote controller installation Tapping screw 8 For wall hook bracket installation Cable tie 1 For transmission and remote controller cable binding 11 11 Wall...

Страница 337: ...5 CONTROL SYSTEM 2019 11 01 DV_CH05_VR2E018EF_04 ...

Страница 338: ...05 82 2 12 Wireless remote controller UTY LNHU 05 87 2 13 IR receiver unit UTB YWC 05 91 2 14 IR receiver unit UTY TRHX 05 94 2 15 IR receiver unit For cassette type UTY LRHYB1 05 97 2 16 IR receiver unit For circular flow cassette type UTY LBHXD 05 99 2 17 Human sensor kit For circular flow cassette type UTY SHZXC 05 101 2 18 Remote sensor unit UTY XSZX 05 103 2 19 Group control method 05 105 2 2...

Страница 339: ...ine LONWORKS Network LONWORKS Network USB line Remote controller line 3 wire Remote controller line 2 wire Remote controller line Single system Shielded Twist Pair Cable Remote controller line Internet or Public telephone line USB 2 Adaptor Locally purchased Locally purchased Touch Panel Controller Wired Remote Controller Wired Remote Controller Touch panel Wireless Remote Controller Simple Remote...

Страница 340: ...c functions by the hotel or office guest Wired simple and wireless remote controllers can be used jointly 4 remote controllers can be connected with single indoor unit Up to 16 indoor units Single control for private room Multiple control for meeting room etc Simple Wired remote controller Simple Remote Controller 3 wire Up to 16 indoor units can be controlled with one simple remote controller Ena...

Страница 341: ...ller Card key Wired remote controller Ext SW Controller Card key Card key Card key Ext SW Controller Single Split or Big Multi System Connectability Single spilit system or Big multi system can be connected to the VRF network system and can be controlled from Touch panel controller or System controller Wired remote controller Touch panel controller Network Convertor UTY VGGXZ1 Single split system ...

Страница 342: ...s To outdoor units Up to 100 indoor units Touch Panel Controller Up to 400 indoor units 400 groups can be controlled with one touch panel controller Up to a total of 16 network convertors central remote controllers and touch panel controllers and network convertor for LONWORKS can be connected to a single VRF network system Commercial building Medium class Touch panel controller Touch panel contro...

Страница 343: ...P to 1600 400 x 4 VRF network system indoor units 1600 groups can be controlled with one System Controller Incorporates a function that automatically calculates electrical charge Up to 100 outdoor units To outdoor units Up to 400 indoor units Commercial building Large class Administrator s room System Controller One System Controller per 4 VRF network systems 4 VRF network systems USB Adaptor 1 2 ...

Страница 344: ...er System Controller Sites with VRF systems Internet or Telephone Line or LAN Server Client Client Client Client Client Remote central control Monitored from up to 5 Clients System Controller System Controller System Controller System Controller System Controller System Controller Site with VRF system Remote central control can be performed by touch panel controller Internet or LAN Remote central ...

Страница 345: ...r flow cassette Cassette Mini duct Slim duct Slim concealed floor Medium static pressure duct High static pressure duct 1 1 Compact floor Floor Ceiling Ceiling Wall mounted 2 2 1 It is not connectable with ARUH72 96TLAV2 in high static pressure duct type 2 It is not connectable with ASUA4 7 9 12 14TLAV1 and ASUB30 36TLAV2 in wall mounted type 1 2 System configuration examples 05 7 1 Control system...

Страница 346: ...nit optional part UTB YWC is necessary 4 IR receiver unit optional part UTY TRHX is necessary 5 Following IR receiver unit optional part is necessary For other than ARUH72 96TLAV2 UTB YWC For ARUH72 96TLAV2 UTY TRHX 6 It is not connectable with ARUH72 96TLAV2 in high static pressure duct type 7 ARUH72 96TLAV2 only 8 It is not connectable with ASUA4 7 9 12 14TLAV1 and ASUB30 36TLAV2 in wall mounted...

Страница 347: ... Network convertor UTY VTGX UTY VGGXZ1 USB adapter Locally purchased Network convertor for LonWorks UTY VLGX BACnet gateway UTY VBGX UTY ABGXZ1 Modbus convertor UTY VMGX Thermostat convertor UTY TTRX Echelon U10 USB Network Interface TP FT 10 Channel Model number 75010R Convertor Adaptor VRF network system Other system Single split system Other system Single split system Multi system BMS BAS Netwo...

Страница 348: ...k convertor UTY VTGX on page 05 109 Can control Fujitsu mini split and HFI models using a network convertor For details refer to Network convertor UTY VTGX on page 05 109 System controller allows to control up to 4 VRF network systems max 1 600 indoor units suitable huge scale application Reliability and easy maintenance Stand alone transmission network allows each equipment to operate individuall...

Страница 349: ...controller Service Tool UTY ASGXZ1 Single system VRF network system side Monitoring side Monitoring side BACnet Gateway UTY ABGXZ1 BACnet LONWORKS Network BACnet 11 811 ft 3 600 m Max Transmission line length BACnet Operator Workstation B OWS NW2 NW3 NW4 Combination of individual remote controller Wired simple and wireless remote controllers can be used jointly Monitoring side Internet or Public T...

Страница 350: ...28 2 100 BACnet gateway UTY VBGX 4 system 128 2 100 UTY ABGXZ1 USB adapter 1 system 1 600 4 VRF networks 400 4 VRF networks Modbus convertor UTY VMGX 9 system 128 2 100 Thermostat convertor UTY TTRX 16 3 Signal amplifier UTY VSGXZ1 40 system Wireless LAN adapter UTY TFSXZ2 1 A maximum of 4 Network convertors for LonWorks can be connected to 1 BMS 2 Maximum controllable indoor unit number per one c...

Страница 351: ...Y RHRY Wired remote controller UTY RNKU 2 Remote control group 3 wire type Simple remote controller With operation mode UTY RSKU Simple remote controller Without operation mode UTY RHKU Adaptor Convertor Connectable units number Remarks External switch controller UTY TERX 2 Remote control group 2 wire or 3 wire type UTY TEKX 3 wire type IR receiver unit UTB YWC UTY LRHYB1 UTY TRHX UTY LBHXD 1 Indo...

Страница 352: ... electricity meter energy saving control without V and S series Different VRF series may be connected for each of the 4 VRF networks supported by the prod uct but different series may not coexist within the same network VR II V II J II J IIS and J IIIL can exist together in same network V and S can exist together in same network too Accessory Name and shape Q ty Application WHITE USB KEY software ...

Страница 353: ...y network VRF Explorer software does not require WHITE USB KEY Software protection key VRF Controller VRF Explorer USB Adapter System Controller On site control Max 4 VRF network systems USB Port Internet or Telephone Line or LAN VRF Explorer VRF Explorer VRF Explorer VRF Building 1 Building Management Company A In charge of the day shift Remote centralized control maintenance center Remote contro...

Страница 354: ...tem Microsoft Windows 7 Home Premium 32 bit or 64 bit SP1 Microsoft Windows 7 Professional 32 bit or 64 bit SP1 Microsoft Windows 8 1 32 bit or 64 bit Microsoft Windows 8 1 Pro 32 bit or 64 bit Microsoft Windows 10 Home 32 bit or 64 bit Microsoft Windows 10 Pro 32 bit or 64 bit Supported languages English Chinese French German Russian Spanish and Polish CPU Intel Core i3 2 GHz or higher Memory 2 G...

Страница 355: ...ible alarm Error e mail notification History management Error history 1 year Operation history and status history 1 year Energy saving management Indoor unit rotation Outdoor unit capacity save Peak cut control 1 month Power consumption monitor Electricity meters supported 200 Outdoor unit required per connection Power consumption information 3 years Electricity charge apportionment Apportionment ...

Страница 356: ...o be connected to an USB port on the PC that System controller is installed System controller runs only on a PC with this WHITE USB KEY However this WHITE USB KEY is not required for remote VRF Explorer software Available option Option Model name Remark Electricity charge apportionment option UTY PLGXA2 Apportions the power used by indoor and outdoor units and automatically calculation the electri...

Страница 357: ...er software does not require WHITE USB KEY Software protection key Remote access option UTY PLGXR2 is necessary VRF Controller VRF Explorer USB Adapter System Controller On site control Max 4 VRF network systems USB Port Internet or Telephone Line or LAN VRF Explorer VRF Explorer VRF Explorer VRF Building 1 Building Management Company A In charge of the day shift Remote centralized control mainten...

Страница 358: ...and monitoring environment for the cus tomer s properties including remote operation NOTES WHITE USB KEY is not required for PCs on the remote site Some function such as equipment registration and input output are invalid on the remote site Optional software to strengthen various function Electricity charge apportionment function can be added by installing optional UTY PLGXA2 Remote centralized co...

Страница 359: ... 64 bit Windows 8 1 and Windows 10 HDD 40 GB or more of free space Display 1 024 768 or higher resolution Interface Ethernet port for getting access to the Internet using LAN or Modem for getting access to the Internet using public telephone line USB ports Maximum of 2 ports Required only for the server PC that works as VRF controller 1 USB port is required for WHITE USB KEY connection 1 USB port ...

Страница 360: ...nagement Error history 1 year Operation history and status history 1 year Energy saving management Indoor unit rotation Outdoor unit capacity save Peak cut control 1 month Power consumption monitor Electricity meters supported 200 Outdoor unit required per connection Power consumption information 3 years Electricity charge apportionment Apportionment charge calculation Apportionment charge bill cr...

Страница 361: ...sh Accessory Name and shape Q ty Application Installation plate 1 For Touch panel controller installation It is attached to the back of the Touch panel controller Screw 8 Screw for Touch panel controller installation Washer 8 Washer for Touch panel controller installation Touch pen 1 Pen for Touch panel controller installation Cable tie 4 For prevention dropping off of the cable CD ROM 1 Includes ...

Страница 362: ...em Microsoft Windows 7 Home Premium 32 bit or 64 bit SP1 Microsoft Windows 7 Professional 32 bit or 64 bit SP1 Microsoft Windows 8 1 32 bit or 64 bit Microsoft Windows 8 1 Pro 32 bit or 64 bit Microsoft Windows 10 Home 32 bit or 64 bit Microsoft Windows 10 Pro 32 bit or 64 bit Supported languages English Chinese French German Russian Spanish and Polish CPU Intel Core i3 2 GHz or higher Memory 2 GB...

Страница 363: ... apportionment option is used via LAN Low noise operation Low noise operation is set to all outdoor units registered by this controller Electricity charge apportionment Op tion Start stop of ECA importing exporting of ECA setting and exporting ECA data Remote language additional registra tion Additional language can be integrated on remote device by creating language database Additional language i...

Страница 364: ...unit registration Function settings of Touch Panel Controller User setting System setting Date and time Group Password Schedule timer Language setting Network Low noise operation Time zone Electricity charge apportionment Display item setting Environment setting Panel positioning Background light setting Sound setting Panel cleaning History Error history Status history Operation history TPC Inform...

Страница 365: ...n be selected Easy to understand GUI of adopted icon Icon display List display Operation mode setting example Large button is designed for easy to access Operation setting screen Optional setting screen 2 3 Touch panel controller UTY DTGYZ1 05 27 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 366: ...onitoring are performed in these group units Group Hallway Group Division A Touch Panel Controller Group Tenant A Group Tenant B Group Tenant F Group Division C Group Division B Group 3F Group 2F Group setting screen 2 3 Touch panel controller UTY DTGYZ1 05 28 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 367: ...ding can be also written to USB flash drive Error history Max 10 items recorded for each touch panel controller and each unit indoor unit and outdoor unit Status history Max 100 operations recorded for each indoor unit of each room Operation hisotry Max 100 operations recorded Optional history screen 2 3 Touch panel controller UTY DTGYZ1 05 29 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 368: ...r remote monitoring Monitor mode main screen example Icon display List display Control main screen example Operation setting screen 2 3 Touch panel controller UTY DTGYZ1 05 30 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 369: ...5 13 16 147 2 1 16 53 2 51 1 4 7 3 3 4 95 8 5 16 211 7 1 16 180 3 9 16 90 3 8 10 5 9 16 142 7 7 16 189 2 15 16 74 2 2 1 4 56 7 2 7 16 62 6 1 2 12 4 5 11 16 145 7 1 2 190 3 8 10 2 1 4 57 1 2 12 R 3 8 4 R 3 8 4 R 1 8 2 5 R 3 16 5 2 Ø15 16 23 7 2 R1 8 2 5 CAUTION Refer to the mounting screw hole positions of the switch box that is to be installed in advance and check the compatibility 2 3 Touch panel...

Страница 370: ...Y EXTERNAL INPUT TRANSMISSION Power supply cable connection terminals Transmission cable through hole External input terminal Case 1 Batch start stop and emergency stop commands K1 K2 K1 K2 CH1 CH2 TM201 EXTERNAL INPUT PCB PCB CN412 CN411 RED WHITE CN201 Case 2 Electricity meter is connected PCB PCB CN412 CN411 RED WHITE CN201 K1 K2 K1 K2 CH1 CH2 TM201 EXTERNAL INPUT Electricity meter 2 3 Touch pa...

Страница 371: ... 200 or more 8 200 or more 4 100 or more Wall 8 200 or more NOTE The switch box that Touch panel controller is to be mounted to should be installed horizon tally in advance CAUTION Following installation positions are prohibited Horizontal way Horizontal way Upside down 2 3 Touch panel controller UTY DTGYZ1 05 33 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 372: ... LAN cable Transmission cable Cable tie Harness Connection cable Screw Washer Screw Touch pen tray a LAN cable b LAN terminal c CF card Rear view Hole in wall CAUTION In advance install a switch box to the wall where Touch panel controller is to be installed 2 3 Touch panel controller UTY DTGYZ1 05 34 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 373: ...cifications Use Cable size Wire type Remarks Power supply cable 20 16 AWG 0 5 1 25 mm2 60245 IEC 57 or equivalent 1 Ø AC 100 240 V 50 60 Hz 2 wire ground Always ground the unit Transmission cable 22 AWG 0 33 mm2 LEVEL4 NEMA non polar 2 core twisted pair solid core shielded LonWorks compatible cable External input output cable 22 AWG 0 33 mm2 Polar 2 core twisted pair Use cable in accordance with l...

Страница 374: ...ion Power supply unit 1 Holder 1 set For power supply unit installation Used for separate type One touch bush 2 For protection of power supply unit cable Screw 8 Screw for Central remote controller installation Connecting cable 1 For power supply unit connection Cable tie 4 For prevention dropping off of the cable CD R 1 Includes the operating manual for Central remote controller Installation manu...

Страница 375: ...iew 1 2 3 4 5 6 7 1 LCD panel 2 CANCEL button 3 OK button 4 LED lamp 5 Function buttons 6 Arrow button 7 MENU button 2 4 Central remote controller UTY DCGY 05 37 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 376: ...ation Room temperature set point upper and lower limitation Weekly timer Weekly timer can set the timer by various combinations Weekday 82 F 28 C 79 F 26 C Set temp Weekend Time 8 00 12 00 13 00 18 00 21 00 Holiday 79 F 26 C 82 F 28 C 79 F 26 C 79 F 26 C 82 F 28 C 82 F 28 C Automatic clock adjustment The time setting of each controller can be set in batch automatically 2 4 Central remote controlle...

Страница 377: ...he number of connected indoor units Step 1 2 3 4 5 Connected indoor units number 1 to 9 units 10 to 20 units 21 to 40 units 41 to 80 units 81 to 100 units Display pattern 9 units display 20 units display 40 units display 80 units display 100 units display 9 20 units display pattern 40 80 100 units display pattern 2 4 Central remote controller UTY DCGY 05 39 2 Control units CONTROL SYSTEM CONTROL S...

Страница 378: ...view Side view Rear view Power supply unit Front view 3 5 16 84 3 7 8 99 2 5 8 67 1 25 7 8 22 1 1 8 29 3 7 8 99 1 13 16 46 5 5 16 135 1 9 16 39 2 R1 8 2 5 3 16 5 2 Ø3 16 5 Side view Top view 1 13 16 46 2 4 Central remote controller UTY DCGY 05 40 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 379: ...r supply DC 5 V DC 5 V Red Rear panel connecting terminal Ground Screw size M2 6 Ground VRF LONWORKS Transmission GND Black X1 X2 Green Power supply unit Power supply cable Reley connector output DC 5 V Power supply 1ø 100 240 V POWER SUPPLY Power supply terminal Ground Screw size M4 2 4 Central remote controller UTY DCGY 05 41 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 380: ...ervice space Installation Setting pattern 1 Separate type Setting pattern 2 Integrated type Power unit Ceiling Control panel Wall Extension cable Service parts supply Power supply unit Wall Control panel 2 4 Central remote controller UTY DCGY 05 42 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 381: ...e tie 2 Cable tie One touch bush 2 Wall Screw 2 Accessories Cut out When wiring the transmission cable in the upward direction of the front panel Power unit cover Screw 4 Screw 2 Screw 2 Screw 2 Accessories Screw 2 Accessories Ceiling 2 4 Central remote controller UTY DCGY 05 43 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 382: ...ble Power supply cable Cable tie One touch bush Screw x 6 Accessories Relay connector Screw x 4 Screw CN13 Connecting cable Cable tie Cable tie One touch bush Wall hole Power supply cable 2 4 Central remote controller UTY DCGY 05 44 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 383: ... 99 135 39 2 Weight Control unit lb g 11 308 Power supply unit 13 355 Fuse capacity A 5 Wiring specifications Use Cable size Wire type Remarks Power supply cable 20 16 AWG 0 5 1 25 mm2 60245 IEC 57 or equivalent 1 Ø AC 100 240 V 50 60 Hz 2 wire ground Always ground the unit Transmission cable 22 AWG 0 33 mm2 LEVEL4 NEMA non polar 2 core twisted pair solid core shielded LonWorks compatible cable Ex...

Страница 384: ...o 12 different languages English Spanish Ger man French Italian Russian Portuguese Turkish Polish Greek Dutch and Chinese Accessory Name and shape Q ty Application Installation manual 1 Operating manual 1 Screw M4 16 mm 4 For installing Cable tie 4 For binding power supply cable and transmission cable 2 5 Central remote controller UTY DCGYZ1 05 46 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 385: ...tton is disabled Select Delete Deletes the selected line Select Copy Copies the selected line New Adds the new line However when the number of setting reaches upper limit this button is disabled h Button OK button Continues the appropriate process Cancel button Cancels the process and closes the cur rent screen Reset button Returns the changed item to initial value Close button Closes the current ...

Страница 386: ...Horizontal airflow direction setting Room temperature upper and lower limitation setting Remote controller prohibition All On Off Mode Temp Timer and Filter R C prohibition setting prohibits individual remote control operation Schedule setting timer 2 5 Central remote controller UTY DCGYZ1 05 48 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 387: ... by analysis of the error history data Dimensions Unit in mm 3 wiring hole 8 1 2 216 2 6 3 4 171 3 16 4 6 13 16 21 5 16 8 4 3 3 8 86 1 5 16 34 3 8 9 5 1 1 2 37 9 5 5 16 134 6 4 round hole 2 5 Central remote controller UTY DCGYZ1 05 49 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 388: ... line terminal name Transmission cable Transmission cable Power supply cable Power supply cable Cable tie Cable tie Installation space Make a service space to perform installation work Unit in mm Service space 9 220 or more 79 2 000 or less 2 5 Central remote controller UTY DCGYZ1 05 50 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 389: ...1 Separate the rear case from the front case Rear case Flat blade screwdriver Front case Slot 6 Screw Rear case Front case 2 5 Central remote controller UTY DCGYZ1 05 51 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 390: ...the wall Cut off Front case Cable cover Epoxy putty More than 1 16 in 1 mm thick NOTES When central remote controller UTY DCGYZ1 is installed at the wall directly install at a flat wall so that small animals do not enter from the rear side When central remote controller UTY DCGYZ1 is installed at the wall directly remove the rubber bush at the rear side 2 5 Central remote controller UTY DCGYZ1 05 ...

Страница 391: ...ase to the rear case Rear case Front case Screw NOTE For details refer to the installation manual of the central remote controller 2 5 Central remote controller UTY DCGYZ1 05 53 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 392: ...4 6 216 2 37 9 Weight oz g 28 2 800 Fuse capacity A 5 Wiring specifications Use Cable size Wire type Remarks Power supply cable for stranded wire 18 16 AWG 0 8 1 25 mm2 60245 IEC 57 or equivalent 1 Ø AC 100 240 V 50 60 Hz 2 wire ground Always ground the unit Power supply cable for solid wire 18 14 AWG 0 8 2 0 mm2 1 Ø AC 100 240 V 50 60 Hz 2 wire ground Always ground the unit Transmission cable 22 ...

Страница 393: ...in a dark room Room temperature display Control up to 16 indoor units Corresponds to 12 different languages English Chinese French German Spanish Russian Polish Italian Por tuguese Greek Turkish and Dutch Accessory Name and shape Q ty Application CD ROM 1 Screw 2 For installing the remote controller Cable tie 1 For remote controller and remote controller cable binding Installation manual 1 Operati...

Страница 394: ... while displaying the Monitor mode screen c LED lamp operation indicator d Touch panel display e Remote controller group name f Clock g Mode h Set temperature i Fan j Away k Room temperature l Override m Menu Various settings can be set n Status Status of the indoor unit and error can be checked o Vacation When this is touched the schedule is disabled and the in door unit remains unoccupied p Stat...

Страница 395: ...B C D 1 640 ft 500 m NOTE Multiple installation method described above is prohibited to combine with 3 wired type re mote controller UTY RNKU UTY RSKU or UTY RHKU and 2 wired type remote con troller UTY RNRUZ Group control With a single remote controller up to 16 indoor units can be simultaneously operated Master A B C D E I U I U I U I U A B C D E Remote controller cable For details of controller...

Страница 396: ...1 Y2 Y3 Indoor unit Group control When there is a functional grounding Remote controller Indoor units Y2 Y2 Y2 Y2 Y2 Y3 Y3 Y3 Y3 Y1 Y1 Y1 Y1 Y1 Dimensions Unit in mm Hole 3 8 3 16 9 4 5 Hole 1 4 3 16 6 4 5 Hole 1 2 3 16 12 5 4 5 13 16 20 4 4 3 4 120 1 3 16 30 1 5 16 33 15 16 23 5 8 15 3 3 5 16 83 5 120 1 13 16 45 3 2 1 2 63 5 2 6 Wired remote controller Touch panel UTY RNRUZ 05 58 2 Control units ...

Страница 397: ...Connection pattern is different according to type of Indoor unit Indoor unit type Connection pattern All cassette type Pattern A All duct type All floor type Floor Ceiling type All ceiling type All wall mounted type Pattern B Pattern A 1 Connect the end of remote controller cable directly to the exclusive terminal block 2 Set the DIP switch SW1 to 2WIRE on the PCB of the indoor unit Terminal block...

Страница 398: ...lack Red Connecting cable Cut and insulate 3 Connect the remote controller cable to the connecting cable and insert it to the connector Set the DIP switch SW1 to 2WIRE on the PCB of the indoor unit Indoor unit PCB Remote controller cable Non polar Connecting cable Connector CNC01 onboard Connect to earth ground screw Functional earthing If necessary Set the DIP switch SW1 to 2WIRE NOTE Layout of t...

Страница 399: ... no condensation Dimensions H W D in mm 4 3 4 4 3 4 11 16 120 120 20 4 Weight oz g 8 220 Wiring specifications Use Cable size Wire type Remarks Remote controller cable 22 to 16 AWG 0 33 to 1 25 mm2 Non polar 2 core Use sheathed twist pair cable 18 AWG Thermostat cable 2 core Use sheathed non twist pair cable Use shielded cable locally purchased in accordance with the regional cable standard 2 6 Wi...

Страница 400: ...ror code can be accessed Up to 16 indoor units can be simultaneously controlled The room temperature can be controlled by detecting the tem perature accurately with built in thermo sensor Accessory Name and shape Q ty Application Remote controller cable 33 ft 10 m For connecting the remote controller Screw 2 For installing the remote controller Cable tie 1 For remote controller and remote controll...

Страница 401: ...ton Deletes the weekly timer schedule k TIMER SET button Sets the date hour minute and on off time l Vertical airflow direction and swing button Push for 2 seconds to change the swing mode m Horizontal airflow direction and swing but ton Push for 2 seconds to change the swing mode n FILTER RESET button o Operation lamp Lights during operation and when the timer is on p Timer and clock indicator q ...

Страница 402: ...ack COM Indoor unit Remote controller 1 2 3 1 2 3 2 remote controllers Remote controllers 1 Red 12 V 2 White Signal 3 Black COM Primary Secondary Indoor unit 1 2 3 1 2 3 1 2 3 Remote controller Dimensions Unit in mm Rear View 4 3 4 120 4 3 4 120 Side view Front view 3 5 16 83 5 5 8 15 3 2 1 2 63 5 Hole 1 2 12 5 Hole 2 Hole 3 3 16 4 5 1 3 16 30 1 5 16 33 5 7 8 23 11 16 18 4 5 9 3 16 4 5 1 4 6 1 13 ...

Страница 403: ...directly to the exclusive terminal block 2 Set the DIP switch SW1 to 3WIRE on the PCB of the indoor unit Terminal block Functional earthing If necessary Remote controller cable Set to 3WIRE the DIP switch SW1 Indoor unit PCB Y1 Y2 Y3 Black White Red NOTES Layout of terminal block and PCB is varies depending on the type of indoor unit Operation may fail if it is connected to the outdoor unit or the...

Страница 404: ... it to the connector Set the DIP switch SW1 to 3WIRE on the PCB of the indoor unit Indoor unit PCB Remote controller cable Connecting cable Connector CNC01 onboard Connect to earth ground screw Functional earthing If necessary Set to 3WIRE the DIP switch SW1 NOTE Layout of terminal block and PCB is varies depending on the type of indoor unit Connector adapter SW1 Indoor unit PCB Specifications Dim...

Страница 405: ...6 indoor units can be simultaneously controlled Can be installed onto SW BOX applies European and other country s standard Accessory Name and shape Q ty Application CD ROM 1 Screw 2 For installing the remote controller Cable tie 1 For remote controller and remote controller cable binding Installation manual 1 Operation manual 1 2 8 Simple remote controller With operation mode UTY RSRY 05 67 2 Cont...

Страница 406: ...N speed indicator k Remote controller address indicator l Status icons Mode mismatch Filter sign 4 Defrost operation Oil recovery operation Under maintenance Error Special state Conducting electricity Emergency stop Operation controlled Forced stop Remote controller sensor is enabled 4 Central controlled Setting temperature range is enabled Operation prohibited m Set temperature Indicates indoor u...

Страница 407: ...40 ft 500 m B C D E 1 640 ft 500 m Electrical wiring 1 remote controller When there is a functional grounding Remote controller Indoor unit Y1 Y1 Y2 Y2 Y3 2 remote controllers When there is a functional grounding Remote controller Remote controller Y1 Y1 Y2 Y2 Y1 Y2 Y3 Indoor unit Group control When there is a functional grounding Remote controller Indoor units Y2 Y2 Y2 Y2 Y2 Y3 Y3 Y3 Y3 Y1 Y1 Y1 ...

Страница 408: ...e All ceiling type All wall mounted type Pattern B Pattern A 1 Connect the end of remote controller cable directly to the exclusive terminal block 2 Set the DIP switch SW1 to 2WIRE on the PCB of the indoor unit Terminal block Functional earthing If necessary Remote controller cable Non polar Indoor unit PCB Set the DIP switch SW1 to 2WIRE NOTES Layout of terminal block and PCB is varies depending ...

Страница 409: ... the PCB of the indoor unit Indoor unit PCB Remote controller cable Non polar Connecting cable Connector CNC01 onboard Connect to earth ground screw Functional earthing If necessary Set the DIP switch SW1 to 2WIRE NOTE Layout of terminal block and PCB is varies depending on the type of indoor unit Connector adapter SW1 Indoor unit PCB Specifications Dimensions H W D in mm 4 3 4 2 15 16 3 4 120 75 ...

Страница 410: ...controlled Can be installed onto SW BOX applies European and other country s standard Accessory Name and shape Q ty Application Remote controller cable 33 ft 10 m For connecting the remote controller Screw 2 For installing the remote controller Cable tie 1 For remote controller and remote controller cable binding Installation manual 1 Operation manual 1 2 9 Simple remote controller With operation ...

Страница 411: ...on i Central control indicator Indicates when function is locked j Fan speed indicator Deletes the weekly timer schedule k Set temperature Indicates error history number in error code history display mode Indicates indoor unit address in address display mode l Operating mode indicator m Indicator Upper Indicates the error code in error code history dis play mode and in self diagnosis mode Indicate...

Страница 412: ...nit Remote controller 1 2 3 1 2 3 2 remote controllers Remote controllers 1 Red 12 V 2 White Signal 3 Black COM Primary Secondary Indoor unit 1 2 3 1 2 3 1 2 3 Remote controller Dimensions Unit in mm 4 3 4 120 2 15 16 75 1 15 16 49 1 9 16 39 15 16 23 5 9 16 14 3 16 4 7 16 11 3 16 4 5 1 2 12 5 hole x 2 hole x 2 5 16 8 2 3 8 60 1 4 6 11 16 18 3 8 9 1 7 8 47 5 3 5 16 83 5 Front View Side View Rear Vi...

Страница 413: ... the exclusive terminal block 2 Set the DIP switch SW1 to 3WIRE on the PCB of the indoor unit Terminal block Functional earthing If necessary Remote controller cable Set to 3WIRE the DIP switch SW1 Indoor unit PCB Y1 Y2 Y3 Black White Red NOTES Layout of terminal block and PCB is varies depending on the type of indoor unit Operation may fail if it is connected to the outdoor unit or the terminal b...

Страница 414: ... connector Set the DIP switch SW1 to 3WIRE on the PCB of the indoor unit Indoor unit PCB Remote controller cable Connecting cable Connector CNC01 onboard Connect to earth ground screw Functional earthing If necessary Set to 3WIRE the DIP switch SW1 NOTE Layout of terminal block and PCB is varies depending on the type of indoor unit Connector adapter SW1 Indoor unit PCB Specifications Dimensions H ...

Страница 415: ...6 indoor units can be simultaneously controlled Can be installed onto SW BOX applies European and other country s standard Accessory Name and shape Q ty Application CD ROM 1 Screw 2 For installing the remote controller Cable tie 1 For remote controller and remote controller cable binding Installation manual 1 Operation manual 1 2 10 Simple remote controller Without operation mode UTY RHRY 05 77 2 ...

Страница 416: ...icator k Status icons Mode mismatch Filter sign 4 Defrost operation Oil recovery operation Under maintenance Error Special state Conducting electricity Emergency stop Operation controlled Forced stop Remote controller sensor is enabled 4 Central controlled Setting temperature range is enabled Operation prohibited l Set temperature Indicates indoor unit address 5 1 Not available for a heat pump mod...

Страница 417: ... ft 500 m B C D E 1 640 ft 500 m Electrical wiring 1 remote controller When there is a functional grounding Remote controller Indoor unit Y1 Y1 Y2 Y2 Y3 2 remote controllers When there is a functional grounding Remote controller Remote controller Y1 Y1 Y2 Y2 Y1 Y2 Y3 Indoor unit Group control When there is a functional grounding Remote controller Indoor units Y2 Y2 Y2 Y2 Y2 Y3 Y3 Y3 Y3 Y1 Y1 Y1 Y1...

Страница 418: ...All ceiling type All wall mounted type Pattern B Pattern A 1 Connect the end of remote controller cable directly to the exclusive terminal block 2 Set the DIP switch SW1 to 2WIRE on the PCB of the indoor unit Terminal block Functional earthing If necessary Remote controller cable Non polar Indoor unit PCB Set the DIP switch SW1 to 2WIRE NOTES Layout of terminal block and PCB is varies depending on...

Страница 419: ...he PCB of the indoor unit Indoor unit PCB Remote controller cable Non polar Connecting cable Connector CNC01 onboard Connect to earth ground screw Functional earthing If necessary Set the DIP switch SW1 to 2WIRE NOTE Layout of terminal block and PCB is varies depending on the type of indoor unit Connector adapter SW1 Indoor unit PCB Specifications Dimensions H W D in mm 4 3 4 2 15 16 3 4 120 75 19...

Страница 420: ...s European and other country s standard Concentrates on the basic operations such as Start Stop Fan control and Temperature setting Accessory Name and shape Q ty Application Remote controller cable 33 ft 10 m For connecting the remote controller Screw 2 For installing the remote controller Cable tie 1 For remote controller and remote controller cable binding Installation manual 1 Operation manual ...

Страница 421: ...cates when function is locked i Fan speed indicator Deletes the weekly timer schedule j Set temperature Indicates error history number in error code history display mode Indicates indoor unit address in address display mode k Operating mode indicator l Indicator Upper Indicates the error code in error code history dis play mode and in self diagnosis mode Indicates the refrigerant system address in...

Страница 422: ...t Remote controller 1 2 3 1 2 3 2 remote controllers Remote controllers 1 Red 12 V 2 White Signal 3 Black COM Primary Secondary Indoor unit 1 2 3 1 2 3 1 2 3 Remote controller Dimensions Unit in mm Front View Side View Rear View hole x 2 hole x 2 4 3 4 120 2 15 16 75 1 15 16 49 1 9 16 39 15 16 23 5 9 16 14 3 16 4 7 16 11 3 16 4 5 1 2 12 5 5 16 8 2 3 8 60 1 4 6 11 16 18 3 8 9 1 7 8 47 5 3 5 16 83 5...

Страница 423: ...he exclusive terminal block 2 Set the DIP switch SW1 to 3WIRE on the PCB of the indoor unit Terminal block Functional earthing If necessary Remote controller cable Set to 3WIRE the DIP switch SW1 Indoor unit PCB Y1 Y2 Y3 Black White Red NOTES Layout of terminal block and PCB is varies depending on the type of indoor unit Operation may fail if it is connected to the outdoor unit or the terminal blo...

Страница 424: ...onnector Set the DIP switch SW1 to 3WIRE on the PCB of the indoor unit Indoor unit PCB Remote controller cable Connecting cable Connector CNC01 onboard Connect to earth ground screw Functional earthing If necessary Set to 3WIRE the DIP switch SW1 NOTE Layout of terminal block and PCB is varies depending on the type of indoor unit Connector adapter SW1 Indoor unit PCB Specifications Dimensions H W ...

Страница 425: ... used jointly with wired remote controllers Easy to change custom code max 4 codes Accessory Name and shape Q ty Application Screw 2 For installing the remote controller Battery 1 5 V R03 AAA 2 For remote controller Remote controller holder 1 For remote controller Installation manual 1 Operation manual 1 2 12 Wireless remote controller UTY LNHU 05 87 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 426: ...ff time h TEST RUN button Only used for the initial test in the unit installation i CLOCK ADJUST button Used for adjusting the clock j TIMER MODE button Selects the timer mode off timer on timer program timer and timer reset k SLEEP button Pressed to select sleep timer l FILTER RESET button m ECONOMY button n SET TEMP temperature button Sets desired temperature Sets remote controller custom code o...

Страница 427: ...nd receiver There is an instant start type inverter type etc fluorescent lamp in the room Air conditioner might not work correctly when strong light hits the signal receiver window Shut off the direct sunlight and also make illuminator far away from the signal receiver window 2 12 Wireless remote controller UTY LNHU 05 89 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 428: ...ont view Side view Bottom view 2 3 8 60 1 3 16 30 Ø1 8 3 5 1 8 1 4 3 5 6 5 hole hole 1 1 16 1 3 3 4 95 6 1 16 155 26 26 Specifications Dimensions H W D in mm 6 11 16 2 3 16 3 4 170 56 19 Weight without batteries oz g 3 85 2 12 Wireless remote controller UTY LNHU 05 90 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 429: ...indoor unit Screw M4 12 mm 1 For attaching the hook metal to holder cover Screw M4 20 mm 2 For installing receiver unit to wall etc Connection cable A 16 ft 5 m 1 For connecting PCB of indoor unit to receiver unit Connection cable B 5 7 8 in 0 15 m 1 Connection cable D 5 7 8 in 0 15 m 1 For connecting PCB of indoor unit to receiver unit Hook metal 1 For installing receiver unit to indoor unit Brac...

Страница 430: ...AL RECEIVER System diagrams Attachment range L 1 L 1 1 Connection cable length L Cable A Standard accessory 16 ft 5 m Cable C Optional service part 33 ft 10 m Signal angle 120 16 ft 5 m 120 ӊ 16 ft 5 m 2 13 IR receiver unit UTB YWC 05 92 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 431: ...1 16 145 3 9 16 90 3 4 18 5 2 3 8 60 2 1 4 57 6 3 5 1 6 8 3 5 7 8 22 9 4 11 16 118 4 2 7 8 72 4 9 16 13 6 9 16 13 6 2 1 4 57 4 5 16 7 2 5 16 7 2 11 16 17 Front View Side View Rear View Specifications Dimensions H W D in mm 5 11 16 3 9 16 1 3 16 145 90 30 Weight oz g 5 150 Optional service part Use the parts number shown below to order the cable from your representative Use the shield type connecti...

Страница 432: ...nit Screw M4 10 mm 2 For attaching the hook metal to the indoor unit Screw M4 12 mm 1 For attaching the hook metal to holder cover Screw M4 20 mm 2 For installing receiver unit to wall etc Connection cable A 16 ft 5 m 1 For connecting PCB of indoor unit to receiver unit Connection cable B 7 7 8 in 0 12 m 1 Hook metal 1 For installing receiver unit to indoor unit Bracket cover 1 For receiver unit I...

Страница 433: ...L RECEIVER System diagrams Attachment range L 1 L 1 1 Connection cable length L Cable A Standard accessory 16 ft 5 m Cable C Optional service part 33 ft 10 m Signal angle 120 16 ft 5 m 120 ӊ 16 ft 5 m 2 14 IR receiver unit UTY TRHX 05 95 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 434: ...57 6 3 5 1 6 8 3 5 7 8 22 9 4 11 16 118 4 2 7 8 72 4 9 16 13 6 9 16 13 6 2 1 4 57 4 5 16 7 2 5 16 7 2 11 16 17 Front View Side View Rear View Specifications Dimensions H W D in mm 5 11 16 3 9 16 1 3 16 145 90 30 Weight oz g 5 150 Optional service part Use the parts number shown below to order the cable from your representative Use the shield type connection cable in accordance with standard of you...

Страница 435: ... IR receiver unit is used Accessory Name and shape Q ty Application Strap 1 For preventing receiver from falling down Installation manual 1 Overview Filter lamp Red Timer lamp Orange Operation lamp Green Manual auto Signal receiver 2 15 IR receiver unit For cassette type UTY LRHYB1 05 97 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 436: ...it Connected to CN18 of PCB Dimensions Unit in mm 7 5 8 193 9 7 5 8 193 9 1 1 4 31 2 Front View Side View Specifications Dimensions H W D in mm 7 5 8 7 5 8 1 1 4 193 9 193 9 31 2 Weight oz g 5 140 2 15 IR receiver unit For cassette type UTY LRHYB1 05 98 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 437: ...rom falling down Cable tie 2 For electrical wiring Installation manual 1 Overview Remote control signal receiver and Manual Auto button FILTER Indicator lamp RED OPERATION Indicator lamp GREEN TIMER Indicator lamp ORANGE Electrical wiring Wire from IR receiver unit Wiring hole Indoor unit Attach the corner plate firmly in 5 places 2 16 IR receiver unit For circular flow cassette type UTY LBHXD 05 ...

Страница 438: ... 6 1 2 164 5 7 8 22 6 Front View Side View Specifications Dimensions H W D in mm 6 1 2 6 1 2 7 8 164 5 164 5 22 6 Weight oz g 4 110 2 16 IR receiver unit For circular flow cassette type UTY LBHXD 05 100 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 439: ... is also judged automatically Accessory Name and shape Q ty Application Cable tie 3 For binding wires Strap 1 For preventing human sensor from falling down Insulation 3 To fasten the human sensor wire Installation manual 1 Operation manual 1 2 17 Human sensor kit For circular flow cassette type UTY SHZXC 05 101 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 440: ...aces Dimensions Unit in mm 6 1 2 164 5 2 3 16 55 3 6 1 2 164 5 1 1 16 27 5 Front View Side View Specifications Dimensions H W D in mm 6 1 2 6 1 2 1 1 16 164 5 164 5 27 5 Weight oz g 4 110 2 17 Human sensor kit For circular flow cassette type UTY SHZXC 05 102 2 Control units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 441: ...anual 1 Screw M4 10 mm 2 Cord clamp 1 Screw M4 16 mm 2 Electrical wiring Remove the screws from the remote sensor unit and remove the cover Connect the cable to the remote sensor unit as shown below Ensure that the wires do not contact each other Remote sensor To indoor unit Cable Dimensions Unit in mm 2 3 16 55 2 2 3 4 70 2 2 18 Remote sensor unit UTY XSZX 05 103 2 Control units CONTROL SYSTEM CO...

Страница 442: ...screw it in place When the cable is buried in the wall Remove the material thinner than the surrounding material in the wiring hole on the remote sensor unit using a pair of cutters Drill a hole in the wall for the cable Seal the area around the cable penetration with putty 13 16 20 13 16 20 Ø1 4 6 to Ø3 8 10 1 16 1 Screw M4 5 8 16 Mounting hole dimensions 2 3 16 55 Fit the cover on the remote sen...

Страница 443: ...en using 2 remote controllers Last command is priority Operation mode might be fixed by system operation Timer setting function become disable from slave remote controller or wireless remote con troller When the airflow direction is set with combination use of wireless remote controller and wired remote controller in the same remote controller group airflow direction setting shown on the re mote c...

Страница 444: ...Heat pump system System controller Group A Group is possible with only one indoor unit Group B Group is possible with spanning the RB groups Group C Group is possible with spanning the RB group and indoor unit of cooling only type Group D Group is possible with spanning the refrigerant systems NOTE The contents of setting may not be reflected by operation status B C D group 2 19 Group control meth...

Страница 445: ... Day of week RC prohibition Cooling Heating priority Address display Room temp 2 2 2 2 Multi language Summer time Name registration Backlight 2D floor layout 3D floor layout Timer Schedule timer Period Year Year Year Week Week On Off Temp Mode Times per day 144 144 20 20 20 On Off timer Sleep timer Program timer Auto off timer Day off timer Min unit of timer setting Minutes 10 10 10 10 10 Control ...

Страница 446: ...iority Address display Room temp Multi language Summer time Name registration Backlight 2D floor layout 3D floor layout Timer Schedule timer Period Week Week On Off Temp Mode Times per day 8 4 On Off timer Sleep timer Program timer Auto off timer Day off timer Min unit of timer setting Minutes 10 to 30 30 5 Control Status monitoring system Electricity charge calculation Error history Emergency sto...

Страница 447: ...e done with these controllers One Network convertor can be connected and controlled up to 16 indoor units One Wired remote controller is possible for one Network con vertor by UTY VTGX Up to 100 Network convertor can be connected in one VRF network system One Network convertor is regarded as one refrigerant system The total refrigerant system in one VRF network system must be within 100 Accessory ...

Страница 448: ...red remote controller Transmission line non polar 2 conductor Remote controller line Network convertor Multi System 2 Branch box Outdoor unit for Multi system 1 All indoor units connected to a Network convertor are operated under same status 2 Network convertor is necessary for each indoor unit to control indoor unit individually 3 1 Network convertor UTY VTGX 05 110 3 Adaptor Convertor units CONT...

Страница 449: ...twork convertor NOTES Do not bind the power cable and the remote controller cable to avoid erroneous operation Use shielded cable for transmission cable in accordance with the regional cable standard Use sheathed PVC cable or shielded cable for remote controller cable in accordance with the regional cable standard Use ground wire to ground the Network convertor 3 1 Network convertor UTY VTGX 05 11...

Страница 450: ...roller cable in Chapter 6 SYSTEM DESIGN on page 06 62 A 6 ft 2 m A B C D E 1 640 ft 500 m For polar 3 wire Network convertor Indoor unit A B X C D E F A B C D E X Remote controller cable For details of controller cable specifications refer to Controller cable in Chapter 6 SYSTEM DESIGN on page 06 62 A 6 ft 2 m A B C D E 328 ft 100 m and X 328 ft 100 m 3 1 Network convertor UTY VTGX 05 112 3 Adapto...

Страница 451: ...2 wire Polar 3 wire Operation of louver from VRF Operation of louver from wired remote controller Restriction of wireless remote controller from central control Restriction of wired remote controller from central control Anti freeze Setting high and low temperature limit Indoor unit rotation Turning off indoor unit external thermostat Outdoor unit forced stop Outdoor unit capacity save Outdoor uni...

Страница 452: ...ity Packaged 0 to 95 RH No condensation Dimensions H W D in mm 5 1 2 4 5 8 1 11 16 140 117 43 Weight oz g 9 250 Wiring specifications Use Cable size Wire type Remarks Transmission cable 22 AWG 0 33 mm2 LEVEL 4 NEMA Non polar 2 core twisted pair solid core shielded LonWorks compatible cable Remote controller cable 2 wire type 22 to 16 AWG 0 33 to 1 25 mm2 Non polar 2 core Use sheathed PVC cable or ...

Страница 453: ...wo Wired remote controllers are possible for one Network convertor Up to 100 Network convertors can be connected in one VRF network sys tem One Network convertor is regarded as one refrigerant system Total refrigerant systems in one VRF network system must be within 100 Accessory Name and shape Q ty Application Cable tie 4 For mounting the power supply cable remote controller cable and transmissio...

Страница 454: ...em 1 All indoor units connected to a Network convertor are operated under same status 2 Network convertor is necessary for each indoor unit to control indoor unit individually Electrical wiring L N POWER X1 X2 TRANSMISSION Y1 Y2 Y3 J1 REMOTE INDOOR UNIT REMOTE CONTROLLER LINE J2 J3 1Ø 50 60 Hz 208 240 V Switch Fuse 3 A Transmission cable to VRF System Transmission cable to VRF System Wired remote ...

Страница 455: ...oid erroneous operation Use shielded cable for transmission line and remote controller line The shielded metal should be grounded Use ground wire to ground the Network convertor 3 2 Network convertor UTY VGGXZ1 05 117 3 Adaptor Convertor units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 456: ...WAE EZ 099DHSE R EZ 000DHSE R EZ 0001HSE R EZ 000GHSE R EZ 00004HSE R EZ 00005HSE R EZ 0015HSE R EZ 0019HSE R EZ 099DHSEFR EZ 0001HSEFR EZ 000DHSEFR EZ 000GHSEFR EZ 0015HSEFR EZ 0994HSE R EZ 000EHSE R EZ 0994HSEFR EZ 099CWSE R EZ 000AWSE R EZ 0001WSE R EZ 000FWSE R EZ 0012WSE R EZ 099CWSEFR EZ 0001WSEFR EZ 000AWSEFR EZ 09906WSE R EZ 000BWSE R EZ 09906WSEFR Numerical character or alphabetical chara...

Страница 457: ...0 to 95 RH No condensation Dimensions H W D in mm 2 5 8 11 5 16 8 5 16 67 288 211 Weight lb g 3 1 500 Fuse capacity A 3 Wiring specifications Use Cable size Wire type Remarks Power supply cable using remote control cable 20 to 16 AWG 0 5 to 1 25 mm2 60245 IEC 57 or equivalent 1 Ø AC 208 240 V 50 60 Hz 2 wire ground Always ground the unit Transmission cable 22 AWG 0 33 mm2 LEVEL 4 NEMA Non polar 2 ...

Страница 458: ...n U S A and Canada CD ROM 1 Includes the software and manuals of tools for Network convertor Connector cable 1 For initial setting tool Installation manual 1 Other required devices Locally purchased To install tool for convertor personal computer that satisfies the following system requirements is necessary Personal computer system requirement Operating system Microsoft Windows 7 Professional 32 b...

Страница 459: ...128 indoor units Maximum 100 outdoor units Maximum 100 outdoor units Maximum 128 indoor units Lighting facilities Security system Ventilation system alarm interface Automatic fire VRF network Indoor unit Outdoor unit Network convertor for LonWorks UTY VLGX 3 3 Network convertor for LonWorks UTY VLGX 05 121 3 Adaptor Convertor units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 460: ...work convertor for LonWorks UTY VLGX Network convertor for LonWorks UTY VLGX LonWorks network Example 2 Prohibited Maximum 128 indoor units Maximum 128 indoor units Network Maximum 100 outdoor units Network convertor for LonWorks UTY VLGX Network convertor for LonWorks UTY VLGX LonWorks 3 3 Network convertor for LonWorks UTY VLGX 05 122 3 Adaptor Convertor units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 461: ... Device 1Φ 50 60 Hz 208 240 V Indoor unit Indoor unit Outdoor Unit Transmission cable Transmission cable Power supply cable Network convertor Master or Slave Outdoor unit Power supply cable Transmission cable to LonWorks network Transmission cable to VRF network Fuse 3 A NOTES Do not bind the power cable and transmission cable to avoid an errorneous operation Use shielded cable for transmission ca...

Страница 462: ...ntrol Filter reset Prohibition of filter sign reset of remote controller Centrally control All mode Prohibition of all mode of remote controller Centrally control Timer mode Prohibition of timer mode of remote controller Centrally control Set temperature mode Prohibition of set temperature mode of remote controller Centrally control On Off mode Prohibition of On Off mode of remote controller Centr...

Страница 463: ...onitored Indoor unit monitoring Batch Maintenance mode status Maintenance status Emergency stop setting status Emergency stop setting status Outdoor unit monitoring Individual Error code Status Error code status Convertor unit monitoring Individual Error code Status Error code status NOTES For detailed information refer to the interface specification posted on Service Supports page of the web site...

Страница 464: ...7 288 211 Weight lb g 3 1 500 Fuse capacity A 3 Wiring specifications Use Cable size Wire type Remarks Power supply cable 20 to 16 AWG 0 5 to 1 25 mm2 60245 IEC 57 or equivalent 1 Ø AC 208 240 V 50 60 Hz 2 wire ground Always ground the unit Transmission cable 22 AWG 0 33 mm2 LEVEL 4 NEMA Non polar 2 core twisted pair solid core shielded LonWorks compatible cable Transmission specifications LonWork...

Страница 465: ...ork Convertor using a Tool for network convertor Software provided by Fujitsu General Job is done by Network Integrator Binding VRF with BMS By Network Integrator Outdoor unit address Refrigerant circuit address Indoor unit address Remote controller address Commissioning Group Group Load Information XIF file XIF file LonWorks Open network Interface for LonWorks VRF LonWorks System 3 3 Network conv...

Страница 466: ...s product from BMS A maximum number of four Network convertors can be connected to one BMS and ID number allocation is like 00 01 and so on 5 Initial setting of indoor unit and outdoor unit address by using the tool for convertor 6 Register the initial setting data to this product Click Register dialog 7 Set configuration properties To set the communication properties of this product select the fo...

Страница 467: ...sed To install tool for convertor personal computer that satisfies the following system requirements is necessary Personal computer system requirement Operating system Microsoft Windows 7 Home Premium 32 bit or 64 bit SP1 Microsoft Windows 7 Professional 32 bit or 64 bit SP1 Microsoft Windows 8 1 32 bit or 64 bit Microsoft Windows 8 1 Pro 32 bit or 64 bit Microsoft Windows 10 Home 32 bit or 64 bit...

Страница 468: ...em alarm interface Automatic fire VRF network Indoor unit Outdoor unit Connected unit Maximum controllable indoor units number per 1 Modbus convertor 128 Maximum controllable outdoor units number per 1 Modbus convertor 100 Maximum connectable Modbus convertor number per 1 VRF network system 9 Maximum number of connected Modbus convertor units to one Modbus master unit Without repeater 31 With repe...

Страница 469: ...utdoor unit Power supply cable Transmission cable to Modbus network Transmission cable to VRF network Modbus convertor 1Ø 50 60 Hz 208 240 V Disconnect switch Switch Fuse 2 A Power supply cable Functions Indoor unit control Individual control Commands from Modbus network are sent to the respective indoor units Modbus network respective indoor units of VRF network Batch control Commands from Modbus...

Страница 470: ... control Individual Outdoor unit low noise Outdoor unit low noise level setting Outdoor unit capacity save Outdoor unit capacity save setting Indoor unit monitoring Individual On Off Status 1 The indoor unit which is now operating can be monitored in all indoor units Operation mode setting status Cooling Heating Auto Fan Dry mode status Temperature setting status Room set temperature status Airflo...

Страница 471: ... posted on Service Supports page of the web site https www fujitsu general com global support 1 To protect the compressor of the outdoor unit carefully read and understand the following caution that may affect the operation of compressor before executing the setting CAUTION When performing periodical settings like schedule settings for the following functions perform the setting to all indoor unit...

Страница 472: ... specifications Use Cable size Wire type Remarks Power supply cable 20 to 16 AWG 0 5 to 1 25 mm2 60245 IEC 57 or equivalent 1 Ø AC 208 240 V 50 60 Hz 2 wire ground Always ground the unit Transmission cable 22 AWG 0 33 mm2 LEVEL 4 NEMA Non polar 2 core twisted pair solid core shielded LonWorks compatible cable Modbus cable 26 to 16 AWG 0 128 to 1 25 mm2 AWG 16 26 3 Wire Sheathed PVC cable Transmiss...

Страница 473: ...LED Scan is complete 4 Turn off the switch of scan setting 5 Address update display by LED 6 Turn on the main power again 7 Address rewriting display by LED Address are synchronized among boards If scan error is generated perform the scan again Setting from PC NOTE For detailed information refer to the application manual included inside packaged DVD 1 Install tool for convertor software in PC Tool...

Страница 474: ...onvertor Thermostat controller Indoor unit Outdoor unit Thermostat convertor Thermostat controller Indoor unit Outdoor unit Single split system Multi split system Serial communication Remote control line Thermostat wire Thermostat convertor Thermostat controller Thermostat convertor Thermostat controller Indoor unit Indoor unit VRF system Outdoor unit VRF network LonWorks Remote controller group R...

Страница 475: ...he transformer as necessary per building code and manufacturer s installation instruc tions Maximum power 5 0 VA Single stage cooling and heating Locally purchased Max 16 units Indoor unit Thermostat convertor AC 208 230 V AC 24 V Thermostat controller Transformer AC 24 V Install the transformer as necessary per building code and manufacturer s installation instruc tions Maximum power 5 0 VA 3 5 T...

Страница 476: ... wire type and 3 wire type are available depending on the device to be connected All wiring shown should be performed with 18 AWG thermostat wire Terminals to thermostat controller on Thermostat convertor support AC 20 to 30 V HIGH MED LOW fan signals are optional and may not be available on all thermostat con trollers Signals for stage 2 are optional W2 and Y2 terminals may not be used in single ...

Страница 477: ...g tem perature of the thermostat remote controller operation prohibition is automatically enabled Air direction adjustment by thermostat No fan mode is available in heat pump system Do not connect between fan signal terminals G G1 G2 or G3 on the convertor and the thermo stat by using wire Error code will be displayed on the built in LED display For indoor unit without error code indicator confirm...

Страница 478: ... 86 7 Weight oz g 4 100 Wiring specifications Use Cable size Wire type Remarks Remote controller cable 2 wire type 22 to 16 AWG 0 33 to 1 25 mm2 Sheathed PVC cable Non polar 2 core twisted pair Maximum cable length 1 640 ft 500 m Remote controller cable 3 wire type 22 AWG 0 33 mm2 Polar 3 core Maximum cable length 82 ft 25 m Thermostat wires 18 AWG 0 82 mm2 Maximum cable length 1 64 ft 50 m Use sh...

Страница 479: ...Green LED2 Orange LED3 Red LED4 Blue Contents N N Off Thermostat convertor error N N On Indoor unit error 0 5 s On 0 5 s Off 0 1 s On 0 1 s Off N Number of flashing For flashing number of each error code and the details refer to ERROR CODES in the installa tion manuals of indoor units 3 5 Thermostat convertor UTY TTRX 05 141 3 Adaptor Convertor units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 480: ...ing tool Dust proof bushing 2 For connecting the power supply cable Other required devices Locally purchased To install tool for BACnet gateway personal computer that satisfies the following system require ments is necessary Personal computer system requirement Operating system Microsoft Windows 7 Professional 32 bit or 64 bit SP1 Microsoft Windows 8 1 Pro 32 bit Microsoft Windows 10 Home 32 bit o...

Страница 481: ...or units Lighting facilities Security system Ventilation system alarm interface Automatic fire VRF network Indoor unit Outdoor unit BACnet gateway UTY VBGX VRF system 1 VRF system 4 Maximum 4 network BACnet gateway UTY VBGX NOTE BACnet gateway Hardware and BACnet gateway Software cannot co exist within a VRF system 3 6 BACnet gateway Hardware UTY VBGX 05 143 3 Adaptor Convertor units CONTROL SYSTE...

Страница 482: ...eway Hardware Do not use 2 holes to tie one cable Power supply Connect mains to the power supply connector as Brown Line L Yellow Earth Ground E Blue Neutral N Ethernet BACnet IP UDP Console UDP and TCP Connect the cable coming from the IP network to the connector ETH of the gateway Use an Eth ernet CAT5 or higher cable VRF network Connect the Lon bus to connectors A B and SNGD of gateway s PCB Co...

Страница 483: ... 3 Connect to VRF network Use the Lon connector in the left bottom corner of the gateway in order to connect the VRF net work to BACnet gateway UTY VBGX Lon terminal block C2 VRF network connection through Lon VRF network Cable Three wires Cable Three wires A X1 B X2 SGND SGND 4 Connect to PC Configuration tool This action allows the user to have access to configuration and monitoring of the devic...

Страница 484: ...le The shield metal should be grounded Do not forget to ground the BACnet gateway Functions Indoor unit control Individual control Commands from BACnet network are sent to the respective indoor units BACnet network respective indoor units of VRF network Batch control Commands from BACnet network are sent to all indoor units connected to VRF network BACnet network All indoor units of VRF network In...

Страница 485: ...etting In MI MO Fan speed status setting In MI MO Suction Room temperature In AI Representative error In BI Error code In MI Temperature H L limit status setting In AI AO H L limit per 3 operation Mode HEAT COOL DRY and AUTO Temperature limit validity status setting In BI BO Filter sign status reset In BI BO Only reset for control Forced thermo off status setting 3 In BI BO Emergency stop In BI R ...

Страница 486: ...ical settings like schedule settings for the following functions perform the setting to all indoor units in the same refrigerant system simultaneously conforming to the timing restriction described below Corresponding function More than 10 minutes must elapse More than 10 minutes must elapse Stop operation Set indoor unit forced thermostat off mode Start operation Release indoor unit forced thermo...

Страница 487: ...0 5 8 6 15 16 60 270 176 Weight lb g 3 1 200 Fuse capacity A 1 25 Wiring specifications Use Cable size Wire type Remarks Power supply cable 20 to 16 AWG 0 5 to 1 25 mm2 60245 IEC 57 or equivalent 1 Ø AC 208 240 V 50 60 Hz 2 wire ground Always ground the unit Transmission cable Ethernet category 5 or higher STP LAN cable with RJ45 Straight cable Transmission specifications BACnet IP ASHRAE 135 Anne...

Страница 488: ...red devices Locally purchased To install tool for BACnet gateway personal computer that satisfies the following system require ments is necessary Personal computer system requirement Operating system Microsoft Windows 7 Home Premium 32 bit or 64 bit SP1 Microsoft Windows 7 Professional 32 bit or 64 bit SP1 Microsoft Windows 8 1 32 bit or 64 bit Microsoft Windows 8 1 Pro 32 bit or 64 bit Microsoft ...

Страница 489: ...spective indoor units via BACnet gateway BMS BACnet gateway respective indoor units of VRF network system Indoor unit status monitoring Input object Indoor unit status is communicated to the BMS via BACnet gateway BMS BACnet gateway respective indoor units of VRF network system Outdoor unit control Output object Commands from BMS are sent to the respective outdoor units via BACnet gateway BMS BACn...

Страница 490: ...us Refer to R C prohibition setting chart 14 Vertical airflow direction status 1 2 3 4 SWING 15 Horizontal airflow direction status 1 2 3 4 5 SWING 16 Special driving status Normal Defrost Oil recovery 17 Managed mode None Master Slave External MO 10 Operation mode status COOL HEAT FAN DRY AUTO 11 Fan speed setting LOW HIGH MED AUTO QUIET MED LOW MED HIGH 12 R C prohibition setting Refer to R C pr...

Страница 491: ... minutes must elapse Set outdoor unit forced off mode Reset outdoor unit forced off mode When performing periodical settings like schedule settings for the following functions per form the setting to all indoor units in the same refrigerant system simultaneously conforming to the timing restriction described below Corresponding function More than 10 minutes must elapse More than 10 minutes must el...

Страница 492: ...connected to the PC 5 Start the application 6 Configure necessary settings for startup operation as follows a Perform all necessary initial settings such as IP address etc Then click OK button Adapter setting window appears automatically b Select the connected adapter and click OK button Then unit registration window appears and starts scanning all connected units automatically c After finishing t...

Страница 493: ... network system For Heat recovery system To prevent the drop of signal level by taking distance of length or quantity of unit in VRF network with installing Signal amplifier signal level can be recovered Accessory Name and shape Q ty Application Cable tie 3 For mounting the power supply cable and transmission cable Screw M4 20 mm 4 For mounting the Network convertor Terminal register 1 Dust proof ...

Страница 494: ...e 3 A Switch Network segment A Network segment B Terminal resistor DIP SW setting Transmission cable Outdoor unit Master unit To slave unit Indoor unit Indoor unit Signal amplifier Terminal resistor Make sure to install 1 piece of terminal resistor to each segment Terminal resistor is provided for each outdoor unit but confirm that there is only one terminal resistor in the same segment 3 8 Signal...

Страница 495: ...nt system 2 A direction B direction Outdoor unit Transmission cable C direction Terminal resistor RB unit Indoor unit Signal amplifier Filter mode On Outdoor C direction Outdoor B direction Outdoor A direction Switch Disconnect switch 1Ø 50 60 Hz 208 240 V Fuse 3 A Make sure to install 1 piece of terminal resistor to each segment Terminal resistor is provided for each outdoor unit but confirm that...

Страница 496: ...ff once Otherwise the setting will not be recognized CN4 Connecting wire Accessory Body PCB Dimensions Unit in mm For dust proof bushing Ø1 1 8 28 3 1 2 89 5 3 1 2 89 5 For dust proof bushing Ø1 1 8 28 1 1 8 29 2 Ø3 16 5 For M4 20 mm screws Hole pitch 3 3 4 95 Hole pitch 3 3 4 95 8 5 16 211 2 5 8 67 4 Ø3 16 5 For M4 20 mm screws Ø7 8 22 For conduit 9 1 2 241 6 10 11 16 272 Hole pitch 11 5 16 288 3...

Страница 497: ...6 67 288 211 Weight lb g 3 1 500 Fuse capacity A 3 Wiring specifications Use Cable size Wire type Remarks Power supply cable 20 to 16 AWG 0 5 to 1 25 mm2 60245 IEC 57 or equivalent 1 Ø AC 208 240 V 50 60 Hz 2 wire ground Always ground the unit Transmission cable 22 AWG 0 33 mm2 LEVEL 4 NEMA Non polar 2 core twisted pair solid core shielded LonWorks compatible cable 3 8 Signal amplifier UTY VSGXZ1 ...

Страница 498: ...ed parts Accessory Name and shape Q ty Application Cable tie 4 For securing controller cable Screw M4 16 mm 3 For installing the External switch controller Installation manual 1 System diagram A B C Indoor Unit SW External input cable External switch controller Remote controller cable Remote controller cable Remote controller Use A B B C 2 wire type 164 ft 50 m or less 1 640 ft 500 m or less 3 wir...

Страница 499: ...mote controller cable External switch controller Indoor unit For polar 3 wire External input cable Remote controller cable External switch controller Indoor unit EXIN2 EXIN1 Remote Controller Cord REMOTE CONTROL 3 9 External switch controller UTY TERX 05 161 3 Adaptor Convertor units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 500: ...witchings such as opening and closing the window Otherwise the op eration signal cannot be received properly and the control from your remote controller will not work In such case canceling of the setting by using Service tool is required Prohibited connection example Example 1 Series connection of window contacts and card holder is prohibited EXIN2 EXIN1 UTY TERX Window contacts Indoor unit Card ...

Страница 501: ... 11 16 43 Hole 1 16 x 5 16 2 x 8 4 5 8 117 5 1 2 140 For open case 1 3 16 1 30 1 3 16 25 1 For code Ø1 4 7 Hole 2 Ø1 4 7 For code Ø1 4 7 2 Ø5 16 8 For code Ø3 16 5 Hole 2 Ø3 16 5 For code Ø3 16 5 25 30 3 9 External switch controller UTY TERX 05 163 3 Adaptor Convertor units CONTROL SYSTEM CONTROL SYSTEM ...

Страница 502: ...Insulated connection White Black Red Connecting cable Cut and insulate 3 Connect the remote controller cable to the connecting cable and insert it to the connector Set the DIP switch SW1 to 2WIRE on the PCB of the indoor unit Indoor unit PCB Remote controller cable Non polar Connecting cable Connector CNC01 onboard Connect to earth ground screw Functional earthing If necessary Set the DIP switch S...

Страница 503: ...lack Red Connecting cable Remote 3 Connect the remote controller cable to the connecting cable and insert it to the connector Set the DIP switch SW1 to 3WIRE on the PCB of the indoor unit Indoor unit PCB Remote controller cable Connecting cable Connector CNC01 onboard Connect to earth ground screw Functional earthing If necessary Set to 3WIRE the DIP switch SW1 NOTE Layout of terminal block and PC...

Страница 504: ...connected to the outdoor unit or the terminal block for power supply For polar 3 wire 1 Connect the end of remote controller cable directly to the exclusive terminal block 2 Set the DIP switch SW1 to 3WIRE on the PCB of the indoor unit Terminal block Functional earthing If necessary Remote controller cable Set to 3WIRE the DIP switch SW1 Indoor unit PCB Y1 Y2 Y3 Black White Red NOTES Layout of ter...

Страница 505: ...pe 22 to 16 AWG 0 33 to 1 25 mm2 Sheathed PVC cable Non polar 2 core twisted pair Maximum cable length 1 640 ft 500 m Remote controller cable 3 wire type 22 AWG 0 33 mm2 Polar 3 core twisted pair Maximum cable length 82 ft 25 m External input cable 22 to 16 AWG 0 33 to 1 25 mm2 2 core twisted pair Maximum cable length 164 ft 50 m Use sheathed cable in accordance with local rules for remote control...

Страница 506: ...on state P2 Arbitrary operation state Other settings are arbitrary Indoor unit External SW controller External contact SW 1 P1 Off P2 On Cool 80 F 26 C SW1 On Off Operation state P2 P1 On Off Cool 80 F 26 C Mode 1 P1 Arbitrary operation state P2 Arbitrary operation state Other settings are arbitrary SW1 On Off P1 P2 Cool Heat Operation state P1 On P2 Cool 80 F 26 C Heat 68 F 20 C 88 F 30 C 60 F 16...

Страница 507: ... 26 C Thermal sensor switch is connected and cooling and heating operations are switched Setting Wiring Operation example Mode 1 Off output Enabled P1 On Cool or Heat P2 On Cool or Heat Operation conditions Unit operating only Other settings are arbitrary Indoor unit Thermal sensor SW External switch controller is connected to all indoor units in the same refrigerant system and cooling and heating...

Страница 508: ...urchased parts Accessory Name and shape Q ty Application Cable tie 5 For External switch controller and cable binding Screw M4 16 mm 2 For installing the External switch controller Installation manual 1 System diagram A B C Indoor Unit SW External input cable External switch controller Remote controller cable Remote controller cable Remote controller A B B C 164 ft 50 m or less 82 ft 25 m or less ...

Страница 509: ...ller External contact SW 1 External contact SW 2 Open circuit voltage 12 V 2 V Short circuit current 2 mA Short circuit detection resistance R on 1 kΩ Open circuit detection resistance R off 50 kΩ Dimensions Unit in mm 2 15 16 75 1 3 16 30 4 3 4 120 13 16 21 3 4 19 5 3 4 19 5 3 4 19 5 3 4 19 5 11 16 18 2 3 8 60 3 5 16 83 5 1 2 12 5 5 Ø1 4 7 Left view Front view Rear view 3 10 External switch contr...

Страница 510: ... to the exclusive terminal block 2 Set the DIP switch SW1 to 3WIRE on the PCB of the indoor unit Terminal block Functional earthing If necessary Remote controller cable Set to 3WIRE the DIP switch SW1 Indoor unit PCB Y1 Y2 Y3 Black White Red NOTES Layout of terminal block and PCB is varies depending on the type of indoor unit Operation may fail if it is connected to the outdoor unit or the termina...

Страница 511: ...Red Connecting cable Remote 3 Connect the remote controller cable to the connecting cable and insert it to the connector Set the DIP switch SW1 to 3WIRE on the PCB of the indoor unit Indoor unit PCB Remote controller cable Connecting cable Connector CNC01 onboard Connect to earth ground screw Functional earthing If necessary Set to 3WIRE the DIP switch SW1 NOTE Layout of terminal block and PCB is ...

Страница 512: ...SW2 On Off Operation state On Off P1 P1 On Cool 80 F 26 C P2 Off P2 Cool 80 F 26 C Controlling operation by On or Off of an external contact switch Setting Wiring Operation example Mode 1 P1 Arbitrary operation state P2 Arbitrary operation state Other settings are arbitrary Indoor unit External SW controller External contact SW 1 P1 Off P2 On Cool 80 F 26 C SW1 On Off Operation state P2 P1 On Off ...

Страница 513: ...ting only Other settings are arbitrary Indoor unit Thermal sensor SW External switch controller is connected to all indoor units in the same refrigerant system and cooling and heating operations are switched by one thermal sensor P1 On Cool 80 F 26 C P2 On Heat 70 F 21 C SW1 Operation state On Off Heat Off On P2 P1 Cool Cool 74 F 23 C 80 F 26 C 70 F 21 C Preventing chatter noise within 1 minute af...

Страница 514: ...ws 10 32 bit 2 GB or more for Windows 7 64 bit Windows 8 1 64 bit and Windows 10 64 bit HDD 40 GB or more of free space Display 1 366 768 or higher resolution Interface 2 USB ports 1 USB port is required for WHITE USB KEY connection 1 USB port is required for Echelon U10 USB Network Interface Software Adobe Reader 9 0 or later Internet transmission rate in remote access Internet environment capabl...

Страница 515: ...sed along with the detailed information in list form to check the operation status of units and make detail analysis on the cause in case an error occurs Equipment detail Status list Displays the detail information for sensor values electrical components etc of units in a specified refrigerant system in list form The information here can be used along with the detailed information in diagram form ...

Страница 516: ... in tree form Remote setting Function Field setting for indoor units is realized remotely System time setting An arbitrary time is set for all the remote controllers within the system Central control forced release The operation setting restriction function of the indoor units set form the controller can be forcibly released remote controller inhibit temperature upper lower limit setting Model nam...

Страница 517: ... version Remote operation Through the Internet Service tool in the PC on VRF system side can be operable in real time from remote side PC Chat enabled and the acquired data by the Service tool can be downloaded by remote side PC 4 1 Service tool UTY ASGXZ1 05 179 4 Service and web monitoring tool CONTROL SYSTEM CONTROL SYSTEM ...

Страница 518: ...space Display 1 366 768 or higher resolution Interface USB port for Echelon U10 USB Network Interface Max 4 software protection key Either of the following interface is required for remote connection Internet using LAN Ethernet port is required Software Adobe Reader 9 0 or later Internet transmission rate in remote access Internet environment capable for communication speed of 3 Mbps or more for u...

Страница 519: ...MGX can be used Support 4 VRF network systems PC USB adapters Max 4 ports per PC permit control and monitoring of up to 1 600 units Suitable for large scale buildings or hotels Max 400 indoor unit Max 400 indoor unit Max 400 indoor unit Max 400 indoor unit VRF network system 1 VRF network system 2 VRF network system 3 VRF network system 4 USB Adapter Locally purchased Personal Computer Locally pur...

Страница 520: ...rror history Graph Data backup Operation setting E mail automatic transmission of system malfunction Network topology analyzer Remote setting System time setting Central control forced release Model name writer Error memory reader Time guard information Off line data reader Version Software update Available only during connection to the Internet 4 2 Web monitoring tool UTY AMGXZ1 05 182 4 Service ...

Страница 521: ...6 SYSTEM DESIGN 2019 11 01 DV_CH06_J3LU061EF_02 ...

Страница 522: ...e size 06 19 2 4 Selection of pipe heat insulating material 06 25 2 5 Additional charge calculation 06 26 2 6 Piping design example 06 28 3 Piping connection 06 35 3 1 Piping to outdoor unit 06 37 3 2 Separation tube 06 41 3 3 Header 06 45 4 Wiring design 06 48 4 1 Electrical wiring 06 48 4 2 Power supply cable 06 50 4 3 Transmission cable 06 54 4 4 Controller cable 06 62 5 Drain connection 06 64 ...

Страница 523: ...ng capacity 1 to 18 units 8 AOU96RLAVL 96 000 1 to 24 units 10 AOU120RLAVL 120 000 1 to 30 units CAUTION When all indoor units are operating at maximum capacity individual indoor unit operates at a slightly lower capacity When connecting more than 100 Do not exceed both of connectable cooling capacity range and maximum connectable indoor unit quantity otherwise it may cause hinder the return of th...

Страница 524: ...L 72 72 2 50 36 3 150 108 2 1 3 36 60 108 OK Indoor unit 1 AUUB30TLAV2 30 1 60 Indoor unit 2 AUUB30TLAV2 30 Example 2 OK Outdoor unit Indoor unit 1 Indoor unit 2 Indoor unit 3 Capacity ratio 130 Model name Cooling capacity Total capacity Connectable indoor unit capacity Judge Min Max kBtu h Outdoor unit AOU72RLAVL 72 72 2 50 36 3 150 108 2 1 3 36 84 108 OK Indoor unit 1 AUUB30TLAV2 30 1 84 Indoor ...

Страница 525: ... 3 1 108 120 Prohibited Indoor unit 1 AUUB36TLAV 36 1 120 Indoor unit 2 AUUB36TLAV 36 Indoor unit 2 AUUB48TLAV2 48 Example 4 OK Outdoor unit Indoor unit 1 Capacity ratio 66 Model name Cooling capacity Total capacity Connectable indoor unit capacity Judge Min Max kBtu h Outdoor unit AOU72RLAVL 72 72 2 50 36 3 150 108 2 1 3 36 48 108 OK Indoor unit 1 AUUB48TLAV2 48 1 48 1 1 Refrigerant system 06 3 1...

Страница 526: ...rk segment Terminal resistor Terminal resistor means resistor should set in network segment Overview VRF network system should keep both of number of unit and wiring length When system exceeds either number of unit or wiring length the system should be divided Different VRF series may not coexist within the same network 1 2 3 4 5 6 25 1 2 3 4 1 2 3 1 2 3 4 5 62 4 62 62 64 64 64 63 63 63 34 26 27 2...

Страница 527: ...k convertor UTY VGGXZ1 Total length of group remote controller cable to Network convertor 328 ft 100 m Used for group remote controller UTY VTGX Remote controller to Network convertor 328 ft 100 m Used for single split air conditioner Indoor unit to Network convertor 328 ft 100 m Network convertor for LonWorks UTY VLGX In each network segment 1 640 ft 500 m Modbus convertor UTY VMGX In each networ...

Страница 528: ...0 100 50 NOTES 1 Different VRF series may be connected for each of the 4 VRF networks supported by the product but different series may not coexist within the same network VR II V II J II J IIS and J IIIL can exist together in same network V and S can exist together in same network too 2 For 1 VRF network system total number of Touch panel controller Central remote con troller Network convertor fo...

Страница 529: ...ch panel UTY RNRUZ Maximum controllable indoor units 16 SET TEMP START STOP Wired remote controller UTY RNKU Maximum controllable indoor units 16 Simple remote controller UTY RSRY UTY RSKU Maximum controllable indoor units 16 Simple remote controller Without operation mode UTY RHRY UTY RHKU Maximum controllable indoor units 16 Wireless remote controller UTY LNHU 1 2 VRF network system 06 7 1 Syste...

Страница 530: ...t convertor UTY TTRX Maximum controllable indoor units 16 BACnet gateway Hardware UTY VBGX 4 1 Maximum controllable indoor units 128 BACnet gateway Software UTY ABGXZ1 1 2 Maximum controllable VRF network system 4 Maximum controllable remote controller group 1 600 per 4 VRF network system Maximum controllable indoor units 1 600 per 4 VRF network system Maximum controllable group 1 600 per 4 VRF ne...

Страница 531: ... KNX convertor for VRF Modbus conver tor for VRF BACnet gateway Hardware is 16 including 1 Network convertors for LonWorks 2 Different VRF series may be connected for each of the 4 VRF networks supported by the product but different series may not coexist within the same network VR II V II J II J IIS and J IIIL can exist together in same network V and S can exist together in same network too 3 1 S...

Страница 532: ...TY LNHU 0 IR receiver unit UTY TRHX 0 IR receiver unit UTB YWC 0 IR receiver unit for cassette type UTY LRHYB1 0 IR receiver unit for circular flow cassette type UTY LBHXD 0 Human sensor kit for circular flow cassette type UTY SHZXC 0 Remote sensor unit UTY XSZX 0 Network convertor UTY VTGX UTY VGGXZ1 1 Network convertor for LonWorks UTY VLGX 1 Adaptor Convertor Modbus convertor for VRF UTY VMGX 1...

Страница 533: ...tion Do not install at the place of following conditions A place exposed to strong or seasonal winds A place where the blown air accumulate A place where there are obstructions to the air near to the inlet and outlet A place exposed to radiation from other heat sources A place where the discharged air will affect animals or plants A place where the noise and hot air will disturb the neighbor A pla...

Страница 534: ...ion resistant rubber to prevent the transmission of vibration to the floor Securely fix the unit when it may be in a position exposed to strong winds When cooling operation will be conducted at outdoor air temperature below 23 F 5 C the out door unit must be installed in a position that is higher than or equal to those of indoor units CAUTION If the unit is installed in a region that is exposed to...

Страница 535: ...cation with high temperature A place near a source of heat steam or flammable gas A place where there is oily smoke machine oil i e factory salty environment with direct sea breeze and too much of dust Mind the following when installing or using the unit Install with the lowest moving parts at least 95 in 2 4 m above floor or grade level Install the indoor and outdoor units power wiring signal wir...

Страница 536: ... MPa Select the pipe size in accordance with the regional standard Lubricant Refrigerant R410A Mixed refrigerant Lubricant FVC68D Tools R410A work requires a number of special tools The items below with symbol are specialized for R410A Make sure that R22 tools cannot be used on R410A systems Tool name Process and application Pipe cutter Pipe cutting Refrigerant piping work Flaring tool Pipe flarin...

Страница 537: ...be of specified material and thickness to meet endurance pressure of the pipe 609 psi 4 2 MPa Do not use pipe with dust and dirt sticking to it during piping connection work Always flow dry nitrogen through piping while braz ing Drain piping work Duct work Installation work Remote controller installation Electrical wiring work Do not connect to the power supply Outdoor unit foundation work Outdoor...

Страница 538: ...h refrigerant Use a vacuum pump with check valve to prevent the back flow of vacuum pump oil into the refrigerant system Additional refrigerant charge Calculate additional refrigerant charge Add additional re frigerant with R410A gage manifold and hose Gas leakage check Outside panel installation Test run and adjustment End of work Hand over Customer training 2 1 Important items when using refrige...

Страница 539: ...the pipe size is larger than designated size The refrigerant flow velocity will drop Refrigerant oil will not return to the outdoor unit Insufficient refrigerant oil resulting in compressor damage The refrigerant in liquid pipe will flush easily Insufficient cooling and heating If the pipe size is smaller than designated size The refrigerant circulation volume will drop Insufficient cooling and he...

Страница 540: ...unit and the first separation tube 10 ft 3 m or more a Allowable height difference Between outdoor unit and indoor unit Outdoor unit is higher than indoor unit 164 ft 50 m or less H1 Outdoor unit is lower than indoor unit O T 2 23 F 5 C 131 ft 40 m or less O T 2 23 F 5 C 3 16 ft 5 m or less Between indoor unit Outdoor unit is higher than indoor unit 164 ft 50 m or less H2 Outdoor unit is lower tha...

Страница 541: ...refer to Important items when using refrigerant R410A on page 06 14 Total cooling capacity of indoor unit is the total value for the cooling capacity at rated condition of indoor unit connected downstream Cooling capacity table Outdoor unit Ton Model name Cooling capacity Btu h Maximum connectable indoor unit 6 AOU72RLAVL 72 000 18 8 AOU96RLAVL 96 000 24 10 AOU120RLAVL 120 000 30 2 3 Pipe size 06 ...

Страница 542: ...0 450 Slim duct Slim concealed floor 7 500 9 500 ARUL7TLAV2 7 13 16 27 9 16 24 7 16 198 700 620 9 500 10 900 ARUL9TLAV2 12 000 13 500 ARUL12TLAV2 14 000 15 600 ARUL14TLAV2 18 000 20 000 ARUL18TLAV2 7 13 16 35 7 16 24 7 16 198 900 620 Medium static pressure duct 24 000 27 000 ARUM24TLAV2 10 5 16 44 11 16 27 9 16 270 1 135 700 30 000 34 000 ARUM30TLAV2 36 000 40 000 ARUM36TLAV2 High static pressure ...

Страница 543: ...16 8 268 840 203 14 000 15 600 ASUA14TLAV1 18 000 20 000 ASUB18TLAV1 12 5 8 39 5 16 9 3 8 320 998 238 24 000 27 000 ASUB24TLAV1 30 000 34 000 ASUA30TLAV2 13 3 8 45 1 4 11 340 1 150 280 34 000 38 000 ASUA36TLAV2 7 500 9 500 ASUA7TLAV 10 13 16 31 1 8 8 7 16 275 790 215 12 000 13 500 ASUA12TLAV 18 000 20 000 ASUB18TLAV 12 5 8 39 5 16 9 320 998 228 24 000 27 000 ASUB24TLAV 2 3 Pipe size 06 21 2 Piping...

Страница 544: ... 96 96 000 3 8 9 52 7 8 22 22 10 120 120 000 1 2 12 70 1 1 8 28 58 Condition 1 Total indoor unit capacity ratio 110 Ton Outdoor unit model code Outdoor unit cooling capacity Outside diameter Liquid pipe Gas pipe Btu h in mm 6 72 72 000 3 8 9 52 3 4 19 05 8 96 96 000 1 2 12 70 7 8 22 22 10 120 120 000 1 2 12 70 1 1 8 28 58 Condition 2 Between outdoor unit and first separation tube or header 229 ft ...

Страница 545: ...oor units connected downstream Pipe size table C Between Separation tube Header and indoor unit Indoor unit cooling capacity Outside diameter Liquid pipe Gas pipe Btu h in mm 4 000 7 500 9 500 1 4 6 35 3 8 9 52 12 000 14 000 18 000 1 4 6 35 1 2 12 70 24 000 30 000 34 000 36 000 48 000 60 000 3 8 9 52 5 8 15 88 72 000 3 8 9 52 3 4 19 05 96 000 3 8 9 52 7 8 22 22 NOTES If the selected pipe diameter ...

Страница 546: ...indoor unit x Btu h Model name x 96 500 UTP AX090A 96 500 x UTP AX180A Header Total cooling capacity of indoor units x Btu h 3 to 6 Branches 3 to 8 Branches x 96 500 UTR H0906L UTR H0908L 96 500 x UTR H1806L UTR H1808L 2 3 Pipe size 06 24 2 Piping design SYSTEM DESIGN SYSTEM DESIGN ...

Страница 547: ... position than the indoor unit fill the connecting part gap with putty etc to prevent the dew condensation water of the valve of the outdoor unit from flowing to the indoors from the gap between the pipe and the heat insulating material Liquid pipe and gas pipe should be completely insulated with same specification Water may leak from the refrigerant lines if the insulation is not completely seale...

Страница 548: ...ount for pipe length in mm lb ft kg m Ø1 4 6 35 0 014 0 021 Ø3 8 9 52 0 039 0 058 Ø1 2 12 70 0 077 0 114 A Total length of Ø1 2 in 12 70 mm liquid pipe a 0 077 lb ft 0 114 kg m Total length of Ø3 8 in 9 52 mm liquid pipe a 0 039 lb ft 0 058 kg m in mm in mm lb kg lb kg Total length of Ø1 4 in 6 35 mm liquid pipe a 0 014 lb ft 0 021 kg m Total in mm lb kg lb kg A lb kg Round up A to 2 decimal place...

Страница 549: ...2RLAVL 6 Total amount of refrigerant C 44 09 lb 20 0 kg AOU96RLAVL 8 AOU120RLAVL 10 Total amount of refrigerant C 56 44 lb 25 6 kg When total refrigerant amount exceed limitation Reduce pipe length for refrigerant system Change the refrigerant system configuration 2 5 Additional charge calculation 06 27 2 Piping design SYSTEM DESIGN SYSTEM DESIGN ...

Страница 550: ...h 5 12 kBtu h 6 12 kBtu h 7 12 kBtu h System configuration Indoor unit Model name Capacity kBtu h 1 ARUL12TLAV2 12 0 2 ARUL12TLAV2 12 0 3 ARUL12TLAV2 12 0 4 ARUL12TLAV2 12 0 5 ARUL12TLAV2 12 0 6 ARUL12TLAV2 12 0 7 ARUL12TLAV2 12 0 8 ARUL9TLAV2 9 5 Total capacity 93 5 Outdoor unit Model name Capacity kBtu h 1 AOU72RLAVL 72 0 Total capacity 72 0 Capacity ratio Total capacity of indoor unit Total cap...

Страница 551: ...1 2 12 70 32 10 g Ø3 8 9 52 Ø5 8 15 88 16 5 g1 Ø1 4 6 35 Ø1 2 12 70 32 10 h Ø1 4 6 35 Ø3 8 9 52 22 7 Limitation check Pipe Diagram Example Limitation Judge ft m Total pipe length Total 498 152 1 312 400 or less OK Between outdoor unit and farthest indoor unit a b c d e f g h 252 77 393 120 or less OK Between the first separation tube and the farthest indoor unit b c d e f g h 121 37 295 90 or less...

Страница 552: ...80 ft 0 014 lb 269 ft 14 559 lb A 0 114 kg 15 m 0 058 kg 55 m 0 021 kg 82 m 6 622 kg Calculation of factory charge amount B Outdoor unit Model name Factory charge amount 1 AOU72RLAVL 24 25 lb 11 0 kg B 24 25 lb 11 0 kg Total refrigerant amount check C C A B 14 559 24 25 38 809 lb 44 09 lb OK C A B 6 622 11 0 17 622 kg 20 kg OK Check pipe length and height difference between the units by comparing ...

Страница 553: ...t Total capacity of outdoor unit 78 0 96 0 81 25 Within 50 to 150 Selection of Separation tube and Header Branch kit no Model name Quantity HD1 UTR H0906L 1 Selection of pipe size Pipe no Pipe diameter in mm Length example ft m Liquid pipe Gas pipe a Ø1 2 12 70 Ø7 8 22 22 232 71 b1 Ø1 4 6 35 Ø1 2 12 70 19 6 b2 Ø3 8 9 52 Ø5 8 15 88 19 6 b3 Ø3 8 9 52 Ø5 8 15 88 22 7 When the length of the pipe betwe...

Страница 554: ... A Diameter of liquid pipe Additional amount for pipe length Liquid pipe length in mm lb ft kg m ft m Ø1 2 12 70 0 077 0 114 232 71 Ø3 8 9 52 0 039 0 058 42 13 Ø1 4 6 35 0 014 0 021 19 6 A 0 077 lb 232 ft 0 039 lb 42 ft 0 014 lb 19 ft 19 768 lb A 0 114 kg 71 m 0 058 kg 13 m 0 021 kg 6 m 8 974 kg Calculation of factory charge amount B Outdoor unit Model name Factory charge amount 1 AOU96RLAVL 24 25...

Страница 555: ...32 5 kBtu h System configuration Indoor unit Model name Capacity kBtu h 1 ARUH60TLAV 60 0 2 ARUM30TLAV2 30 0 3 ARUL14TLAV2 14 0 4 ARUL9TLAV2 9 5 5 ARUL9TLAV2 9 5 6 ARUL9TLAV2 9 5 Total capacity 132 5 Outdoor unit Model name Capacity kBtu h 1 AOU120RLAVL 120 0 Total capacity 120 0 Capacity ratio Total capacity of indoor unit Total capacity of outdoor unit 132 5 120 0 110 4 Within 50 to 150 Selectio...

Страница 556: ...1 269 82 17 5 or more OK Between outdoor unit and the first separation tube a 246 75 10 3 or more OK Calculation of additional charge refrigerant Calculation of additional amount for pipe length A Diameter of liquid pipe Additional amount for pipe length Liquid pipe length in mm lb ft kg m ft m Ø1 2 12 70 0 077 0 114 311 95 Ø3 8 9 52 0 039 0 058 104 32 Ø1 4 6 35 0 014 0 021 82 25 A 0 077 lb 311 ft...

Страница 557: ...and installation Make sure that no dust or water enters the pipe during preparation or installation When installing the pipe make bends as few as possible and make radius as large as possi ble Cut the branch kit at the right size or use the reducer to match the pipe to the branch kit Piping treatment The pipes vibrate expand and contract during operation so if loads are concentrated in one area it...

Страница 558: ...state of brazing pipe section Nitrogen gas used Nitrogen gas used but not sufficient Oxigen gas still inside the pipe Nitrogen gas does not used When brazing the pipes do not use flux If the flux is chlorine based the pipes will corrode and when the flux contains fluorine the refrigerant oil will deteriorate etc Using the flux has an adverse affect on the refrigerant piping system For brazing mate...

Страница 559: ... the edge with rust preventive paint is recommend ed The piping can be connected from 3 directions of the front the lateral side and the bottom When connecting at the bottom remove the service panel and piping cover on the front of the out door unit and open the knockout hole provided at the bottom corner of the piping outlet When cutting the slits use a steel saw and cut out the 2 slits as shown ...

Страница 560: ...ase Fig A 3 11 16 94 2 3 8 61 2 3 8 61 3 15 16 100 13 16 21 3 5 8 92 3 9 16 90 9 16 14 2 3 8 60 1 2 12 Front connection Lateral connection Bottom connection Slit Slit Fig B Fig C Bottom connection 3 1 Piping to outdoor unit 06 38 3 Piping connection SYSTEM DESIGN SYSTEM DESIGN ...

Страница 561: ...nch pipe in accordance with the following instructions 1 Verify that the liquid side and gas side 3 way valves are closed Fig A 2 Cut the end of the liquid side and gas side pinch pipe and vent the gas inside the pinch pipe Fig B 3 After all the gas is vented melt the brazing filler metal on connecting part using a torch and remove the pinch pipe Fig C 3 way valves Pinch pipes End of pinch pipes F...

Страница 562: ... or brazing the joint pipe carry out the work while cooling down the 3 way valve sufficiently Braze the joint pipe onto the 3 way valve at the liquid and gas side Install the joint pipe appropri ately so that it can be connected easily with the main pipe Braze the joint pipe at the liquid and gas side with the main pipe NOTE Be sure to supply nitrogen when brazing Joint pipe A L Joint pipe A acces...

Страница 563: ...in 0 to 3 mm 1 2L 1 8 0 in 3 0 mm L 1 2L Joint pipe Branch kit Field pipe Standard cutting position Connections NOTE Insert the field pipe firmly until it touches the joint pipe Separation tube When the pipe size of the Separation tube itself does not match or when piping sizes differ ever if it cuts the pipe use attached reducer or attached expander Joint pipe Separation tube Field pipe Reducer o...

Страница 564: ... a reduction in performance 15 Prohibited Good Prohibited During piping work apply nitrogen gas while brazing the pipes If pipes are brazed without ap plying nitrogen gas it will create a large amount of oxidation film which will cause a critical malfunction To prevent moisture or foreign matter from entering during work do not leave the piping open Refer to the installation manual supplied with t...

Страница 565: ...tance 2 ft 0 5 m or more for straight part to Separation tube in order to prevent the outdoor unit malfunction and generation of refrigerant noise About the connecting curvature of field pipe and Separation tube The filed pipe should be connected to the Separation tube so that the curved angle on each side is 3 degree or less 3 3 A B 2 ft 0 5 m 0 to 1 in 0 to 26 mm 0 to 1 in 0 to 26 mm Allowed val...

Страница 566: ...d heat insulation and the heat insulation on the local piping Insulations Locally purchased Contact each other Tapes Locally purchased CAUTION Insulate the liquid and gas pipe completely If not it may cause the water condensation or per formance reduction Wrap the heat insulation with tape or pipe cover in order to extend the life time of heat insula tion Take proper measurement to strengthen by u...

Страница 567: ...it side You can connect the indoor unit to any branch Always have at least one indoor unit connected to the port furthest opposite the outdoor unit side 2 Use a pipe cutter to cut at the location that matches the piping size or use expanders as neces sary Joint pipe Connections Field pipe Expander Cut in the center of the connections 3 Attach a plugging pipe provided if there is no piping connecte...

Страница 568: ...pe Liquid pipe CAUTION Separation tube is not allowed to install Header kit Outdoor unit Header Indoor unit Header Outdoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit 3 3 Header 06 46 3 Piping connection SYSTEM DESIGN SYSTEM DESIGN ...

Страница 569: ... line β2 Horizontal line Brazing point α2 Straight pipe length A straight pipe minimum length 2 ft 0 5 m before Header is necessary in order to separate the refrigerant exactly Main pipe 2 ft 0 5 m or more To indoor unit To indoor unit To indoor unit 2 ft 0 5 m or more Heat insulation installation After brazing the piping attach heat insulation 1 Remove the protective paper for the tape on the hea...

Страница 570: ...umidity locations install using Ground Fault Equipment Breaker GFEB to reduce the risk of leaking current which may result in electric shock or poten tial fire CAUTION When approved for use in local code we suggest installing Ground Fault Equipment Breaker GFEB In that case GFEB shall be per Fujitsu recommended capacity in order to prevent mal function of breaker device Always use a dedicated powe...

Страница 571: ...olled Total wiring length Max 1 640 ft 500m Touch Panel Controller System Controller IR receiver unit Duct type indoor unit can be controlled with wireless remote controller Service Tool Multi system Card key Single system Outdoor unit Indoor unit Cassette Indoor unit Duct RB unit Single RB unit Multi Touch Panel Controller Group Remote Controller Wired Remote Controller Wired Remote Controller Ce...

Страница 572: ...value increase the wire diameter to stay within design limits Indoor unit Model Recommended cable size AWG MAX CKT BKR A Breaker for leakage current Remarks All models 16 to 10 15 Refer to Table B 208 230 V 60 Hz 2 wire ground Refer to the table for the breaker specifications of each installation condition Perform the power crossover wiring within the range of the same refrigerant system When the ...

Страница 573: ...nits 30 mA 0 1 sec or less 36 or less 100 mA 0 1 sec or less 37 to 121 If the total number of units connected to the breaker exceeds 36 either add a 30 mA breaker or use a breaker with a greater capacity NOTE For how to count the units refer to the table below Connected unit Q ty Count Indoor units Except High static pressure duct 1 1 Indoor units High static pressure duct 1 3 Example 1 Connected ...

Страница 574: ...l standard When approved for use in local code we suggest installing Ground Fault Equipment Breaker GFEB In that case GFEB shall be per Fujitsu recommended capacity in order to prevent mal function of breaker device Example 1 Using terminal board for indoor unit Sub breaker Sub breaker Sub breaker 40A 40A 50A Power cable Power cable Power cable Sub breaker Terminal board Terminal board Sub breaker...

Страница 575: ...ne breaker as shown below b a c AC 230 V AC 24 V c AC 24 V c AC 24 V a Circuit breaker b Relay c External power supply unit b a c AC 230 V AC 24 V b a c AC 230 V AC 24 V b a c AC 230 V AC 24 V AC 230 V power breaker OFF only for some indoor units connected with remote controller cable 4 2 Power supply cable 06 53 4 Wiring design SYSTEM DESIGN SYSTEM DESIGN ...

Страница 576: ...C Ohm 1 000 ft Ohm 305 m Less than 18 DC resistance unbalancing 68 F 20 C Less than 5 Dielectric voltage Between conductor and conductor V min AC 350 Insulation resistance 68 F 20 C Between conductor and conductor Mohm km More than 500 After charging DC 500 V 1 min Static capacitance between conductors 1 KHz nF km Less than 56 Unbalanced static capacitance To ground 1 KHz nF km Less than 3 28 Char...

Страница 577: ... the following cases Signal amplifier is required When the total length of the transmission cable exceeded 1 640ft 500 m AB BC BD DE EF 1 640ft 500 m Fig 1 When total number of the units is over 64 When the total length of the transmission cable exceeded 1 640ft 500 m Transmission cable length between each unit 1 312ft 400 m Total transmission cable length 11 811ft 3 600 m A B C D E F A B C D NS 1...

Страница 578: ...nsmission cable like as Fig 1 and Fig 2 Transmission cable Refrigerant system 1 Refrigerant system 2 Refrigerant system 3 Transmission cable Transmission cable Fig 1 Fig 2 Indoor unit Indoor unit Indoor unit Outdoor unit Outdoor unit Outdoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Refrigerant system 1 Refrigerant system 2 Refrigerant sys...

Страница 579: ...or unit Z1 Z2 Connection for different refrigerant circuit of outdoor unit 3 Confirm the transmission wiring rule For details of wiring rules refer to Wiring rules on page 06 55 4 Confirm how to install Signal amplifier For details of wiring rules refer to Wiring rules on page 06 55 5 Confirm how to wire transmission cable Confirm how to connect transmission cable between indoor units Arrange so t...

Страница 580: ...y Outdoor unit Remote control unit Indoor unit Breaker Transmission Transmission Remote control Remote control Remote control Transmission Transmission Breaker Breaker Breaker Indoor unit Indoor unit Power supply Power supply Power supply 208 230V 3N 60 Hz 208 230V 1Ø 60 Hz 208 230V 1Ø 60 Hz 208 230V 1Ø 60 Hz Remote control unit Remote control unit X1 X2 Indoor units to outdoor unit Z1 Z2 Connecti...

Страница 581: ...ircuit breaker Outdoor unit power supply cable Indoor unit power supply cable Remote controller cable Transmission cable 208 230V 1Ø 60Hz 208 230V 3Ø 60Hz 4 3 Transmission cable 06 59 4 Wiring design SYSTEM DESIGN SYSTEM DESIGN ...

Страница 582: ...r communication for one terminal In this case use a terminal box NOTE Do not loop Example 1 Connecting each outdoor unit and indoor unit with one wiring Refrigerant system 1 Signal amplifier Refrigerant system 2 Refrigerant system 3 Example 2 Separating transmission cable Separate on the terminal for transmission cable Separate using terminal board System controller Refrigerant system 1 Refrigeran...

Страница 583: ...erant system 1 Refrigerant system 2 Refrigerant system 3 System controller Example 4 Combination of example 2 and 3 Terminal board Refrigerant system 1 Refrigerant system 2 Refrigerant system 3 System controller 4 3 Transmission cable 06 61 4 Wiring design SYSTEM DESIGN SYSTEM DESIGN ...

Страница 584: ...m2 Shielded polar 3 core External input 22 AWG 0 33 mm2 Shielded non polar 2 core twisted pair IR receiver unit for All duct type 16 ft 5 m cable attached IR receiver unit for Circular flow cassette type Indoor unit Connection cable IR receiver unit for Cassette type Human sensor kit for Circular flow cassette type Remote sensor unit 33 ft 10 m cable attached Drain pump unit 1 For maximum connecta...

Страница 585: ...axi mum cable length Maximum connectable number of remote controller 2 wire type Cable size S Total cable length L AWG mm2 L 328 ft 100 m 328 ft 100 m L 820 ft 250 m 820 ft 250 m L 1 640 ft 500 m 16 1 25 4 4 4 18 0 75 1 25 S 0 75 4 4 2 20 0 5 0 75 S 0 5 4 2 2 22 0 3 0 5 S 0 3 4 1 1 4 4 Controller cable 06 63 4 Wiring design SYSTEM DESIGN SYSTEM DESIGN ...

Страница 586: ...e drain water in the pipe may freeze in extremely cold weather As the drain water flows out of the outdoor unit during heating operation install the drain pipe and correct it to a commercial 5 8 in 16 mm hose When installing a drain pipe plug all the holes other than the drain pipe mounting hole in the bot tom of outdoor unit with drain cap so there is no water leakage 17 9 16 in 446 mm 23 5 8 in ...

Страница 587: ...he accessory band Except compact wall mounted type and wall mounted type Compact cassette type 11 in 300 mm or less Max 27 in 700 mm Attached band Drain hose accessory Downward gradient 1 100 or more Horizontal or upward gradient Ø3 4 I D Ø1 1 16 O D Locally purchased 60 to 79 in 1 5 m to 2 0 m Downward gradient 1 100 or more Hanging fitting Air bleeding Rise Trap Ï Ï Ï Prohibited Drain lift up pi...

Страница 588: ... 16 O D Locally purchased Ø3 4 I D Ø1 1 16 O D 11 in 300 mm or less Max 33 in 850 mm Air bleeding Rise Trap Ï Ï Ï Prohibited Drain lift up pipe restrictions Lift up height 33 in 850 mm from ceiling Drain hose pipe length 11 in 300 mm between indoor unit and lift up pipe Water leakage may result from a failure to adhere to the restrictions above 5 2 Indoor unit 06 66 5 Drain connection SYSTEM DESIG...

Страница 589: ...gradient 1 100 or more 28 in 700 mm or less Use general hard polyvinyl chloride pipe VP25 O D 2 in 32 mm Do not perform a rise trap and air bleeding Provide a downward gradient 1 100 or more Provide supporters when long pipes are installed Use an insulation material as needed to prevent the pipes from freezing Install the pipes in a way that allows for the removal of the control box 5 2 Indoor uni...

Страница 590: ...t 60 to 79 in 1 5 m to 2 0 m Max 28 in 700 mm Ï Ï Ï Floor standing concealed setting Prohibited Trap Drain cap Rise Install the drain pipe with downward gradient 1 50 to 1 100 and so there are no rises or traps in the pipe Use general hard polyvinyl chloride pipe VP25 O D 2 in 32 mm and connect it with adhe sive polyvinyl chloride so that there is no leakage When the pipe is long install supporter...

Страница 591: ...a drain port on the left and right sides Select the drain port to match the local conditions Nylon fastener Drain port Drain cap CAUTION Always check that the drain cap is installed to the unused drain port and fastened with the nylon fastener If the drain cap is not installed or is not sufficiently fastened by the nylon fastener water may drip during the cooling operation 5 2 Indoor unit 06 69 5 ...

Страница 592: ...1 100 or more Make sure that the drain hose is installed without rises Make the trap near to the indoor unit position the trap in a location where it can be cleaned Safety drain pipe There is no need to provide a trap for the overflow drain If the overflow drain is connected to the main drain pipe make the connection below the trap on the main drain pipe Once installation is completed checked the ...

Страница 593: ... Drain pan Drain hose Drain pan Drain cap Left piping Pipe Cable Drain hose Cable For connection from the left rear Putty Putty Ï Ï Ï No upward slope Accumulated drain water Air End of drain hose is immersed in water 2 in 50 mm or less from ground No gap Drain cock Drain cap Hexagon wrench Ï No upward slope 5 2 Indoor unit 06 71 5 Drain connection SYSTEM DESIGN SYSTEM DESIGN ...

Страница 594: ...e with the VT wire Drain hose VT wire Base Bottom Intake grille Cut the grille Pass the drain hose through here Piping hole Floor console setting Arrange the drain hose lower than this position Ï Ï Prohibited Prohibited Do not install the unit so that the drain hose side is too high Height A should be less than 13 16 in 5 mm 5 2 Indoor unit 06 72 5 Drain connection SYSTEM DESIGN SYSTEM DESIGN ...

Страница 595: ...ted Drain hose End in water Supporter 60 to 79 in 1 5 to 2 0 m Rise Trap Fasten the drain pipe with VT wire so that the pipe slopes correctly within the indoor unit Drain hose Indoor unit rear view VT wire 5 2 Indoor unit 06 73 5 Drain connection SYSTEM DESIGN SYSTEM DESIGN ...

Страница 596: ...ther than ASUB18TLAV1 and ASUB24TLAV1 Ï Ï Ï Prohibited Drain cap Drain hose Saddle No gap No gap Drain cap Drain Cock End in water Wave Liftted up Insulation Insulation Indoor unit drain hose Hexagonal wrench Installation method of drain cap For left outlet piping cut off the piping outlet cutting groove with a hacksaw Remove the drain cap by pulling at the projection at the end of the cap with pl...

Страница 597: ... 1 1 2 38 mm or more Downward gradient 1 100 to 1 50 A Compact cassette type 28 in 700 mm or less Circular flow cassette type type Cassette type 34 in 850 mm or less For High static pressure duct type 4 in 100 mm or more For Mini duct type and Slim duct type 28 in 700 mm or less Select converging drain pipes whose diameter is suitable for the operating capacity of the unit 5 2 Indoor unit 06 75 5 ...

Страница 598: ...in to prevent condensation Secure the drain pipe to the wall with a saddle Pipe Saddle Wall Outside wall cap Sealer putty Outdoors Seal the hole around drain pipe with caulk Silicone sealant Heat insulation adhesive tape Be sure to coat the entire and surface Is there is a gap it could cause condensation 5 2 Indoor unit 06 76 5 Drain connection SYSTEM DESIGN SYSTEM DESIGN ...

Страница 599: ...7 FUNCTION SETTINGS 2019 11 01 DV_CH07_J3LU061EF_02 ...

Страница 600: ...Indoor unit setting by UTY RNRUZ 07 93 2 9 Function details 07 96 2 10 Wired remote controller UTY RNKU 07 101 2 11 Simple remote controller UTY RSKU UTY RHKU 07 103 2 12 Touch panel controller 07 105 2 13 Central remote controller UTY DCGY 07 106 2 14 Central remote controller UTY DCGYZ1 07 107 2 15 Wired remote controller Touch panel 07 109 2 16 Simple remote controller UTY RSRY UTY RHRY 07 113 ...

Страница 601: ... For proper operation of the air conditioner perform the setting as described in the instruction RELATED LINKS System type setting on page 07 2 Address setting on page 07 3 Manual address setting method on page 07 8 Address setting by remote controller on page 07 15 Automatic address setting on page 07 49 Terminal resistor setting on page 07 56 Indoor unit connection check on page 07 57 07 1 1 Sys...

Страница 602: ...ck For details refer to Indoor unit connection check on page 07 57 Step 4 Function setting Indoor unit setting For the actual switch positions refer to Function settings on page 07 59 Step 1 Refrigerant circuit address setting Set the rotary switch REF AD x10 and x1 For details refer to Address setting on page 07 3 Step 2 Terminal resistor setting Set the rotary switch IU AD x10 and x1 For details...

Страница 603: ...System design in Chapter 6 SYSTEM DESIGN on page 06 1 to confirm the details of each unit and perform the set ting Outdoor unit addresses and setting ranges Setting Setting range Type of switch Remarks A Refrigerant circuit address 00 99 Setting example 01 REF AD x10 REF AD x1 Arbitrary numbers can be set in range of 00 99 Terminal resistor ON OFF SET5 DIP switch SET5 4 Refer to Terminal resistor ...

Страница 604: ...page 07 52 E Indoor unit address 00 63 Manual address setting Arbitrary numbers can be set in range of 00 63 Setting example 12 IU AD x10 IU AD x1 Wireless R C This switch is set to 00 at factory setting Refer to Address setting by wireless remote controller on page 07 15 Wired R C 3 wire type This switch is set to 00 at factory setting Refer to Address setting by wired remote controller UTY RNKU ...

Страница 605: ...ller convertor address 00 15 1 Modbus convertor for VRF on page 07 121 Modbus convertor for VRF on page 07 121 Network convertor for LonWorks M Network convertor for LonWorks on page 07 124 Central remote controller N Central remote controller UTY DCGY on page 07 106 Central remote controller UTY DCGYZ1 on page 07 107 Wired remote controller 2 wire type F Remote controller address 1 32 2 Manual ad...

Страница 606: ...etF SetD SetE SetF SetD SetE SetF SetD SetE SetF SetD SetE SetF SetD SetE SetF SetD SetE SetF SetD SetE SetF SetD SetE SetF SetD SetE SetF SetD SetE SetF SetD SetE SetF SetD SetE SetF SetD SetE SetF 00 SetN SW2 of DIP Switch1 ON OFF SetJ SW2 of DIP Switch1 ON OFF SetJ 00 SetG 1 SetK Signal amplifier Max 8 Master Master Master 00 R C line 2 wire R C line 2 wire 18 01 18 02 18 03 18 04 18 05 18 1 2 ...

Страница 607: ...e range of 0 to 99 The indoor unit address can be set to arbitrary numbers in the range of 0 to 63 In case of 3 wire type of remote controller set the remote controller address in the order of 0 1 2 15 Blank is not allowed In the automatic address setting of 2 wire type remote controller the remote controller ad dress is set to 0 automatically In the manual address setting of 2 wire type remote co...

Страница 608: ... 01 02 01 01 01 0 1 2 02 02 02 0 1 2 00 01 02 25 25 25 0 1 2 01 02 25 Refrigerant system 1 Refrigerant system 2 Refrigerant system 25 Setting example Outdoor unit Set A Indoor unit Set D Refrigerant circuit address Rotary switch setting Rotary switch setting REF AD x10 REF AD x1 REF AD x10 REF AD x1 01 0 1 0 1 11 1 1 1 1 25 2 5 2 5 50 5 0 5 0 Setting range 00 99 Arbitrary numbers can be set Same a...

Страница 609: ...0 00 00 0 1 0 00 Indoor unit address Rotary switch setting IU AD x10 IU AD x1 03 0 3 11 1 1 30 3 0 47 4 7 Setting range 00 63 Arbitrary numbers can be set Do not set indoor unit address to the range of 64 99 Do not set the same address number to 2 or more indoor units 1 3 Manual address setting method 07 9 1 System settings FUNCTION SETTINGS FUNCTION SETTINGS ...

Страница 610: ...ire type R C 2 2 00 Remote controller address Rotary switch Switch position RC AD 0 0 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 A 11 B 12 C 13 D 14 E 15 F 1 Set the remote controller address in order of 0 1 2 15 Blank is now allowed 2 When remote controller group is not constructed 1 1 connection of indoor unit and re mote controller be sure that the remote controller address is set to the initial se...

Страница 611: ...RB AD 1 Rotary switch Touch panel controller setting Set G Before performing the initial setting set the Touch panel controller address first For details refer to the setting manual 00 01 02 03 Touch panel controller Max 16 2 The sum total of the Touch panel controller Central remote controller Network convertor for Group remote controller Modbus convertor and Network convertor for LonWorks is a m...

Страница 612: ...ess of Network convertor for single split air conditioner outdoor unit and the indoor unit is a maximum of 100 Dual remote control switch Set J According to the number of connecting wired remote controller s turn ON or OFF the switch 2 of DIP switch 1 on the slave remote controller 2 wired remote controllers are connected in a remote control group Only 1 wired remote controller is connected in a r...

Страница 613: ...in one VRF network system is prohib ited 15 Network convertor for LONWORKS The sum total of the Touch panel controller Central remote controller Network convertor for Group remote controller Modbus convertor and Network convertor for LonWorks is a maxi mum of 16 1 3 Manual address setting method 07 13 1 System settings FUNCTION SETTINGS FUNCTION SETTINGS ...

Страница 614: ...mote controller Max 16 1 Setting up more than one Network convertor in one VRF network system is prohibited 2 The sum total of the Touch panel controller Central remote controller Network convertor for Group remote controller Modbus convertor and Network convertor for LonWorks is a max imum of 16 1 3 Manual address setting method 07 14 1 System settings FUNCTION SETTINGS FUNCTION SETTINGS ...

Страница 615: ... required set by the rotary switch on the indoor unit PCB Preparation 1 This step is unnecessary for newly installed and not yet set the switch Set the rotary switch on the indoor unit PCB for manual address setting Initially set to 00 as factory setting The layout of the switches differs by the type of the indoor unit For the details refer to Setting on indoor unit PCB on page 07 67 Rotary switch...

Страница 616: ...ss valid range 00 to 99 Switches between the setting number bottom line and function number top line Increases and decreases the displayed number Starts the address setting mode Changes the address indicator digits Transmits address setting Used to reconfirm the address setting Used to confirm the address setting Indication of address code Indication of address data number the right digit Indicati...

Страница 617: ...onds 3 short beeps MANUAL AUTO MANUAL AUTO IR receiver unit 2 While holding down the FAN and the SET TEMP buttons press the RESET button The function setting mode will be activated SET TEMP RESET FAN Function setting mode display Selection and confirmation of custom code 1 In function setting mode display press the SET TEMP or button to select the custom code that matches the setting with the indo...

Страница 618: ...stom code press the TIMER MODE button to send the code to the indoor unit 2 short beeps Correct code Wrong code No response 1 4 Address setting by remote controller 07 18 1 System settings FUNCTION SETTINGS FUNCTION SETTINGS ...

Страница 619: ...umber Set at 01 3 Press the FAN button to enter the address data setting mode The address data will flash when this button is pressed Address data 4 Press the SET TEMP or button to adjust the address data The indoor unit address range is between 00 and 63 Each time the MODE button is pressed it switches between the left digit and the right digit Change digit Range 00 to 63 Up Down 1 4 Address sett...

Страница 620: ...er as follows OPERATION Green TIMER Orange Lit continuously Flashes times of address numbers the left digit FILTER Red Flashes times of address numbers the right digit Example ADDRESS 34 OPERATION lamp Green TIMER lamp Orange FILTER lamp Red 0 5 sec ON 0 5 sec OFF 4 times 3 times 1 to 10 sec 1 to 10 sec 0 5sec ON 0 5sec OFF When the address setting is 0 TIMER lamp and FILTER lamp will not flash Co...

Страница 621: ...tton to adjust function number 02 Set at 02 3 Press the FAN button to enter the address data setting mode The address data will flash when this button is pressed Address data 4 Press the SET TEMP or button to adjust the address data The refrigerant circuit address range is between 00 and 99 Each time the MODE button is pressed it switches between the left digit and the right digit Change digit Ran...

Страница 622: ...ec OFF Flashes times of address numbers the left digit FILTER Red Flashes times of address numbers the right digit Example ADDRESS 25 OPERATION lamp Green TIMER lamp Orange FILTER lamp Red 5 times 0 5sec ON 0 5sec OFF 1sec ON 1sec OFF 2 times 1 10 sec 1 10 sec 0 5sec ON 0 5sec OFF When the address setting is 0 TIMER lamp and FILTER lamp will not flash Address indication will be switched automatica...

Страница 623: ... of each LED lamp is darkening though the content of the display does not change 3 short beeps MANUAL AUTO MANUAL AUTO IR receiver unit 2 Press the RESET button RESET For the custom code setting of b c or d perform the setting after pressing the RESET button After completing the procedure above no address setting signal is received If the address setting signal is sent 5 short beeps will be emitte...

Страница 624: ...FILTER lamp Red 0 5 sec ON 0 5 sec OFF 4 times 3 times 1 to 10 sec 1 to 10 sec 0 5sec ON 0 5sec OFF TIMER set Refrigerant circuit address setting 1 Make sure that the function number is set to 01 with referring the step 2 in Refrigerant circuit address setting on page 07 21 2 Press the TIMER set button Associating indication will be shown on the indoor unit LED lamps Example ADDRESS 25 OPERATION l...

Страница 625: ...t performed address cannot be read correctly After all the addresses have been set the circuit breaker needs to be switched off for at least 2 minutes After the 2 minutes has passed power can be restored The set address is stored in the PCB and will remain in memory even when the power of in door unit is turned off However setting address is effective after disconnecting the power supply and then ...

Страница 626: ...door unit are set at 0 facto ry setting The layout of the switches differs by the type of the indoor unit For the details refer to Setting on indoor unit PCB on page 07 67 Rotary switch type A SW601 SW602 SW604 SW605 SW606 SW607 SW608 Check the switch position is set at 0 Factory setting IU AD x10 IU AD x1 REF AD x10 REF AD x1 2 If multiple indoor units are connected to a single wired remote contr...

Страница 627: ...it address 02 Refrigerant circuit address Remote controller address Remote controller address setting number 00 to 15 SET BACK button Switches the remote controller address setting number SET TIME and button Switches the function number Setting number Indoor unit address valid range 00 to 63 Refrigerant circuit address valid range 00 to 99 SET TEMP V and Λ button Switches the setting number TIMER ...

Страница 628: ...MP button The setting range is from 00 to 63 Example When indoor unit address data 12 is set up Indoor unit address data 4 Confirm the selected indoor unit address data by pressing the TIMER SET button The data will be transferred to the indoor unit ERROR GOOD When the address data is properly set up on the indoor unit the flashing of the number stops and the set number will be displayed GOOD When...

Страница 629: ...cuit address by pressing the SET TEMP or the SET TEMP button The setting range is from 00 to 99 Refrigerant circuit address data Example When refrigerant circuit address data 18 is set up 4 Confirm the selected refrigerant circuit address data by pressing the TIMER SET button The data will be transferred to the indoor unit GOOD ERROR When the address data is properly set up on the indoor unit the ...

Страница 630: ...g mode on page 07 30 00 01 01 01 02 01 13 01 14 01 15 01 0 1 2 0 1 0 Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Wired remote controller Wired remote controller Wired remote controller Resetting the power after setting up all indoor units NOTES If the reset is not performed function cannot be read correctly After all the functions have been set the circuit breaker needs...

Страница 631: ...r unit are set at 0 facto ry setting The layout of the switches differs by the type of the indoor unit For the details refer to Setting on indoor unit PCB on page 07 67 Rotary switch type A SW601 SW602 SW604 SW605 SW606 SW607 SW608 Check the switch position is set at 0 Factory setting IU AD x10 IU AD x1 REF AD x10 REF AD x1 2 If multiple indoor units are connected to a single wired remote controll...

Страница 632: ...TEMP button to select F1 Menu 2 F1 settings mode or F2 Menu 2 F2 settings mode F1 Initial settings mode F2 Maintenance settings mode 4 While displaying the settings mode selection screen press START STOP button Setting item selection screen with item number will be displayed Item number Setting mode selection screen Setting item selection screen 5 While displaying the setting item selection screen...

Страница 633: ...his setting on the master remote controller 1 While displaying the function setting screen press the TEMP or TEMP button to se lect the 2 wire remote controller address Function setting screen Example Selecting the 2 wire remote controller address 002 01 2 Press the START STOP button to switch to the function number setting Example Selecting the 2 wire remote controller address Function number 3 P...

Страница 634: ...the address data is properly set up on the indoor unit the set number will be dis played GOOD When the address data is not set up correctly is displayed ERROR Back to the previ ous step and set up the indoor unit address data again 7 To return to the 2 wire remote controller address selection screen press the START STOP button If setting has been completed press FAN button to return to the Menu 2 ...

Страница 635: ...ber setting Example Selecting the 2 wire remote controller address Function number 3 Press the TEMP or TEMP button to adjust the function number Function number Function number 4 Press the START STOP button to switch to the refrigerant circuit address setting Refrigerant circuit address Function number 5 Press the TEMP or TEMP button to adjust the refrigerant circuit address number Example Selecti...

Страница 636: ...remote controller address selection screen press the START STOP button If setting has been completed press FAN button to return to the Menu 2 F1 item selection screen When returning to the 2 wire remote controller address selection screen Setting completed and returning to the Menu 2 F1 item selection screen Completion of setting mode 1 To exit the setting mode and return to the Menu 1 item select...

Страница 637: ...all indoor units NOTES If the reset is not performed function cannot be read correctly After all the functions have been set the circuit breaker needs to be switched off for at least 2 minutes After the 2 minutes has passed power can be restored The set function is stored in the PCB and will remain in memory even when the power of in door unit is turned off However setting function is effective af...

Страница 638: ...ting The layout of the switches differs by the type of the indoor unit For the details refer to Setting on indoor unit PCB on page 07 67 Rotary switch type A SW601 SW602 SW604 SW605 SW606 SW607 SW608 Check the switch position is set at 0 Factory setting IU AD x10 IU AD x1 REF AD x10 REF AD x1 2 If multiple indoor units are connected to a single simple remote controller set up the remote controller...

Страница 639: ...s address setting SET TEMP p and q button Switches the various numbers UTY RSK With operation mode UTY RHK Without operation mode 01 Indoor unit address 02 Refrigerant circuit address Remote controller address setting number 00 to 15 Indoor unit address valid range 00 to 63 Refrigerant circuit address valid range 00 to 99 Function number Remote controller address FAN button Each time this button i...

Страница 640: ...FAN button Function number indicator flashes Function number 3 Display the function number 01 by pressing SET TEMP button or SET TEMP but ton Function number 4 Press the FAN button Setting number indicator flashes Indoor unit address data 5 Set up the indoor unit address data by pressing SET TEMP button or SET TEMP button Setting range is from 00 to 63 Example When indoor unit address data 12 is s...

Страница 641: ...te controller 1 In initial display of the address setting mode by pressing SET TEMP button or SET TEMP button select a remote controller address Select the indoor unit you want to oper ate If the indoor unit you want to operate has already been selected skip this step Initial display of address setting mode Example When remote controller address 01 is selected Remote controller address 2 Press the...

Страница 642: ...data 6 Confirm the selected refrigerant circuit address data by pressing the START STOP button The data will be transferred to the indoor unit GOOD ERROR When the address data is properly set up on the indoor unit the set number will be dis played GOOD When the address data is not set up correctly is displayed ERROR Back to the previ ous step and set up the indoor unit address data again 1 4 Addre...

Страница 643: ...page 07 41 Simple remote controller Simple remote controller Simple remote controller 00 01 01 01 02 01 13 01 14 01 15 01 0 1 2 0 1 0 Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Resetting the power after setting up all indoor units NOTES If the reset is not performed function cannot be read correctly After all the functions have been set the circuit breaker needs to be ...

Страница 644: ...ches differs by the type of the indoor unit For the details refer to Setting on indoor unit PCB on page 07 67 Rotary switch type A SW601 SW602 SW604 SW605 SW606 SW607 SW608 Check the switch position is set at 0 Factory setting IU AD x10 IU AD x1 REF AD x10 REF AD x1 2 If multiple indoor units are connected to a single wired remote controller set up the remote con troller address with Automatic add...

Страница 645: ...n Setting screen 002 01 00 00 Address Function No Setting No Function Setting Back Setting 2 Address screen is displayed Select the address of the indoor unit whose function number is to be set by touching or 002 01 Address Cancel OK All When OK is touched the display returns to the Function Setting screen 3 Touch Function No on the Function Setting screen 002 01 00 00 Address Function No Setting ...

Страница 646: ... 7 Touch Yes on the verification screen No Yes Function Settung Function setting will be performed OK Refrigerant circuit address setting 1 Touch Address on the Function Setting screen 002 01 00 00 Address Function No Setting No Function Setting Back Setting 2 Address screen is displayed Select the address of the indoor unit whose function number is to be set by touching or When setting at all the...

Страница 647: ... No by touching or Set ting range is from 00 to 99 Example When refrigerant circuit address data 18 is set 18 002 01 02 Function Setting Cancel OK Address Function No Setting No When OK is touched the Function Setting verification screen is displayed 7 Touch Yes on the verification screen No Yes Function Settung Function setting will be performed OK After the Setting screen was displayed the displ...

Страница 648: ...Resetting the power after setting up all indoor units NOTES If the reset is not performed function cannot be read correctly After all the functions have been set the circuit breaker needs to be switched off for at least 2 minutes After the 2 minutes has passed power can be restored The set function is stored in the PCB and will remain in memory even when the power of in door unit is turned off How...

Страница 649: ...ponents location Components related to automatic address setting are located on the outdoor unit PCB Set the functions of an outdoor unit with the push buttons SW107 SW108 and SW109 while ob serving the 7 segment LED lamps LED105 and LED104 on the PCB LED101 GREEN SW107 SW108 SW109 SW106 SW105 SW110 POWER MODE MODE EXIT LED105 LED104 REF AD SET1 SET2 SET3 SET4 LED102 RED ERROR SELECT ENTER X 10 X ...

Страница 650: ...setting procedure Automatic address setting of signal amplifier CAUTION This function can be used for a maximum of 8 signal amplifiers installed within a same refriger ant system Perform this setting on only 1 outdoor unit master unit within the same network No duplicate setting of this function from other outdoor unit is allowed When setting the address of a signal amplifier automatically be sure...

Страница 651: ...LED105 LED104 LED105 LED104 6 When the automatic address setting is completed the number of signal amplifier is displayed on the LED104 Verify that the count matches the number of signal amplifiers being installed LED105 LED104 LED105 LED104 Example When 8 signal amplifiers are being connected 7 To exit the automatic address setting press the ENTER button SW109 in the setting complet ed status sho...

Страница 652: ...r verifying that the system is operating normally press the MODE EXIT button SW107 once LED105 LED104 LED105 LED104 2 Press the SELECT button SW108 to display F3 on LED104 1 Do not set F1 and F9 usually since they are used for maintenance The display of the LED104 changes each time the SELECT button is pressed LED105 LED104 LED105 LED104 LED105 LED104 LED105 LED104 1 1 Monitoring mode Setting mode...

Страница 653: ...tomatic setting of the addresses of three indoor units failed LED105 LED104 LED105 LED104 LED105 The number of indoor units of which automatic address setting succeeded LED104 The number of indoor units of which automatic address setting failed If automatic address setting failed make sure that all of the rotary switches SW6 to SW9 on the PCBs of the failed indoor units are positioned at 0 and tha...

Страница 654: ...efrigerant circuit address No Master unit Master unit Master unit Signal amplifier 1 Activate the automatic address setting function of signal amplifier on the master unit of Refrig erant system 1 1 An address is automatically assigned to all signal amplifiers on the network Because an address is also assigned to the signal amplifiers being connected in Refrigerant system 2 and3 its is not necessa...

Страница 655: ...hen indoor units are being connected via different refrigerant systems never activate the au tomatic address setting function of indoor unit As long as master units are on the same network any master unit can set the addresses of sig nal amplifiers automatically Perform this setting on only 1 outdoor unit master unit within the same network No duplicate setting of this function from other outdoor ...

Страница 656: ...take note of the following conditions How many network segments are there in a VRF system Where will you set the terminal resistors in a network segment Condition for 1 segment Total number of outdoor units indoor units and signal amplifiers is less than 64 or the total length of the transmission line is less than 500 m How many outdoor units are connected in 1 refrigerant system Based on the cond...

Страница 657: ...When 12 is displayed on the LED105 hold down the ENTER button SW109 for 3 seconds or longer Unless it is held down for at least 3 seconds the selection will not be confirmed When the indoor unit connection check function is activated the display changes to run LED105 LED104 LED105 LED104 When the function is not activated during maintenance the display changes to FAIL LED105 LED104 LED105 LED104 6...

Страница 658: ...T button SW108 Number of indoor unit connection is error LED105 LED104 LED105 LED104 Volume ratio of the indoor units connection is error LED105 LED104 LED105 LED104 Overlap address of the indoor unit is error LED105 LED104 LED105 LED104 To display the address of the overlap indoor unit hold down the ENTER button SW109 Example Displaying overlap address to indoor unit address 3 LED105 LED104 LED10...

Страница 659: ...Y RNKU on page 07 101 Simple remote controller UTY RSKU UTY RHKU on page 07 103 Touch panel controller on page 07 105 Central remote controller UTY DCGY on page 07 106 Central remote controller UTY DCGYZ1 on page 07 107 Wired remote controller Touch panel on page 07 109 Simple remote controller UTY RSRY UTY RHRY on page 07 113 Network convertor UTY VTGX on page 07 115 Network convertor UTY VGGXZ1 ...

Страница 660: ...tion of the outdoor unit has stopped if it is still running stop the oper ation and turn off the power 2 Remove the front panel of the outdoor unit 3 Remove the lid of the electrical component box to expose the PCB 4 Turn on the power of the outdoor unit When the system is operated normally the indicator lamps may light as in following figure LED101 GREEN POWER MODE LED105 LED104 LED102 RED ERROR ...

Страница 661: ...e mode you want to set on the LED105 LED105 LED104 LED105 LED104 Example To select switching between Forced stop and Emergency stop Then press the ENTER button SW109 to confirm the mode you want to set Flashing of LED105 stops and lights a number and the lit number on the LED104 starts to flash LED105 LED104 LED105 LED104 5 Again with referring to Setting list on page 07 63 press the SELECT button...

Страница 662: ...ous step 5 seconds after even if the ENTER button SW109 is not pressed the LED105 starts to flash automatically LED105 LED104 LED105 LED104 Then press the MODE EXIT button SW107 to exit the function setting mode LED105 LED104 LED105 LED104 2 1 Setting on outdoor unit PCB 07 62 2 Function settings FUNCTION SETTINGS FUNCTION SETTINGS ...

Страница 663: ...power mode 2 1 3 Prohibited 0 0 Prohibited Setting prohibited 0 1 Prohibited 1 4 Prohibited 0 0 Prohibited Setting prohibited 0 1 Prohibited 0 2 Prohibited 0 3 Prohibited 2 0 Switching between batch stop or emergency stop 0 0 Batch stop This mode selects the pattern of the stop function to be operated by the external input terminal CN134 Batch stop The stop of all indoor units connected to same re...

Страница 664: ... 3 Prohibited 2 5 Prohibited 0 0 Prohibited Setting prohibited 0 1 Prohibited 0 2 Prohibited 0 3 Prohibited 2 6 Prohibited 0 0 Prohibited Setting prohibited 0 1 Prohibited 2 7 Prohibited 0 0 Prohibited Setting prohibited 0 1 Prohibited 2 8 Change of unit Temperature 0 0 Celsius C 0 1 Fahrenheit F 2 9 Change of unit Pressure 0 0 MPa 0 1 psi 3 0 Outdoor unit capacity save setting 0 0 Level 1 Stop Th...

Страница 665: ... 1 3 57 2 F 14 C 1 4 60 8 F 16 C 1 5 64 4 F 18 C 4 0 Capacity priority setting in low noise mode 0 0 Off Quiet priority If the cooling heating performance becomes insufficient when the low noise mode is set it is possible to set Capacity priority that automatically cancels the low noise mode Once performance is restored the mode will automatically return to the low noise mode 0 1 On Capacity prior...

Страница 666: ...d to CN135 0 1 Setting number 01xx 9 8 Setting number 98xx 9 9 Setting number 99xx 9 0 Prohibited 0 0 Prohibited Setting prohibited 0 1 Prohibited 0 2 Prohibited 0 3 Prohibited 0 4 Prohibited 0 5 Prohibited 0 6 Prohibited 0 7 Prohibited 0 8 Prohibited 0 9 Prohibited 1 0 Prohibited 1 1 Prohibited 1 When electricity meter number is set to 000 and 201 to 299 the pulses input to CN135 be come ineffect...

Страница 667: ...ium static pressure duct High static pressure duct Floor ceiling Ceiling Type 2 Wall mounted ASUB18 24 Type 3 Wall mounted ASUA7 9 12 14TLAV Type 4 Circular flow cassette Type 5 Wall mounted ASUA4 7 9 12 14TLAV1 Type 6 Wall mounted ASUB30 36 Type 7 Compact floor Type 1 SET1 SET2 DIP switch Type A SW1 Main PCB DIP switch Type B Rotary switch Type C Rotary switch Type D DIP switch Type A SW601 SW602...

Страница 668: ...W602 SW604 SW605 SW606 SW607 SW608 SW PCB SET1 SET2 DIP switch Type A SW1 Main PCB DIP switch Type B Type 3 Rotary switch type C DIP switch type A Main PCB SET1 SET2 DIP switch type A 2 2 Setting on indoor unit PCB 07 68 2 Function settings FUNCTION SETTINGS FUNCTION SETTINGS ...

Страница 669: ...A Rotary switch Type C Type 5 Rotary switch Type C DIP switch Type A SET2 SET1 DIP switch Type A Type 6 Rotary switch Type C SET2 SET1 DIP switch Type A DIP switch Type A 2 2 Setting on indoor unit PCB 07 69 2 Function settings FUNCTION SETTINGS FUNCTION SETTINGS ...

Страница 670: ...m code switch 1 2 Wireless remote controller custom code switch 2 3 Prohibited 4 Prohibited SET3 1 Drainage function switch Mini duct type and Slim duct type only 2 Auto louver grille setting switch Mini duct type and Slim duct type only 3 Prohibited 4 Prohibited Type B 2WIRE 3WIRE SW1 Remote controller wire type switch Rotary switch Type C IU AD x1 Indoor unit address switch 1 IU AD x10 Indoor un...

Страница 671: ... wireless remote controller This DIP switch sets the custom code of the wireless remote controller of an indoor unit If multiple indoor units are being installed in the same room switch the custom codes of the corre sponding wireless remote controllers in order to prevent their signals from being mixed When switching the custom code of the wireless remote controller of an indoor unit be sure to al...

Страница 672: ...nage SET4 2 Switching of Auto louver grille setting for Mini duct type and Slim Duct type only When Auto louver grille kit optional parts is attached this switch should be set On Enabled SET4 2 Auto louver grille setting Factory setting Off Disabled On Enabled SET4 3 Setting prohibited SET4 3 Factory setting Off Fixed On Setting prohibited SET4 4 Setting prohibited SET4 4 Factory setting Off Fixed...

Страница 673: ...digit 0 RC AD Remote controller address Switching of Remote controller address When the indoor unit is wired by remote controller group to identity the indoor unit in the remote controller group the number remote controller address in the remote controller group is set 3 wire type only for manual address setting Set the remote controller address in order of 0 1 2 3 15 Blank is not allowed Rotary s...

Страница 674: ...ch Displays the target item of the local function setting No name d Unit list Displays a list of addresses Refrigerant no Unit no of the target unit selected in a and b In addition multiple units can be handled simultaneously by arbitrary selection background blue color for target unit selection This list displays the following information in addition to address Read value Displays the value of th...

Страница 675: ...cted in d Thereafter the setting contents result is displayed at the read value field of d for check use After the setting is completed subsequent processing can be canceled by clicking the button again h Progress bar Displays the processing progress of f or g i Close button Closes this screen Remote Setting screen However when read write processing for unit was performed confirmation dialog box o...

Страница 676: ...y After the function is performed the result is displayed d Refrigerant system address selection Specifies the refrigerant system address which the outdoor unit to be operated remotely belongs to e Outdoor unit selection Specifies the outdoor unit to be operated remotely f Result for the function applied to one outdoor unit After the function is performed the result is displayed g Start button Per...

Страница 677: ...s operating the function may not be changed When the remote perform function and the function by the push button on the PCB of the outdoor unit are performed at the same time the remote perform function will not be operat ed Check that the push button is not used before starting the remote perform function 2 3 Setting by service tool UTY ASGXZ1 07 77 2 Function settings FUNCTION SETTINGS FUNCTION ...

Страница 678: ...ir tight test and vacuuming have been performed firmly There is no wiring mistake 2 Turn on the power of indoor units By turning on the power the indoor units initialize EEV Indoor units Indoor units Breaker ON Before proceeding the function setting refer to the following sections and perform necessary steps Button name and function on page 07 16 Entering function setting mode on page 07 17 Select...

Страница 679: ...by pressing the START STOP button once A beeping sound 2 short beeps 1 long beep 2 short beeps and 1 long beep will be emitted if the command is accept ed Beeps are emitted intermittently 2 short beeps 1 long beep 2 short beeps and 1 long beep In the following case the setting signal will not be accepted correctly and 5 short beeps will be emitted The function setting number is set out of range 2 ...

Страница 680: ... Flashes times of function numbers the left digit Flashes times of function numbers the right digit FILTER Red Flashes times of setting numbers the right digit Example Function number 26 Setting number 31 OPERATION lamp Green TIMER lamp Orange FILTER lamp Red 0 5 sec ON 0 5 sec OFF 0 5 sec ON 0 5 sec OFF OFF OFF 1 time 3 times 2 times 6 times Phase1 12 sec Phase2 12 sec 0 5 sec ON 0 5 sec OFF 0 5 ...

Страница 681: ...AL AUTO IR receiver unit 2 Press the RESET button RESET For the custom code setting of b c or d perform the setting after pressing the RESET button After completing the procedure above no function setting signal is received If the function setting signal is sent 5 short beeps will be emitted indicating an error When returning the function setting mode again press the MANUAL AUTO button for 3 sec o...

Страница 682: ...er 26 Setting number 31 0 5sec ON 0 5sec OFF 0 5sec ON 0 5sec OFF OFF OFF 1 time 3 times 2 times 6 times Phase1 12sec Phase2 12sec 0 5sec ON 0 5sec OFF 0 5sec ON 0 5sec OFF Example Function number 30 Setting number 01 OPERATION lamp Green TIMER lamp Orange FILTER lamp Red OPERATION lamp Green TIMER lamp Orange FILTER lamp Red 0 5sec ON 0 5sec OFF OFF 1 time 1 time 3 times 3 times Phase1 12sec Phas...

Страница 683: ...tched off for at least 2 minutes After the 2 minutes has passed power can be restored The set function is stored in the PCB and will remain in memory even when the power of in door unit is turned off However setting function is effective after disconnecting the power supply and then recon necting it Record the latest configuration of the indoor unit function setting on a label and put the label on...

Страница 684: ...ge 07 8 0 1 2 3 Indoor unit Indoor unit Indoor unit Indoor unit RC AD RC AD RC AD RC AD Wired remote controller Example When 4 indoor units are connected 2 Before turning on the power of indoor unit reconfirm following items Piping air tight test and vacuuming have been performed firmly There is no wiring mistake 3 Turn on the power of indoor units By turning on the power the indoor units initiali...

Страница 685: ...the TIMER SET button The data will be transferred to the in door unit ERROR GOOD When the address data is properly set up on the indoor unit the flashing of the number stops and the set number will be displayed GOOD When the address data is not set up correctly is displayed ERROR Back to the previ ous step and set up the indoor unit address data again RELATED LINKS Completion of setting mode on pa...

Страница 686: ... is not performed function cannot be read correctly After all the functions have been set the circuit breaker needs to be switched off for at least 2 minutes After the 2 minutes has passed power can be restored The set function is stored in the PCB and will remain in memory even when the power of in door unit is turned off However setting function is effective after disconnecting the power supply ...

Страница 687: ...umbers and setting numbers refer to the indoor unit installation manu al Preparation 1 If multiple indoor units are connected to a single wired remote controller set up the remote con troller address with Automatic address setting 0 0 0 0 Indoor unit Indoor unit Indoor unit Indoor unit RC AD RC AD RC AD RC AD Simple remote controller Example When 4 indoor units are connected 2 Before turning on th...

Страница 688: ...setting Example Selecting the 2 wire remote controller address Function number 3 Press the TEMP or TEMP button to adjust the function number Function number 4 Press the START STOP button to switch to the setting number adjustment Function number Setting number 5 Press the TEMP or TEMP button to adjust the setting number Setting number 6 Press the START STOP button The data will be transferred to t...

Страница 689: ...Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Simple remote controller Simple remote controller Simple remote controller Resetting the power after setting up all indoor units NOTES If the reset is not performed function cannot be read correctly After all the functions have been set the circuit breaker needs to be switched off for at least 2 minutes After the 2 minutes has passed powe...

Страница 690: ...ler set up the remote controller address RC AD manually on the indoor units PCBs by referring Manual address setting method on page 07 8 0 1 2 3 Indoor unit Indoor unit Indoor unit Indoor unit RC AD RC AD RC AD RC AD Simple remote controller Example When 4 indoor units are connected 2 Before turning on the power of indoor unit reconfirm following items Piping air tight test and vacuuming have been...

Страница 691: ... controller address 2 Press the FAN button Function number indicator flashes Function number 3 Set up the function number by pressing SET TEMP button or SET TEMP button Function number 4 Press the FAN button Setting number indicator flashes Setting number 5 Set up the setting number by pressing SET TEMP button or SET TEMP button Setting number Example Function number 30 Setting number 01 2 7 Indoo...

Страница 692: ... 02 01 13 01 14 01 15 01 0 1 2 0 1 0 Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Resetting the power after setting up all indoor units NOTES If the reset is not performed function cannot be read correctly After all the functions have been set the circuit breaker needs to be switched off for at least 2 minutes After the 2 minutes has passed power can be restored The set ...

Страница 693: ...Automatic address setting 0 0 0 0 Indoor unit Indoor unit Indoor unit Indoor unit RC AD RC AD RC AD RC AD Wired remote controller Touch panel Example When 4 indoor units are connected 2 Before turning on the power of indoor unit reconfirm following items Piping air tight test and vacuuming have been performed firmly There is no wiring mistake 3 Turn on the power of indoor units By turning on the p...

Страница 694: ...ncel OK When OK is touched the display returns to the Function Setting screen 5 Touch Setting on the Function Setting screen 002 01 30 00 Address Function No Setting No Function Setting Back Setting 1 1 When All is selected in step 2 and different Setting No is set from 2 or more indoor units is displayed here 6 Setting screen of Setting No is displayed Set the Setting No by touching or Example Fu...

Страница 695: ...ontroller Touch panel Wired remote controller Touch panel Wired remote controller Touch panel 00 01 01 01 02 01 13 01 14 01 15 01 0 0 0 0 0 0 Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Resetting the power after setting up all indoor units NOTES If the reset is not performed function cannot be read correctly After all the functions have been set the circuit breaker need...

Страница 696: ...together Cassette type only 01 Raise Horizontal swing airflow direction 24 00 Standard Adjusts the horizontal swing airflow direction For horizontal swing equipped models 01 Left half 02 Right half Static pressure 26 00 SP mode 00 Range of static pressure mode varies on the indoor unit models For details refer to Range of static pressure mode by model on page 07 100 As for the characteristics of e...

Страница 697: ...espond to the ventilation set to 01 01 Follow the setting on the remote controller External control 46 00 Start Stop Allows an external controller to start or stop the system or to perform an emergency stop or to perform a forced stop If an emergency stop is performed from an external controller same refrigerant system will be disabled If forced stop is set indoor unit stops by the input to the ex...

Страница 698: ...Mode 2 03 Mode 3 04 Mode 4 05 Mode 5 06 Mode 6 07 Mode 7 08 Mode 8 Control switching of external heaters 61 00 Auxiliary heater control 1 Sets the control method for external heater being used For details of the control method refer to External output in Chapter 8 EXTERNAL INPUT AND OUTPUT on page 08 5 Heater external heater Heat pump VRF outdoor unit 01 Auxiliary heater control 2 02 Heat pump pro...

Страница 699: ...e between cooling and heating settings deadband for dual setpoint auto mode function number 68 NOTE Deadband value will be usable provided that the corresponding operating device is connected 01 0 9 F 0 5 C 02 1 8 F 1 0 C 03 2 7 F 1 5 C 04 3 6 F 2 0 C 05 4 5 F 2 5 C 06 5 4 F 3 0 C 07 6 3 F 3 5 C 08 7 2 F 4 0 C 09 8 1 F 4 5 C Standby time for auxiliary equipment operation 71 00 Disabled Sets the st...

Страница 700: ... 99 External heater On External heater Off External heater On External heater Off Set value of function 62 00 t 5 4 F 3 C t 1 8 F 1 C t 0 9 F 0 5 C t 0 9 F 0 5 C 01 t 3 6 F 2 C t 1 8 F 1 C t 1 8 F 1 C t 0 9 F 0 5 C 02 t 3 6 F 2 C t 1 8 F 1 C t 3 6 F 2 C t 0 9 F 0 5 C 03 t 5 4 F 3 C t 1 8 F 1 C t 5 4 F 3 C t 0 9 F 0 5 C 04 t 7 2 F 4 C t 1 8 F 1 C t 7 2 F 4 C t 0 9 F 0 5 C 05 t 9 0 F 5 C t 1 8 F 1 C...

Страница 701: ...P Switch 1 ON ON OFF DIP switch 1 setting SW1 Setting prohibited SW1 Factory setting OFF Fixed at OFF ON Setting prohibited SW2 Dual remote controller setting Set the remote controller SW2 according to the following table Number of remote controller Primary unit Secondary unit Factory setting SW2 SW2 1 Normal OFF 2 Dual OFF ON 1 2 3 1 2 3 1 2 3 Indoor unit Remote controller cable When ground wire ...

Страница 702: ...hibited SW6 Memory backup setting Only for wired remote controller Set to ON to use batteries for the memory backup If there is a power failure when this setting is enabled all the settings stored in the memory will be saved SW6 Memory backup Factory setting OFF Disable ON Enable NOTE Never turn it ON in the case of simple remote controller 2 10 Wired remote controller UTY RNKU 07 102 2 Function s...

Страница 703: ...ory setting OFF Fixed at OFF ON Setting prohibited SW2 Dual remote controller setting Set the remote controller SW2 according to the following table Number of remote controller Primary unit Secondary unit Factory setting SW2 SW2 1 Normal OFF 2 Dual OFF ON 1 2 3 1 2 3 1 2 3 Indoor unit Remote controller cable When ground wire is necessary Master unit Slave unit Remote controller SW3 Fahrenheit F Ce...

Страница 704: ...ited SW5 Setting prohibited SW5 Factory setting OFF Fixed at OFF ON Setting prohibited SW6 Setting prohibited SW6 Factory setting OFF Fixed at OFF ON Setting prohibited 2 11 Simple remote controller UTY RSKU UTY RHKU 07 104 2 Function settings FUNCTION SETTINGS FUNCTION SETTINGS ...

Страница 705: ... set between 00 and 15 Up to 16 of this controller can be installed in 1 system When installing 2 or more controllers set up so that Address No does not overlap When installing multiple controllers in the same VRF network system avoid to overlap the Address No of following controllers Even the same type of controllers the Address No is not allowed to overlap Touch panel controller Central remote c...

Страница 706: ...f this controller can be installed in 1 system When installing 2 or more controllers set up so that Address No does not overlap When installing multiple controllers in the same VRF network system avoid to overlap the Address No of following controllers Even the same type of controllers the Address No is not allowed to overlap Touch panel controller Central remote controller Modbus convertor Networ...

Страница 707: ... case back side Set the DIP switch to ON Memory backup setting DIP switch Factory setting OFF Disabled ON Enabled Address setting 1 Tap Menu button 2 Tap Installer Setting 3 Tap Central controller Address Setting 2 14 Central remote controller UTY DCGYZ1 07 107 2 Function settings FUNCTION SETTINGS FUNCTION SETTINGS ...

Страница 708: ...ame VRF network system avoid to overlap the Address No of following controllers Even the same type of controllers the Address No is not allowed to overlap Touch panel controller Central remote controller Modbus convertor Network convertor for LONWORKS Network convertor for Group remote controller For details refer to the operating manual of the controller 2 14 Central remote controller UTY DCGYZ1 ...

Страница 709: ...he Maintenance screen NOTE The address of this unit is set automatically Do not change the indoor unit remote con troller address from the factory setting 0 Verify that the address is 0 Manual address setting of the remote controller 1 Touch Manual Addressing on the R C Address Setting screen 001 01 R C Address Setting Current Address Back Manual Addressing Address Reset 2 Manual Addressing screen...

Страница 710: ...o 32 but set it so that it does not duplicate the remote controller address of an indoor unit connected by the same remote controller cable Resetting the manual address setting number 1 Touch Address Reset on the R C Address Setting screen 001 05 R C Address Setting Current Address Back Manual Addressing Address Reset 2 A verification screen is displayed When the Yes is touched a message screen is...

Страница 711: ...Password and touch OK I U Address Verification screen is displayed Previous Page Back Next Page Page 2 3 Maintenance Test Run R C Address Setting Function Setting I U Address Setting 1 002 1 01 01 002 2 01 02 2 002 3 01 03 3 002 4 01 04 4 002 5 01 05 5 002 6 01 06 6 Page 1 2 I U Address Verification No System Unit Ref In Back Check Next Page 2 When the screen has multiple pages they can be switche...

Страница 712: ...erified is touched the appropriate indoor unit performs the air blow and the LED lamps blink Only when the indoor unit has that function 1 002 1 01 01 2 002 2 01 02 3 002 3 01 03 End Next Page Page 1 2 I U Address Verification No System Unit Ref In 6 When the End is touched the display returns to the I U Address Verification screen men tioned in step 2 1 002 1 01 01 2 002 2 01 02 3 002 3 01 03 End...

Страница 713: ... F1 item selection screen NOTE In the case of automatic address settings do not change the remote controller address for the indoor unit and keep it at the initial setting of 0 Addresses will be automatically set when initially starting up this unit Master or slave setting of remote controller 1 Select the 06 in Menu 2 F1 Settings Then press the button 2 Select the 0 Master or the 1 Slave with the...

Страница 714: ...ller Indoor unit address verification 1 Select the 10 in Menu 2 F2 Settings Then press the button 2 Display the smallest 2 wire remote controller address of indoor unit system number and unit number of the remote controller group This address displayed can be switched by the TEMP or TEMP button If an indoor unit other than VRF is connected is displayed Press the button to display the refrigerant s...

Страница 715: ...t 01 0 1 99 9 9 NOTES Setting range 00 to 99 Arbitrary numbers can be set When connecting the Network convertor for single split air conditioner set up the number so that the refrigerant circuit address number of the outdoor unit and indoor unit does not over lap The sum total of the refrigerant circuit address of Network convertor for single split air conditioner outdoor unit and the indoor unit ...

Страница 716: ...e indoor unit NOTE When 2 wire type remote controller is connected set to OFF for all models SET2 4 Factory setting ON Wireless remote controller model name AR RAK1E Model name Rear view 3 wire type wired remote controller model name AR WAG1E UTY RNNGU YYYYYYYY Model name Rear view OFF Other than the remote controller mentioned above SET3 Remote controller 2 wire 3 wire switching Set this setting ...

Страница 717: ...y numbers can be set The sum total of the Touch panel controller Central remote controller Network convertor for Group remote controller Modbus convertor and Network convertor for LonWorks is a maximum of 16 For Touch panel controller Central remote controller Network convertor for Group re mote controller Modbus convertor and Network convertor for LonWorks connected in same VRF network system set...

Страница 718: ...ng the Network convertor for single split air conditioner set up the number so that the refrigerant circuit address number of the outdoor unit and indoor unit does not overlap The sum total of the refrigerant circuit address of Network convertor for single split air conditioner outdoor unit and the indoor unit is a maximum of 100 2 18 Network convertor UTY VGGXZ1 07 118 2 Function settings FUNCTIO...

Страница 719: ...hile holding down SW4 the set button press and release SW7 the reset button to en ter the address setting mode The address setting mode is activated only if the set button is held down when SW7 re leased D19 3 Press SW4 the set button to display the current address The address is set to A1 at the factory D19 Example 1 When A1 is set Example 2 When A12 is set 2 19 Signal amplifier 07 119 2 Function...

Страница 720: ...iers be sure to select a different address for each am plifier If the same address is used for different signal amplifiers normal communication cannot be done 5 Press SW4 the set button to set the selected address Example Address no 5 is set D19 6 Turn the power off and on or press SW7 the reset button to exit the address setting mode and return to the normal mode If an address setting error occur...

Страница 721: ...6 or more the remote controller address of the convertor is 15 The sum total of the Touch panel controller Central remote controller Network convertor for Group remote controller Modbus convertor and Network convertor for LonWorks is a maxi mum of 16 For Touch panel controller Central remote controller Network convertor for Group remote controller Modbus convertor and Network convertor for LonWork...

Страница 722: ...SET4 SET5 Modbus slave address setting Setting range 1 247 Arbitrary numbers can be set For details refer to the installation manual SET6 1 Setting prohibited SET6 1 Factory setting OFF Fixed at OFF ON Setting prohibited SET6 2 Modbus communication stop bit setting SET6 2 Mod bus communication stop bit Factory setting OFF 1 bit ON 2 bit SET6 3 Modbus communication parity setting SET6 3 Mod bus com...

Страница 723: ...OFF Fixed at OFF ON Setting prohibited SET7 4 Terminal resistance setting Terminal resistance of Modbus communication can be set Terminal resistance 120 Ω In case of circuit terminal resistance set the terminal resistance to be enabled SET7 4 Terminal resistance Factory setting OFF Disable ON Enable 2 20 Modbus convertor for VRF 07 123 2 Function settings FUNCTION SETTINGS FUNCTION SETTINGS ...

Страница 724: ...utton to set special mode 2 Special mode 2 is the address setting mode 4 Press SW4 set button Current set address is displayed Example Address no 15 Factory setting 5 Press SW3 mode button to select the address The displayed address changes as fol lows each time the mode button is pressed A00 A15 A02 A01 Example Address no 3 is selected 6 Press SW4 set button to set the selected address Example Ad...

Страница 725: ...T1 LED2 LED3 LED4 GRN ORG RED BLU 3WIRE 2WIRE DIP switch setting SET1 2WIRE 3WIRE setting Remote controller 2WIRE 3WIRE switching SW Factory setting 2WIRE Set matched with the connection method of the remote controller cable to be connected 2 22 Thermostat convertor 07 125 2 Function settings FUNCTION SETTINGS FUNCTION SETTINGS ...

Страница 726: ... 70 21 Pattern 4 When SET3 1 is set to ON Two stage setting SET3 2 Cooling setting temperature SET3 2 Cooling setting temperature F C Remarks Factory setting Stage 1 Stage 2 OFF 68 20 64 18 Pattern 1 ON 72 22 68 20 Pattern 2 SET3 3 3 4 Heating setting temperature SET3 3 SET3 4 Heating setting temperature F C Remarks Factory setting Stage 1 Stage 2 OFF OFF 81 27 86 30 Pattern 1 OFF ON 77 25 82 28 P...

Страница 727: ...cient Set the delay off time by SET2 3 and SET2 4 SET2 3 SET2 4 Delay off time Factory setting OFF OFF 0 minute OFF ON 5 minutes ON OFF 10 minutes ON ON 20 minutes SET2 1 2 2 Fan setting signal on terminal G SET2 1 SET2 2 Indoor unit airflow Factory setting OFF OFF AUTO OFF ON HIGH ON OFF MED ON ON LOW 2 22 Thermostat convertor 07 127 2 Function settings FUNCTION SETTINGS FUNCTION SETTINGS ...

Страница 728: ...following sections Button name and function on page 07 27 Indoor unit setting by UTY RNKU on page 07 84 Function details on page 07 96 Simple remote controller UTY RSKU UTY RHKU Airflow is set by function number 26 static pressure For details refer to the following sections Button name and function on page 07 39 Indoor unit setting by UTY RSKU UTY RHKU on page 07 90 Function details on page 07 96 ...

Страница 729: ...ster Indoor Unit b When Set is touched on the Master Indoor Unit Setting screen a verification screen is displayed Master Indoor Unit Setting Back Set Master Indoor Unit Setting Not Master Indoor Unit No Yes Master Indoor Unit Setting The connected indoor unit will be set as the master indoor unit OK c When Yes is touched on the verification screen the setting data is transmitted to the indoor uni...

Страница 730: ...d It automatically returns to the regular display after 20 seconds if there is no button entry When the setting or canceling is completed the indication on the wired remote con troller changes to the regular indication from blinking NOTES When operation lock indicator lights on the MODE button is locked because of the following reasons Operation lock indicator Priority on administrative indoor uni...

Страница 731: ...arison Indoor unit rotation operation Reduces the power consumption by changing the indoor unit which is to be set forced thermostat OFF in turn Operating the air conditioner even in the spring and autumn when the heat load is comparatively light may have an energy saving effect Because it is an intermittent operation it does not loose much comfort and is a control which is difficult for the user ...

Страница 732: ...other times when the heat load is high In addition because the upper limit capacity of the outdoor unit is limited directly it is a control which easily exhibits an energy saving effect compared to rotation control However because the outdoor unit does not operate above the limited capacity there may be a loss of comfort depend ing on the indoor heat load The operation capacity upper limit rate of...

Страница 733: ...Group A Group C Group A Group B Group C Group D Group B Group D Group A Group B Group C Group D Group A Group B Group C Group D Grou Grou ON ON ON OFF Step 1 Set temperature shift Step 2 Thermostat OFF Step 3 Outdoor unit stop Normal Indoor units outside the scope of energy saving control Specifies the maximum average electric power kW for the entire air conditioning system 1 period Without contro...

Страница 734: ...source supply system Electricity meter installation sites number s and connecting outdoor units Appropriate VT CT specifications For details refer to Electrical wiring on page 07 138 Installation restriction and requirement of energy saving units on page 07 136 Electricity meter system on page 07 149 3 Purchase the electricity meters and related hardware and materials For details refer to Electric...

Страница 735: ...m usage en vironment installation environment and so forth a different effect may appear according to the building and operating period even when operated with the same settings and schedule Try to gain an understanding of the features of each energy saving function and confirm the actual effect through operation and apply appropriate settings etc as required Target electric power of peak cut func...

Страница 736: ...TY APGXZ1 UTY PEGXZ1 stop energy saving control such as forced thermostat OFF outdoor unit forced OFF and outdoor unit capacity save from the building management system through the following units BACnet gateway Software Network convertor for LonWorks When energy saving control is performed from multiple points trouble may occur System controller BACnet gateway Energy saving control prohibited Ene...

Страница 737: ...me Because an actual System Controller calculate power charge apportionment data in one day units electricity charge apportionment calculation can be performed at an arbitrary day in one day units Example 1 When the tenants of a tenant building etc are billed for their air conditioning electricity charge once a month if the electricity bill arrives from the electric power company each month the el...

Страница 738: ...cated by CT ratio There are types which is inserted between power cables and types which are coupled to the power cables Pulse unit Pulse unit indicates the relationship between electricity meter output pulse and measured power The value specified in pulse unit indicates the power in kWh consumed on the power cable for 1 pulse Units kWh pulse The value specified by pulse unit takes into account th...

Страница 739: ...ine length restriction 25 m or less Between electricity meter and touch panel controller Wiring specifications 2 core twisted pair 0 33 mm2 22 AWG 3 1 Pulse signal normally OFF open ON closed when shorted 2 When affected by interference by induction select shielded CVV cable CVV S cable This is because copper shielding tape is wrapped around CVV cable and induction interference from ad jacent powe...

Страница 740: ...Electricity meter Roof air conditioner 1st floor air conditioner All refrigerant system Electric substation equipment Refrigerant system 1 SBK MBK Whm Refrigerant system 1 Heat pump type Installation example for each tenant Electric substation equipment SBK MBK SBK SBK MBK Whm Whm Whm 3 phase electric power Single phase electric power MBK Main Breaker SBK Sub Breaker Whm Electricity meter Roof air...

Страница 741: ... units which per form apportionment calculation Peak cut control Only for System controller Installation of an electricity meter is essential Power consumption graph display Only for System controller Installation of an electricity meter is essential Whm Whm Whm Electricity meter Installation example Remote controller group Electricity meter connection range Units without electricity meter Functio...

Страница 742: ... system 3 VRF network system 1 VRF network system 2 VRF network system 3 Whm Whm Whm Whm With the electricity charge apportionment function an electricity meter system cannot span TPC Whm Whm Whm Whm TPC1 management range TPC2 management range TPC2 TPC1 Whm Whm Whm TPC1 management range TPC2 management range TPC2 TPC1 Create an electricity meter system within the range of the units managed by each...

Страница 743: ...ent range TPC2 TPC1 Whm I F Whm I F Connect the electricity meter that measures the units managed by the appropriate TPC to the electricity meter I F belonging to the TPC main unit 2 26 Electricity charge apportionment setting System controller Touch panel controller 07 143 2 Function settings FUNCTION SETTINGS FUNCTION SETTINGS ...

Страница 744: ... meter is possible Whm There are no restrictions on outdoor units which connect an electricity meter An arbitrary electricity meter can be connected to an arbitrary outdoor unit 2 26 Electricity charge apportionment setting System controller Touch panel controller 07 144 2 Function settings FUNCTION SETTINGS FUNCTION SETTINGS ...

Страница 745: ...ich connects a group remote controller is an excep tion 1 The electricity charge apportionment function cannot be used with single types air condition ers which are connected to a network converter 2 In the peak cut control though the power will be included in the target power the actual con trol will not be performed Whm Single split sytem Single split system Whm Whm VRF system VRF system Electri...

Страница 746: ...y meter is used by electricity charge apportionment function install the elec tricity meter so that it does not cross over the contract setting set by electricity charge appor tionment Whm Whm Whm Whm Whm Whm Contract 1 Contract 2 Contract 3 Whm Whm Whm Whm Whm Whm Whm Whm Contract 1 Contract 2 Contract 3 2 26 Electricity charge apportionment setting System controller Touch panel controller 07 146...

Страница 747: ...unit only Connect the electricity meter to the outdoor unit Electricity meter is not connected to outdoor unit Whm Outdoor unit indoor unit electricity charge apportionment Connection of an electricity meter to the outdoor unit and indoor unit is necessary Electricity meter is not connected to some indoor units Electricity meter is connected to outdoor unit only even though outdoor unit indoor uni...

Страница 748: ...install the electricity meter so that the units A and B are included The input value in the calculation as a constant value when the external output value is ON is included Whm DX kit B External fan A Run stop state External output linked units Whm Whm DX kit B External fan A Run stop state External output linked units The electricity meter is installed so that the units A and B are included The e...

Страница 749: ...When installing electricity meters as shown below 5 electricity meters systems are set as follows Whm Whm Whm Whm Whm Whm Electricity meter system 1 Electricity meter system 2 Electricity meter system 3 Electricity meter system 4 Electricity meter system 5 Electricity meter Setting of outdoor unit and System controller To obtain the appropriate power consumption by System controller the power valu...

Страница 750: ...ome necessary when setting System controller later Refer also to Setting on outdoor unit PCB on page 07 60 Electricity meter pulse setting 1 Fixed to 1 When 1 pulse comes from the electricity meter the outdoor unit communicates 1 to the System controller System controller Electricity meter system setting Units measured by electricity meter Set the outdoor unit and indoor unit measured by the elect...

Страница 751: ...alent to 1kWh When set number of pulses come from the electricity meter the outdoor unit communicates 1 to the system controller System controller Electricity meter system setting Units measured by electricity meter Set the outdoor unit and indoor unit measured by the electricity meter of the meter no set at the outdoor unit The value set by each outdoor unit is used Pulse setting Electricity mete...

Страница 752: ...2 26 Electricity charge apportionment setting System controller Touch panel controller 07 152 2 Function settings FUNCTION SETTINGS FUNCTION SETTINGS ...

Страница 753: ...8 EXTERNAL INPUT AND OUTPUT 2019 11 01 DV_CH08_J3LU061EF_02 ...

Страница 754: ...nit external input output 08 7 3 Indoor unit 08 8 3 1 Combination of external input and output 08 9 3 2 External input 08 10 3 3 External output 08 34 3 4 Function summary of indoor unit external input and output 08 55 3 5 Optional parts 08 56 4 Controller 08 57 4 1 Touch panel controller 08 57 4 2 Central remote controller UTY DCGY 08 63 4 3 Central remote controller UTY DCGYZ1 08 69 4 4 Function...

Страница 755: ...units are as follows 1 2 Connected unit Max length L Cable PCB Type L ft m Input Output Outdoor unit 492 150 492 150 Indoor unit 492 150 82 25 Touch panel controller 82 25 82 25 Central remote controller 82 25 82 25 08 1 1 Design precautions EXTERNAL INPUT AND OUTPUT EXTERNAL INPUT AND OUTPUT ...

Страница 756: ...ent location on page 08 2 Wiring specifications on page 08 3 External input on page 08 3 External output on page 08 5 Optional parts on page 08 6 Function summary of outdoor unit external input output on page 08 7 2 1 Component location CN136 BLK EXT OUT 1 CN137 BLU EXT OUT 2 CN131 YEL CN132 GRN CN134 RED CN133 WHT CN135 ORG EXT IN 1 PLUSE IN EXT IN 4 EXT IN 2 EXT IN 3 CN115 BLK BASE HEATER Outdoo...

Страница 757: ...n Batch stop or Emergency stop operation 2 3 CN135 Orange 4 No pulse No information from electricity meter Pulse Power usage information from electricity meter 1 The external input priority mode must be set by pressing push button on outdoor unit PCB 2 Batch stop or Emergency stop pattern can be selected by pressing push button on outdoor unit PCB 3 The emergency stop function mounted in the equip...

Страница 758: ...te controller is possible When function setting is Emergency stop mode Connector Input signal Command CN134 On Emergency stop Off Normal CN134 Indoor unit Outdoor unit Command Operation Emergency stop Normal On On On On Off Stop Remote controller NOTES All indoor units of same refrigerant system stops when Emergency stop operates When the Emergency stop is triggered indoor unit stops and Start Sto...

Страница 759: ...less Provide a load resistance such that the current be comes 30 mA or less 3 Polarity is for pin no 1 and for pin no 2 Connect correctly Operation status This output indicates Operation status of the outdoor unit As for the required wiring specifications refer to Wiring specifications on page 08 3 Operation 12 24 V 0 V Stop 1 2 CN137 Blue Connected unit DC power supply External 12 to 24 V Connect...

Страница 760: ...connection to pin no 2 and pin no 4 2 The allowable current is 1 A or less 2 5 Optional parts External connect kit Model name Exterior Q ty Usage UTY XWZXZ6 1 For external input Low noise mode Cooling Heating priority Outdoor unit operation peak control Emergency Batch stop For external output Error status Operation status UTY XWZXZ9 1 For external output Base heater UTY XWZXZF 1 For external inpu...

Страница 761: ...t 40 capacity 30 02 Energy saving level 3 Operated at 60 capacity 30 03 Energy saving level 4 Operated at 80 capacity 30 03 Energy saving level 5 Operated at 100 capacity NOTES For selecting relay minimum permissible load must be less than 1 mA When using Apply voltage take polarity for Pin 1 Number inside bracket such as 20 00 in the table above indicates function number and set ting number Equip...

Страница 762: ...t CNA02 UTY XWZXZD Forced thermostat off Apply voltage CNA03 UTY XWZXZ7 Dry contact CNA04 UTY XWZXZE Operation status CNB01 UTY XWZXZC Error status Indoor unit status Auxiliary heater output RELATED LINKS External input on page 08 10 External output on page 08 34 Optional parts on page 08 56 Function summary of indoor unit external input and output on page 08 55 08 8 3 Indoor unit EXTERNAL INPUT A...

Страница 763: ...VRF cooling on Cooling thermostat on Cooling HIGH LOW output Remote controller output External heater output 60 04 Economizer 3 Cooling 2 output Nothing heater output VRF cooling on Cooling thermostat on Error status Remote controller output Cooling HIGH LOW output 60 05 Humidifier 1 Nothing operation status output Forced thermostat off Heating thermostat on Error status Indoor unit fan operation ...

Страница 764: ...terminal of Dry contact terminal according to the application Both types of terminals cannot be used simultaneously CNA01 CNA03 Apply voltage terminal When a power supply must be provided at the input device you want to connect use the Apply voltage terminal CNA01 CNA03 1 2 1 2 3 Input device 1 Input device 2 Input device 3 1 2 2 3 2 DC power supply 12 to 24 V Connected unit PCB CNA01 CNA03 Load r...

Страница 765: ...01 Indoor unit 1 2 3 PCB CNA01 Indoor unit CNA02 CNA04 Dry contact terminal When a power supply is unnecessary at the input device you want to connect use the Dry contact terminal CNA02 CNA04 1 2 1 2 3 Connected unit PCB GND Ch1 Ch3 Ch2 CNA02 CNA04 1 1 2 1 1 Select very low current use contacts usable at DC 12 V DC 1 mA or less 2 The wiring is different from Apply voltage terminals Be sufficiently...

Страница 766: ...not connect to multiple indoor units directly since it will cause breakdown Input signal type The input signal type can be selected by switching the DIP switch on the indoor unit PCB DIP switch SET2 2 Edge or Pulse selection of external input SET2 2 External input select Factory setting Off Edge On Pulse Pulse Edge The width of pulse must be longer than 200 msec NOTE Input signal type of Ch3 Force...

Страница 767: ...tory setting CNA01 or CNA02 EXT IN1 Ch1 Off On Operation On Off Stop Operation Stop Remote controller On Off Indoor unit On Ch1 input of CNA01 or CNA02 In case of Pulse input Function setting DIP switch Connector Channel no Input signal Command 46 00 SET2 2 On CNA01 or CNA02 EXT IN1 Ch1 Off On Operation Ch2 Off On Stop On On Off Operation Stop Remote controller On Off Indoor unit Ch1 Input CNA01 o...

Страница 768: ...ormal On Off Emergency stop Normal Operation Stop Remote controller On On Indoor unit Command On Ch1 input of CNA01 or CNA02 In case of Pulse input Function setting DIP switch Connector Channel no Input signal Command 46 01 SET2 2 On CNA01 or CNA02 EXT IN1 Ch1 Off On Emergency stop Ch2 Off On Normal On Off Operation Stop Remote controller On Off Emergency stop Normal On On On Indoor unit Command C...

Страница 769: ...n Forced stop On Off Normal On Off Emergency stop Normal Operation Stop Remote controller On On Indoor unit Command On Ch1 input of CNA01 or CNA02 In case of Pulse input Function setting DIP switch Connector Channel no Input signal Command 46 02 SET2 2 On CNA01 or CNA02 EXT IN1 Ch1 Off On Forced stop Ch2 Off On Normal On Off Operation Stop Remote controller On Off Forced stop Normal On On On Indoo...

Страница 770: ... resistance Load resistance Indoor unit 1 2 3 PCB CNA01 Indoor unit 1 2 3 PCB CNA01 Indoor unit Wired or Simple remote controller Remote controller group 1 2 3 Input device 1 Input device 2 DC power supply 12 to 24 V Connected unit PCB PROHIBITED CNA01 Load resistance Load resistance Indoor unit 1 2 3 PCB CNA01 Indoor unit 1 2 3 PCB CNA01 Indoor unit Wired or Simple remote controller Remote contro...

Страница 771: ...etting for Fan setting when cooling thermostat off Number 49 00 Follow the setting on the remote controller Forced thermostat off is one of the energy saving functions For example when the outdoor tem perature is lower than the indoor temperature indoor unit of air conditioner perform Fan operation based on the received signal from external controller Cooling only 82 F 28 C 75 C 24 C Cooling opera...

Страница 772: ...or temp On Outdoor temp Indoor temp Off Normal Forced thermostat off Open Close Signal detected by external controller Command from external controller EEV Indoor unit Fan On Off Normal means that the indoor unit continues appropriate operation until Forced thermostat off sig nal is received at condition which are set by central and individual controller or detected by ther mo sensors of the indoo...

Страница 773: ...it Function no Set setting no 49 00 Setting no Example of electrical circuit 1 2 3 4 5 6 1 2 CNA04 Indoor unit Service parts Relay External controller Indoor unit PCB Max 492 ft 150 m Dry contact external input wire CNB01 Specification of external input Item Specification Terminal CNA04 Output voltage DC 12 V Wire diameter 22 AWG 0 33 mm2 Twisted Service part no 9368778019 Requirement for relay sw...

Страница 774: ...rmistor Indoor temperature Outdoor temperature Indoor temperature Outdoor temperature Cooling operation Thermostat on Fan stop Thermostat off 82 F 28 C 75 C 24 C 88 F 31 C 82 F 28 C System diagram example oor unit䛸External Input re Service parts ௨እ䛿䛩䜉 ᆅㄪ㐩䛻䛺䜚䜎䛩䚹 External controller External input wire Ventilator Except Indoor unit and External wire service parts are procured at field Indoor tempera...

Страница 775: ...y central and individual controller or detected by ther mo sensors of the indoor unit Function setting of indoor unit Indoor unit continues appropriate operation until Forced thermostat off signal is received at condi tion which are set by central and individual controller or detected by thermo sensors of the indoor unit Once the Forced thermostat off signal is received the indoor unit stops opera...

Страница 776: ...ternal input wire CNB01 Specification of external input Item Specification Terminal CNA04 Output voltage DC 12 V Wire diameter 22 AWG 0 33 mm2 Twisted Service part no 9368778019 Requirement for relay switch Item Specification Minimum permissible load 1 mA or less 3 2 External input 08 22 3 Indoor unit EXTERNAL INPUT AND OUTPUT EXTERNAL INPUT AND OUTPUT ...

Страница 777: ... Individual connection 76 F 80 F 74 F 84 F 68 F Away Custom Auto Auto Cool Heat Office Set Temp Mode Menu Status Vacation Fan Fri 10 00AM Room Temp Cool Heat Direct Digital Controller Thermistor Ventilator Output Cooling thermostat on Output Off Cooling thermostat off Input VRF cooling control Input On VRF cooling off 76 F 80 F 74 F 84 F 68 F Away Custom Auto Auto Cool Heat Office Set Temp Mode Me...

Страница 778: ... electrical circuit 1 2 3 4 5 6 1 2 CNA04 Indoor unit Service parts Relay External controller Indoor unit PCB Max 492 ft 150 m Dry contact external input wire CNB01 Specification of external input Item Specification Terminal CNA04 Output voltage DC 12 V Wire diameter 22 AWG 0 33 mm2 Twisted Service part no 9368778019 Requirement for relay switch Item Specification Minimum permissible load 1 mA or ...

Страница 779: ...ditioner Economizer Remarks Heating Cold climate 34 F 1 C or less Minimum Heating Disabled Heating by air conditioner Fresh air intake cooling Cool climate 34 to 55 F 1 to 13 C Optimum Stop Enabled Cooling by intaken fresh air only Combined Warm climate 55 to 75 F 13 to 24 C 100 Cooling Enabled Combined cooling by intaken fresh air and air conditioner VRF cooling Hot climate 75 F 24 C or more Mini...

Страница 780: ...udges the amount of outdoor air intake depending on indoor unit output at operating condition occupied status and outdoor temperature etc Operating mode Operation Condition Enthalpy or Temperature VRF indoor unit Damper Free cooling Outdoor Return Mechanical cooling Cooling on Off HIGH LOW Mechanical and free cooling Cooling on On LOW HIGH Cooling thermostat off or Heating Cooling off Off Off Cool...

Страница 781: ...t Economizer logic modules Only the terminals connected to the indoor unit are mentioned here for description As for the connected sensor or other connections to economizer logic module refer to the manual of the module 3 2 External input 08 27 3 Indoor unit EXTERNAL INPUT AND OUTPUT EXTERNAL INPUT AND OUTPUT ...

Страница 782: ...ing on Economizer input Cooling HIGH LOW output Cooling 2 Cooling thermostat on Cooling 1 Wired remote controller Economizer logic module Indoor unit Occupied Unoccupied status Remote controller output Occupied Unoccupied status By the wired remote controller touch panel external output indication is transferred to economiz er logic module through the indoor unit Economizer logic module is require...

Страница 783: ...oling LOW On Off LOW On Occupied On Minimum Mechanical cooling HIGH On On HIGH On Occupied On Minimum Free cooling only On Off LOW On Occupied Off Modulating Min Max Mechanical and free cooling On On HIGH On Occupied On Modulating Min Max Cooling thermostat off or Heating Off On Occupied Off Minimum Off Off Off Unoccupied Off None 1 Indoor unit decides the cooling HIGH LOW based on the set tempera...

Страница 784: ... diagram example Economizer 2 Function setting 60 03 1 2 3 4 1 2 TR 1 3 N TR1 2 5 5 6 Indoor unit Economizer logic modules Relay Coil side DC 12V Relay Coil side AC 24V CNB01 CNA04 AC power supply 24V Only the terminals connected to the indoor unit are mentioned here for description As for the connected sensor or other connections to economizer logic module refer to the manual of the module 3 2 Ex...

Страница 785: ... DC 12V Relay Coil side AC 24V CNB01 CNA04 AC power supply 24V Only the terminals connected to the indoor unit are mentioned here for description As for the connected sensor or other connections to economizer logic module refer to the manual of the module 3 2 External input 08 31 3 Indoor unit EXTERNAL INPUT AND OUTPUT EXTERNAL INPUT AND OUTPUT ...

Страница 786: ...n page 08 32 60 06 Output 4 Pins 1 5 60 07 Output 3 Pins 1 4 60 08 Output 2 Pins 1 3 In line 60 05 43 00 Enabled Output 1 Pins 1 2 Output 3 Pins 1 4 Refer to Example 2 In line connection on page 08 33 60 06 Output 4 Pins 1 5 60 05 43 01 Disabled Output 1 Pins 1 2 Not used Refer to Example 3 In line connection on page 08 33 60 06 Output 4 Pins 1 5 60 07 Output 3 Pins 1 4 60 08 Output 2 Pins 1 3 Exa...

Страница 787: ...l output Heating thermostat on Humidifier Operation status Heating operation Heating thermostat on output EEV on off External heater output on off Fan 43 00 43 01 Cool air prevention OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON The heating thermostat output for CNB01 1 2 or 1 3 or 1 4 or 1 5 will be on when EEV on or exter nal heater on The heating thermostat output will be off when EEV off or extern...

Страница 788: ...indicator etc are connected directly 1 2 3 4 5 6 PCB CNB01 Connected device 1 Operation status Connected device 3 Indoor unit fan operation status Connected device 2 Error status When connecting to unit equipped with a power supply 1 2 3 4 5 6 Relay PCB CNB01 Connected device 1 Operation status Connected device 3 Indoor unit fan operation status Connected device 2 Error status Connected device 4 E...

Страница 789: ... 1 3 is on when an error is generated for the indoor unit Error Normal 12 V 0 V CNB01 1 3 Output Indoor unit Indoor unit fan operation status External output 3 Function setting Connector Output signal Command 60 00 60 01 CNB01 Pins 1 4 0 V 12 V Fun run 60 05 60 06 12 V 0 V Fun stop The output for CNB01 1 4 is on when the indoor unit fan is operating The output is off when the fan is stopped or dur...

Страница 790: ... Enabled Individual Off Auxiliary heater control by outdoor temperature 2 VRF heat pump External device In line 61 04 On Enabled Individual Off Auxiliary heater control by outdoor temperature 3 VRF heat pump External device 2 In line 61 05 On Enabled Individual Off Auxiliary heat pump control External device VRF heat pump In line 61 06 On Enabled Individual Off Auxiliary heat pump control by outdo...

Страница 791: ...pump control by outdoor temperature 1 External device VRF heat pump 3 In line 35 01 Enabled Individual On Enabled 1 Auxiliary heat pump control by outdoor temperature 2 External device VRF heat pump 2 In line 35 01 Enabled Individual On Enabled 1 Auxiliary heat pump control by outdoor temperature 3 External device VRF heat pump 2 3 In line 35 01 Enabled Individual On Enabled 1 NOTES Corresponding ...

Страница 792: ...le of heating device Floor heating device On Off WARNING For duct and cassette types always set indoor unit fan setting for external heater when auxil iary heater is installed Design and install external heater appropriately with considering its protection For wall mounted type combination use with an external heater as shown below is prohibited External heater Indoor unit Supply air Return air In...

Страница 793: ...nnecessary Off Off Off Off B Primary heater only When room temperature stays in zone B for a long time auxiliary equipment also operates On Off 1 C Auxiliary equipment also operates On On 2 On On 2 1 For standby time for auxiliary equipment operation refer to indoor unit function number 71 Func tion details in Chapter 7 FUNCTION SETTINGS on page 07 96 2 When indoor unit function number 61 is set t...

Страница 794: ...nd room temperature Tr increases above 69 8 F 21 C signal output is off and room temperature Tr decreases below 66 2 F 19 C signal output is on and room temperature Tr decreases below 50 F 10 C signal output is off Auxiliary heater control 2 Control that excludes A from Auxiliary heater control 1 on page 08 40 Operation Condition Heater on Heater is on as shown in following diagram of heating temp...

Страница 795: ...ature Other than heating mode Error occurred Forced thermostat off Indoor unit fan setting for external heater Disabled Temperature of heater on Thon Adjustable by function number 62 for indoor unit Operating temperature switching of external heaters All control temperatures will shift by adjusting Thon Tr Room temperature Ts Set temperature Thon Heater on temperature Off On Tr Ts Tr Ts Thon 0 9 F...

Страница 796: ...al heater Disabled Temperature of heater on Thon Adjustable by function number 62 for indoor unit Operating temperature switching of external heaters All control temperatures will shift by adjusting Thon Outdoor temperature zone boundary A and B Adjustable individually by function setting number 36 and 37 for outdoor unit External heater output Tr Room temperature Ts Set temperature Thon Heater on...

Страница 797: ... that zone for minimum of 30 min 46 4 F 8 C 42 8 F 6 C 0 4 F 18 C 4 F 20 C On Off Fan DIP SW2 3 On DIP SW2 3 Off NOTE In following operations EEV will be on in heat pump prohibition zone Other than heating Test run This control is enabled when the function setting number 35 of the outdoor unit presence of heater selection control by outdoor temperature is enabled 3 3 External output 08 43 3 Indoor...

Страница 798: ...stat off Indoor unit fan setting for external heater Disabled Temperature of heater on Thon Adjustable by function number 62 for indoor unit Operating temperature switching of external heaters All control temperatures will shift by adjusting Thon Outdoor temperature zone boundary A Adjustable by function setting number 36 for outdoor unit External heater output Tr Room temperature Ts Set temperatu...

Страница 799: ...nimum of 30 min 46 4 F 8 C 42 8 F 6 C 0 4 F 18 C 4 F 20 C On Off On Off Fan DIP SW2 3 On DIP SW2 3 Off NOTE In following operations EEV will be on in heat pump prohibition zone Other than heating Test run This control is enabled when the function setting number 35 of the outdoor unit presence of heater selection control by outdoor temperature is enabled 3 3 External output 08 45 3 Indoor unit EXTE...

Страница 800: ...ostat off Indoor unit fan setting for external heater Disabled Temperature of heater on Thon Adjustable by function number 62 for indoor unit Operating temperature switching of external heaters All control temperatures will shift by adjusting Thon Outdoor temperature zone boundary B Adjustable by function setting number 37 for outdoor unit External heater output Tr Room temperature Ts Set temperat...

Страница 801: ...erature zone 46 4 F 8 C 42 8 F 6 C 0 4 F 18 C 4 F 20 C On Off On Off Fan DIP SW2 3 On DIP SW2 3 Off NOTE In following operations EEV will be on in heat pump prohibition zone Other than heating Test run This control is enabled when the function setting number 35 of the outdoor unit presence of heater selection control by outdoor temperature is enabled 3 3 External output 08 47 3 Indoor unit EXTERNA...

Страница 802: ...re of heater on Thon Set temperature Ts 0 9 F 0 5 C Temperature of heater off Set temperature Ts 0 9 F 0 5 C Tr Room temperature Ts Set temperature Thon Heater on temperature Off On Tr Ts Tr Ts Thon 0 9 F 0 5 C Tr Ts 0 9 F 0 5 C Auxiliary heat pump On Off Temperature of heater on Thon Adjustable by function number 62 for indoor unit Operating temperature switching of heat pump All control temperat...

Страница 803: ...ed Temperature of heater on Thon Set temperature Ts 0 9 F 0 5 C Temperature of heater off Set temperature Ts 0 9 F 0 5 C Tr Room temperature Ts Set temperature Thon Heater on temperature Off On Tr Ts Tr Ts Thon 0 9 F 0 5 C Tr Ts 0 9 F 0 5 C Auxiliary heat pump On Off Temperature of heater on Thon Adjustable by function number 62 for indoor unit Operating temperature switching of heat pump All cont...

Страница 804: ...e outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min 46 4 F 8 C 42 8 F 6 C 0 4 F 18 C 4 F 20 C On Off On Off Fan DIP SW2 3 On DIP SW2 3 Off NOTE In following operations EEV will be on in heat pump prohibition zone Other than heating Test run This control is enabled when the function setting number 35 of the outdoor unit presence of heater selection...

Страница 805: ...ed Temperature of heater on Thon Set temperature Ts 0 9 F 0 5 C Temperature of heater off Set temperature Ts 0 9 F 0 5 C Tr Room temperature Ts Set temperature Thon Heater on temperature Off On Tr Ts Tr Ts Thon 0 9 F 0 5 C Tr Ts 0 9 F 0 5 C Auxiliary heat pump On Off Temperature of heater on Thon Adjustable by function number 62 for indoor unit Operating temperature switching of heat pump All cont...

Страница 806: ...ion zone On 12 V Off 0 V Heater EEV On Off Outdoor temperature Factory setting Outdoor temperature zone 46 4 F 8 C 42 8 F 6 C 0 4 F 18 C 4 F 20 C On Off On Off Fan DIP SW2 3 On DIP SW2 3 Off NOTE In following operations EEV will be on in heat pump prohibition zone Other than heating Test run This control is enabled when the function setting number 35 of the outdoor unit presence of heater selectio...

Страница 807: ...ed Temperature of heater on Thon Set temperature Ts 0 9 F 0 5 C Temperature of heater off Set temperature Ts 0 9 F 0 5 C Tr Room temperature Ts Set temperature Thon Heater on temperature Off On Tr Ts Tr Ts Thon 0 9 F 0 5 C Tr Ts 0 9 F 0 5 C Auxiliary heat pump On Off Temperature of heater on Thon Adjustable by function number 62 for indoor unit Operating temperature switching of heat pump All cont...

Страница 808: ...erature zone transition from one to another will stay in that zone for minimum of 30 min 46 4 F 8 C 42 8 F 6 C 0 4 F 18 C 4 F 20 C Combination zone Heat pump prohibition zone On Off On Off Fan DIP SW2 3 On DIP SW2 3 Off NOTE In following operations EEV will be on in heat pump prohibition zone Other than heating Test run This control is enabled when the function setting number 35 of the outdoor uni...

Страница 809: ...ize 22 AWG 0 33 mm2 Twisted Max cable length 492 ft 150 m Default setting is Edge signal If you use Pulse signal DIP switch 2 2 must be set to On Indoor unit external output function Dry contact Apply voltage Dry contact Function Operation status Error status Indoor unit fan operation status Auxiliary heater output Specifications Terminal CNB01 Pin1 2 CNB01 Pin1 3 CNB01 Pin1 4 CNB01 Pin1 5 Termina...

Страница 810: ...ly voltage terminal UTY XWZXZC 1 For output port UTY XWZXZB 1 For control input port Apply voltage terminal UTY XWZXZD 1 For control input port Dry contact terminal UTY XWZXZE 1 For forced thermostat off port Dry contact terminal 3 5 Optional parts 08 56 3 Indoor unit EXTERNAL INPUT AND OUTPUT EXTERNAL INPUT AND OUTPUT ...

Страница 811: ... 75 External input This function performs Emergency stop or All On All Off by using the signal to be input externally at external input terminals Input select Use either one of Apply voltage terminal of Dry contact terminal according to the application Both types of terminals cannot be used simultaneously For more details refer to the operation manual of Touch panel controller It is possible to sw...

Страница 812: ...etection resistance R ON 500 Ω Open circuit detection resistance R OFF 100 kΩ A twisted pair cable 22 AWG 0 33 mm2 should be used Maximum cable length 82 ft 25 m Connection example 2 When the electricity meter is connected Electricity meter K1 K2 K1 K2 CH1 CH2 TM201 EXTERNAL INPUT RED CN412 WHITE CN411 CN201 PCB PCB Connect the electricity meter to CH1 In this case the use of CH2 is prohibited 4 1...

Страница 813: ...M201 EXTERNAL INPUT RED CN412 WHITE CN411 CN201 PCB PCB Electricity meter 1 Make the power supply DC12 to 24 V Select a power supply capacity with an ample sur plus for the connected load 2 Do not impress a voltage exceeding 24 V across K1 K2 3 The allowable current is DC 10 mA or less Recommended DC 5 mA Provide a load resistance such that the current becomes DC10 mA or less Select very low curre...

Страница 814: ...ected Edge L H Emergency stop or All on Ch1 L H Emergency stop reset or All off Pulse L H 300 ms or more Emergency stop or All on Ch1 Emergency stop reset or All off Ch2 L H 50 ms or more Electricity meter signal Ch1 When Edge is selected only Ch1 can be used Control input function In case of Edge input Terminal Channel no Input signal Command TM201 Ch1 Off On All on Emergency stop On Off All off ...

Страница 815: ...Ch1 Pulse All on Emergency stop Ch2 All off Normal Off Off On On TM201 Ch1 Ch2 Indoor unit The width of pulse must be longer than 300 msec All on Emergency stop All off Normal 4 1 Touch panel controller 08 61 4 Controller EXTERNAL INPUT AND OUTPUT EXTERNAL INPUT AND OUTPUT ...

Страница 816: ... DC 15 mA or less 3 Polarity is for pins 1 and 3 for pins 2 and 4 Connect correctly Operation status External output 1 The output for CN410 1 2 is on when one or more indoor units are operating The output is off when all of the indoor units are stopped Operation Stop 12 V 0 V CN410 1 2 output Indoor unit s Error status External output 2 The output for CN410 3 4 is on when an error is generated at ...

Страница 817: ...mergency stop or All On All Off by using the signal to be input externally at external input terminals Input select Use either one of Apply voltage terminal or Dry contact terminal according to the application Both types of terminals cannot be used simultaneously CN6 and CN7 Dry contact terminal When a power supply is unnecessary at the input device you want to connect use the Dry contact terminal...

Страница 818: ...t a power supply capacity with an ample sur plus for the connected load 2 Do not impress a voltage exceeding 24 V across pin 1 3 3 The allowable current is DC 5 mA or less Recommended DC 5 mA Provide a load resistance such that the current becomes DC 5 mA or less A twisted pair cable 22 AWG 0 33 mm2 should be used Maximum cable length 82 ft 25 m 4 2 Central remote controller UTY DCGY 08 64 4 Contr...

Страница 819: ...input signals 2 Press the button and move the cursor to the Input Method menu Edge button Detects the signal rise and fall Pulse button Detects the signal level Pulse Edge The width of pulse must be longer than 300 msec 3 When the button is pressed setting is complete Control input function In case of Edge input Connector Input signal Command CN6 or CN11 Off On All on Emergency stop On Off All off...

Страница 820: ...ency stop CN7 or CN12 Off On All off Normal Off Off On On CN6 or CN11 CN7 or CN12 Indoor unit The width of pulse must be longer than 300 msec All on Emergency stop All off Normal 4 2 Central remote controller UTY DCGY 08 66 4 Controller EXTERNAL INPUT AND OUTPUT EXTERNAL INPUT AND OUTPUT ...

Страница 821: ...a load resistance such that the current becomes DC 15 mA or less 3 Polarity is for pins 1 and 3 for pins 2 and 4 Connect correctly Operation status External output 1 The output for CN9 3 4 is on when one or more indoor units are operating The output is off when all of the indoor units are stopped Operation Stop 12 V 0 V CN9 3 4 Output Indoor unit s Error status External output 2 The output for CN9...

Страница 822: ...WZXZ7 Edge Pulse For control input port Dry contact terminal 2 1 UTY XWZXZ8 Edge Pulse For control input port Apply voltage terminal 2 1 UTY XWZXZA 1 For output port 4 2 Central remote controller UTY DCGY 08 68 4 Controller EXTERNAL INPUT AND OUTPUT EXTERNAL INPUT AND OUTPUT ...

Страница 823: ... of Apply voltage terminal or Dry contact terminal according to the application Both types of terminals cannot be used simultaneously CN12 CH1 and CN13 CH2 Dry contact terminal When a power supply is unnecessary at the input device you want to connect use the Dry contact terminal CN12 Ch1 and CN13 Ch2 PCB CN13 Ch2 Black CN12 Ch1 White Connected unit Short circuit detection resistance R ON 500 Ω Op...

Страница 824: ...oss pin 1 3 3 The allowable current is DC 5 mA or less Recommended DC 5 mA Provide a load resistance such that the current becomes DC 5 mA or less A twisted pair cable 22 AWG 0 33 mm2 should be used Maximum cable length 82 ft 25 m Input method Terminal Input signal Operation Edge CN14 Ch1 Low High Emergency Stop or All on High Low Emergency Stop reset or All Off Pulse CN14 Ch1 Low High Emergency S...

Страница 825: ...ables Emergency stop by external input All On Off Enables batch operation on or off by external input Not Used Does not receive external input signals 5 Tap Input method and select following input method Edge button Detects the signal rise and fall Pulse button Detects the signal level Pulse Edge The width of pulse must be longer than 300 msec 6 When OK button is tapped setting is complete 4 3 Cen...

Страница 826: ...f Normal In case of Pulse input Connector Input signal Command CN12 Ch1 or CN14 Ch1 Off On All on Emergency stop CN13 Ch2 or CN15 Ch2 Off On All off Normal Off Off On On CN13 Ch2 or CN15 Ch2 CN12 Ch1 or CN14 Ch1 Indoor unit The width of pulse must be longer than 300 msec All on Emergency stop All off Normal 4 3 Central remote controller UTY DCGYZ1 08 72 4 Controller EXTERNAL INPUT AND OUTPUT EXTERNAL...

Страница 827: ...istance such that the current becomes DC 15 mA or less 3 Polarity is for pins 1 and 3 for pins 2 and 4 Connect correctly Operation status External output 1 The output for CN18 3 4 is on when one or more indoor units are operating The output is off when all of the indoor units are stopped Operation Stop 12 V 0 V CN18 3 4 Output Indoor unit s Error status External output 2 The output for CN18 1 2 is...

Страница 828: ...ZXZ7 Edge Pulse For control input port Dry contact terminal 1 2 UTY XWZXZ8 Edge Pulse For control input port Apply voltage terminal 1 2 UTY XWZXZA 1 For output port 4 3 Central remote controller UTY DCGYZ1 08 74 4 Controller EXTERNAL INPUT AND OUTPUT EXTERNAL INPUT AND OUTPUT ...

Страница 829: ...e size 22 AWG 0 33 mm2 Twisted Max cable length 82 ft 25 m Central remote controller UTY DCGY Dry contact Apply voltage Dry contact Apply voltage Function Emergency stop Screen icon Screen icon All on All off Screen icon Screen icon Specifications Terminal CN6 Pin 1 2 CN6 Ch1 Pin 1 2 CN7 Ch2 Pin 1 2 CN11 Pin 1 3 CN11 Ch1 Pin 1 3 CN12 Ch2 Pin 1 3 Signal type Edge Pulse Edge Pulse External power sup...

Страница 830: ...Apply voltage Apply voltage Function Operation status Error status Specifications Terminal CN410 Pin1 2 CN410 Pin3 4 External power supply Allowable voltage DC12 V Allowable current 15 mA or less Wire size 22 AWG 0 33 mm2 Twisted Max cable length 82 ft 25 m Controller Central remote controller Model name UTY DCGY UTY DCGYZ1 Dry contact Apply voltage Apply voltage Apply voltage Function Operation s...

Страница 831: ...9 NOTES 2019 11 01 DV_CH09_J3LU061EF_04 ...

Страница 832: ...4 2 Installation precautions 09 5 2 1 Indoor unit installation precautions 09 5 2 2 Outdoor unit installation precautions 09 8 3 Compatibility of VRF system 09 9 3 1 Compatibility of controller system 09 9 3 2 Compatibility of adapter convertor maintenance tool 09 12 4 About connection between series 09 14 4 1 Piping connection 09 14 4 2 Wiring connection 09 15 ...

Страница 833: ...ary safety concern is asphyxiation due to oxygen deprivation Concentration limit The purpose of the concentration limit is to protect occupants in the unlikely event that the entire re frigerant system leaks into the smallest room served by the system To calculate the potential refrig erant concentration divide the total refrigerant in the system by the volume of the smallest space served by the s...

Страница 834: ...t system is divided into 2 or more refrigerant systems and each system is in dependent total amount of refrig erant of each system shall be adopted 2 Calculate room volume by regarding portion marked in gray as one room or the smallest room a Without partition b When there are partitions but there is an effective opening for ventilation between the rooms Outdoor unit Indoor unit Outdoor unit Indoo...

Страница 835: ... ft3 kg m3 Capacity of smallest room where indoor unit is installed Unit ft3 m3 When the result of calculation exceeds the limiting concentration perform the same calculation by shifting to second smallest and the third smallest rooms until the final result is below the limiting concentration 1 2 Checking concentration limit 09 3 1 Refrigerant leakage caution NOTES NOTES ...

Страница 836: ...rigerant charging amount by shortening the length of the refrigerant pipes Lower the capacity of the outdoor unit Separate the outdoor unit into multiple units to lower the outdoor unit capacity for each refriger ant system and reduce the refrigerant charging amount For example by changing a 12 ton 1 unit system to a 6 ton 2 units system the refrigerant amount for each refrigerant system can be re...

Страница 837: ...her matter which effects equipment is gen erated Places where there is a lot of oil splash and steam such as kitchen or machinery room Places where machinery which generates high frequencies is used Ocean beaches and other areas where there is a lot of salt Places where carbon fibers or any kind of powder suspended in the air Inside of vehicles ships and other conveyances Places where voltage fluc...

Страница 838: ...t outlet When inside the ceiling is high temperature and high humidity When the indoor unit is installed where the inside of the ceiling is 86 F 30 C RH80 or greater the dew point temperature of the outer perimeter may become higher than the cabinet surface temperature and moisture will condense on the surface of the cabinet and water drops may fall inside the room Figure 2 1 Moist air curve In ad...

Страница 839: ... C Figure 2 1 Moist air curve Slit of heat insulating material facing upward Covered gas pipe heat insulation strengthened Heat insulating material locally purchased Small exposed part of copper pipe is desirable Fit tightly purpose is to cover the sealant Binding material Flare connection To indoor unit Heat insulation reinforcement material locally purchased Figure 2 2 Work method when reinforci...

Страница 840: ...laces Condition Contents Countermeasures Reference When installed near adjacent houses Perform installation work so that operating sound does not disturb the neighbors 1 Install a soundproof barrier 2 Change the installation site When there is the possibility of strong wind If the outdoor unit is exposed to strong wind capacity may drop frost may form during heating and operation may be stopped by...

Страница 841: ...xterior Part name Model name All series of outdoor unit System controller UTY APGXZ1 OK System controller lite UTY ALGXZ1 OK Touch panel controller UTY DTGYZ1 OK Central remote controller UTY DCGY OK Central remote controller UTY DCGYZ1 OK Different VRF series may be connected for each of the 4 VRF networks supported by the prod uct but different series may not coexist within the same network VR I...

Страница 842: ... Temp Cool Heat Wired remote controller Touch panel UTY RNRUZ OK SET TEMP START STOP Wired remote controller UTY RNKU OK Simple remote controller UTY RSRY OK Simple remote controller Without operation mode UTY RHRY OK Simple remote controller UTY RSKU OK Simple remote controller Without operation mode UTY RHKU OK 3 1 Compatibility of controller system 09 10 3 Compatibility of VRF system NOTES NOTE...

Страница 843: ...Model name All series of outdoor unit Wireless remote controller UTY LNHU OK It is not connectable with indoor units of previous model 3 1 Compatibility of controller system 09 11 3 Compatibility of VRF system NOTES NOTES ...

Страница 844: ...tor for LonWorks UTY VLGX OK Modbus convertor for VRF UTY VMGX OK Thermostat convertor UTY TTRX OK BACnet gateway Hardware UTY VBGX OK BACnet gateway Software UTY ABGXZ1 OK Wireless LAN adapter UTY TFSXZ2 OK Signal amplifier UTY VSGXZ1 OK External switch controller UTY TERX UTY TEKX OK 3 2 Compatibility of adapter convertor maintenance tool 09 12 3 Compatibility of VRF system NOTES NOTES ...

Страница 845: ... connected for each of the 4 VRF networks supported by the prod uct but different series may not coexist within the same network VR II V II J II J IIS and J IIIL can exist together in same network V and S can exist together in same network too 3 2 Compatibility of adapter convertor maintenance tool 09 13 3 Compatibility of VRF system NOTES NOTES ...

Страница 846: ...Outdoor unit J II Refrigerant pipe Separation tube Refrigerant system 1 Refrigerant system 2 Refrigerant system 3 RB unit Refrigerant pipe Separation tube Outdoor unit Refrigerant pipe Separation tube Outdoor unit Example 2 Prohibited VR II Outdoor unit V II Outdoor unit J II RB unit Refrigerant system 1 Refrigerant pipe Separation tube Outdoor unit 4 1 Piping connection 09 14 4 About connection b...

Страница 847: ...RF network system Refrigerant system 2 Refrigerant system 3 Outdoor unit Outdoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit RB unit IN U OUT U RB unit IN U OUT U RB unit IN U OUT U Indoor unit Indoor unit Indoor unit Refrigerant system 1 Refrigerant system 2 Refrigerant system 3 VR II Outdoor unit J II Outdoor unit V II Outdoor unit Master Master Slave...

Страница 848: ...utdoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit RB unit IN U OUT U RB unit IN U OUT U RB unit IN U OUT U Indoor unit Indoor unit Indoor unit Refrigerant system 1 Refrigerant system 2 Refrigerant system 3 VR II Outdoor unit J II Outdoor unit V II Outdoor unit Master Master Slave Slave Slave VR II Outdoor unit V II Outdoor unit VR II Outdoor unit Figur...

Страница 849: ... unit Outdoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit RB unit IN U OUT U RB unit IN U OUT U RB unit IN U OUT U Indoor unit Indoor unit Indoor unit Refrigerant system 1 Refrigerant system 2 Refrigerant system 3 VR II Outdoor unit J II Outdoor unit V II Outdoor unit Master Master Slave Slave Slave VR II Outdoor unit V II Outdoor unit VR II Outdoor uni...

Страница 850: ...4 2 Wiring connection 09 18 4 About connection between series NOTES NOTES ...

Страница 851: ...10 OPTIONAL PARTS 2019 11 01 DV_CH10_VR2E018EF_05 ...

Страница 852: ...ol 10 9 4 Adapter Convertor Maintenance tool 10 11 5 Cassette grille 10 13 6 Others 10 14 6 1 Parts list 10 14 6 2 Applicable parts 10 18 7 Optional parts installation 10 21 7 1 Drain pump unit for duct type 10 21 7 2 Drain pump unit for ceiling 10 25 7 3 Fresh air intake kit for compact cassette type 10 26 7 4 Fresh air intake kit for cassette type 10 36 7 5 Auto louver grille kit 10 46 7 6 Exter...

Страница 853: ...06 14 For 2 pipes Total cooling capacity of indoor units at rated condition x kBtu h Model name Connection capacity of separation tube kBtu h x 96 5 UTP AX090A 4 x 92 5 4 x 48 8 x 96 5 4 x 92 5 4 x 48 8 x 96 5 Liquid pipe Gas pipe 96 5 x UTP AX180A Liquid pipe Gas pipe 92 5 x 4 x 96 5 96 5 x 96 5 x 92 5 x 4 x 96 5 1 1 Connection capacity 10 1 1 Separation tube OPTIONAL PARTS OPTIONAL PARTS ...

Страница 854: ...8 80 Liquid pipe 1 Expander Ø3 4 19 05 Ø7 8 22 22 Ø7 8 22 22 Ø1 1 8 28 58 Expander 16 13 16 427 3 1 8 80 15 9 16 396 3 15 16 100 3 1 8 80 13 16 20 Ø3 8 9 52 Ø1 2 12 70 Ø5 8 15 88 Ø3 4 19 05 Ø7 8 22 22 Ø1 2 12 70 Ø5 8 15 88 Ø3 4 19 05 Ø3 8 9 52 Ø1 2 12 70 Ø5 8 15 88 13 16 20 Gas pipe 1 For liquid pipe 1 For gas pipe 1 Heat insulation 2 Tape 8 1 2 Dimensions 10 2 1 Separation tube OPTIONAL PARTS OPT...

Страница 855: ...3 8 9 52 Ø1 4 6 35 3 1 8 80 Liquid pipe 1 Reducer 10 5 16 262 3 1 8 80 13 3 4 349 5 1 8 130 Reducer 3 3 4 95 9 16 15 Ø3 4 19 05 Ø7 8 22 22 Ø1 1 8 28 58 Ø3 8 9 52 Ø1 2 12 70 Ø5 8 15 88 Ø1 1 8 28 58 Ø7 8 22 22 Ø3 4 19 05 Ø7 8 22 22 9 16 15 Gas pipe 1 For liquid pipe 1 For gas pipe 1 Heat insulation 2 Tape 8 1 2 Dimensions 10 3 1 Separation tube OPTIONAL PARTS OPTIONAL PARTS ...

Страница 856: ...Piping design in Chapter 6 SYSTEM DESIGN on page 06 14 Total cooling capacity of indoor units x Btu h 3 to 6 Branches 3 to 8 Branches x 96 500 UTR H0906L UTR H0908L 96 500 x UTR H1806L UTR H1808L 2 1 Connection capacity 10 4 2 Header OPTIONAL PARTS OPTIONAL PARTS ...

Страница 857: ... 25 1 16 637 6 1 16 154 2 13 16 72 Detail B Ø1 2 12 70 Ø5 8 15 88 Ø3 4 19 05 Ø7 8 22 22 Ø5 8 15 88 Ø1 2 12 70 Ø3 8 9 52 Ø1 2 12 70 Ø5 8 15 88 Ø3 4 19 05 3 8 10 1 9 16 40 3 8 10 1 9 16 40 2 13 16 72 1 9 16 40 3 8 10 3 1 8 80 3 1 8 80 3 1 8 80 2 3 8 60 Gas pipe 1 Ø1 4 6 35 1 15 16 50 Closed pipe A 4 Ø3 8 9 52 1 15 16 50 Closed pipe B 2 Ø1 2 12 70 1 15 16 50 Closed pipe C 2 Ø 1 2 6 3 8 1 0 Closed pip...

Страница 858: ...0 3 8 10 3 1 8 80 5 127 Ø1 2 12 70 Ø5 8 15 88 Ø3 4 19 05 Ø7 8 22 22 Ø5 8 15 88 Ø1 2 12 70 Ø3 8 9 52 3 1 8 80 2 3 8 60 3 1 8 80 3 1 8 80 3 1 8 80 2 3 8 60 2 3 8 60 3 8 10 1 9 16 40 2 13 16 72 3 8 10 1 9 16 40 2 13 16 72 Ø1 2 12 70 Ø5 8 15 88 Ø3 4 19 05 Gas pipe 1 Ø6 35 50 Ø1 4 6 35 1 15 16 50 Closed pipe A 6 Ø3 8 9 52 1 15 16 50 Closed pipe B 4 Ø1 2 12 70 1 15 16 50 Closed pipe C 2 Ø 1 2 6 3 8 1 0 ...

Страница 859: ...80 9 16 15 3 9 16 90 P3 1 8 7 22 1 16 P80 7 560 28 3 4 730 6 3 16 157 Detail A Detail B A B A A B A A A Ø1 1 8 28 58 3 8 10 1 9 16 40 2 13 16 72 3 8 10 1 9 16 40 2 13 16 72 Ø3 4 19 05 Ø7 8 22 22 Ø1 2 12 70 Ø5 8 15 88 Ø3 8 9 52 Ø1 2 12 70 Ø5 8 15 88 Ø13 16 20 Ø7 8 22 22 Gas pipe 1 Ø1 4 6 35 1 15 16 50 Closed pipe A 4 Ø3 8 9 52 1 15 16 50 Closed pipe B 2 Ø1 2 12 70 1 15 16 50 Closed pipe C 2 Ø 1 2 6...

Страница 860: ...8 80 9 16 15 3 9 16 90 P3 1 8 7 22 1 16 P80 7 560 28 3 4 730 6 3 16 157 Detail A Detail B A B A A B A A A Ø1 1 8 28 58 3 8 10 1 9 16 40 2 13 16 72 3 8 10 1 9 16 40 2 13 16 72 Ø3 4 19 05 Ø7 8 22 22 Ø1 2 12 70 Ø5 8 15 88 Ø3 8 9 52 Ø1 2 12 70 Ø5 8 15 88 Ø13 16 20 Ø7 8 22 22 Gas pipe 1 Ø1 4 6 35 1 15 16 50 Closed pipe A 6 Ø3 8 9 52 1 15 16 50 Closed pipe B 2 Ø1 2 12 70 1 15 16 50 Closed pipe C 4 Ø 1 2...

Страница 861: ...buildings and tenants The operation status of all connected indoor units can be viewed at a glance on a large LCD monitor to simplify individual control to batched control Central remote controller UTY DCGYZ1 Central control of small and medium sized buildings and tenants Central remote controller realizes the trouble support function remote monitoring and remote operation 3 2 Individual control E...

Страница 862: ...rature setting Wire type Non polar 2 wire Simple remote controller UTY RSKU Compact remote controller concentrates on the basic functions such as Start Stop fan control temperature setting and operation mode Wire type Polar 3 wire Simple remote controller Without operation mode UTY RHKU Compact remote controller concentrates on the basic functions such as Start Stop fan control temperature setting...

Страница 863: ...Fujitsu General products using a third party thermostat BACnet gateway Hardware UTY VBGX For connection between VRF network system to the BMS system using BACnet protocol Supports max 128 indoor units BACnet gateway Software UTY ABGXZ1 The central control of maximum 1600 indoor units can be realized by connecting the VRF network system to the BACnet a global standard for open network Wireless LAN ...

Страница 864: ...ion status and error history can be grasped promptly and adequately Web monitoring tool UTY AMGXZ1 Trouble free operation at all times by web monitoring system The operation status of the VRF network system within the building can be monitored in real time over the Internet 10 12 4 Adapter Convertor Maintenance tool OPTIONAL PARTS OPTIONAL PARTS ...

Страница 865: ...s For Compact cassette type UTG CCGVG Grid type grille For Compact cassette type UTG CCGV Standard type grille For Circular flow cassette type UTG LCGVCW UTG LCGVCB For Cassette type UTG LCGV 10 13 5 Cassette grille OPTIONAL PARTS OPTIONAL PARTS ...

Страница 866: ...e duct type Air filter UTD LF25NA 2 pcs For High static pressure duct type Air filter UTD LF60KA For Medium static pressure duct type Drain pump unit UTZ PU1NBA For Ceiling type Drain pump unit UTZ PU1EBA For Compact cassette type Air outlet shutter plate UTR YDZB For Cassette type and Circular flow cassette type Air outlet shutter plate UTR YDZK 6 1 Parts list 10 14 6 Others OPTIONAL PARTS OPTION...

Страница 867: ...G AKXA W For Compact floor type Half concealed kit UTR STA For all duct type IR receiver unit UTY TRHX For all duct type IR receiver unit UTB YWC For Cassette type IR receiver unit UTY LRHYB1 For Circular flow cassette type IR receiver unit UTY LBHXD For Circular flow cassette type Human sensor kit UTY SHZXC 6 1 Parts list 10 15 6 Others OPTIONAL PARTS OPTIONAL PARTS ...

Страница 868: ...tte type 2 For Compact cassette type Insulation kit for high humidity UTZ KXRA 1 For Compact cassette type Fresh air intake kit UTZ VXAA For Cassette type Fresh air intake kit UTZ VXRA For Mini duct and Slim duct type Auto louver grille kit UTD GXTA W For Slim duct type Auto louver grille kit UTD GXSA W UTD GXSB W External power supply unit UTZ GXXA 6 1 Parts list 10 16 6 Others OPTIONAL PARTS OPT...

Страница 869: ...emote controller UTY XWZXZ8 For Outdoor unit UTY XWZXZ9 For Touch panel controller and Central remote controller UTY XWZXZA For Indoor unit and RB unit UTY XWZXZB For Indoor unit UTY XWZXZC For Indoor unit UTY XWZXZD For Indoor unit UTY XWZXZE For Outdoor unit UTY XWZXZF 6 1 Parts list 10 17 6 Others OPTIONAL PARTS OPTIONAL PARTS ...

Страница 870: ... power supply unit UTY LRHYB1 UTY LBHXD UTY SHZXC UTZ GXXA Compact cassette Circular flow cassette Cassette Type Fresh air intake kit Model name UTZ VXAA UTZ VXRA Compact cassette AUUA4TLAV2 AUUA7TLAV2 AUUA9TLAV2 AUUA12TLAV2 AUUA14TLAV2 AUUA18TLAV2 AUUA24TLAV2 Circular flow cassette Cassette Type Insulation kit for high humidity UTZ KXRA UTZ KXGC Compact cassette Circular flow cassette Cassette Ty...

Страница 871: ...e duct Type IR receiver unit Air filter External power supply unit Model name UTB YWC UTY TRHX UTD LF25NA UTD LF60KA UTZ GXXA Mini duct Slim duct Slim concealed floor Medium static pressure duct High static pressure duct ARUH36TLAV ARUH48TLAV ARUH60TLAV ARUH72TLAV2 ARUH96TLAV2 Type Auto louver grille kit Model name UTD GXTA W UTD GXSA W UTD GXSB W Mini duct Slim duct Slim concealed floor ARUL7TLAV...

Страница 872: ...WZXZB UTY XWZXZC UTY XWZXZD UTY XWZXZE Wall mounted Type External power supply unit Model name UTZ GXXA Wall mounted ASUA4TLAV1 ASUA7TLAV1 ASUA9TLAV1 ASUA12TLAV1 ASUA14TLAV1 ASUB18TLAV1 ASUB24TLAV1 ASUA30TLAV2 ASUA36TLAV2 ASUA7TLAV ASUA12TLAV ASUB18TLAV ASUB24TLAV For others Type External connect kit UTY XWZXZ6 UTY XWZXZ7 UTY XWZXZ8 UTY XWZXZ9 Outdoor unit Touch panel controller Central remote con...

Страница 873: ...60 Hz mA 114 92 Dimensions H W D in mm 6 15 16 7 6 1 16 176 178 154 Weight lb kg 6 2 5 Connection pipe diameter in mm I D 3 4 19 05 O D 1 1 16 27 Direction of pipe connection 1 360 Angle of pipe connection 2 0 to 90 Horizontal to vertical Control method Control board of indoor unit Safety device Float switch Thermal fuse 1 Direction of pipe connection 2 Angle of pipe connection 7 1 Drain pump unit...

Страница 874: ... 000 1 13 16 46 10 5 8 270 Air Top view Front view 19 470 or more 6 150 or more Drain pump unit Connected drain pipe I D 3 4 19 05 O D 1 1 16 27 Rear view 7 178 6 7 16 163 6 15 16 176 NOTES Leave the space required to service the unit Set a maintenance hole near the drain pump unit 7 1 Drain pump unit for duct type 10 22 7 Optional parts installation OPTIONAL PARTS OPTIONAL PARTS ...

Страница 875: ...urely Make sure that the drain pump unit is not slanted 0 5 mm 0 5 mm AIR AIR Ceiling Level meter Level meter Good Bad Good Bad Installing hose Max 39 3 8 in 1 m Downward Vertical Horizontal Bend radius is 2 3 8 in 60 mm or more Downward gradient of 1 50 to 1 100 Part Hose Upward Trap Vertical loop Example of wrong construction 7 1 Drain pump unit for duct type 10 23 7 Optional parts installation ...

Страница 876: ...rap Bad Max 39 3 8 in 1 m For construct centralized drain pipe fittings refer to the electrical wiring Electrical wiring Model UTZ PU1NBA Control box Circuit board Drain pump wire Connector Blue Drain pump unit Float switch wire Connector Red Control box cover Indoor unit To indoor unit circuit board 7 1 Drain pump unit for duct type 10 24 7 Optional parts installation OPTIONAL PARTS OPTIONAL PART...

Страница 877: ... hose A Drain pan assy Drain hose B Installing pipe Set up the drain hose for a maximum rise 19 11 16 in 500 mm and give the drain pipe a down ward gradient of 1 25 to 1 100 Install the drain pipe so there is no rise trap or air bleed 59 1 16 to 78 3 4 in 1 5 to 2 m Max height 19 11 16 in 500 mm Supporter Rise Trap Air Bleeding Bad Bad Bad 7 2 Drain pump unit for ceiling 10 25 7 Optional parts ins...

Страница 878: ...5 585 Weight Net lb kg 8 3 5 Gross 12 5 5 Dimensions Unit in mm 22 7 16 570 Min 17 11 16 450 4 1 4 108 Ø3 15 16 100 1 3 4 45 10 1 8 257 7 15 16 201 22 7 16 570 26 7 8 683 15 3 8 390 4 3 4 120 5 7 8 to 7 7 8 150 to 200 12 15 16 328 15 11 16 398 12 3 16 310 Ceiling opening space Inspection hatch Top view Side view Side view NOTE When installing this kit inspection hatch is necessary It is necessary ...

Страница 879: ...essure of Fresh air intake kit Measurement position of shown in the graph Airlfow Pa 0 0 20 0 40 0 60 0 80 inWG CFM 0 50 100 150 200 m h Unit in mm 7 3 Fresh air intake kit for compact cassette type 10 27 7 Optional parts installation OPTIONAL PARTS OPTIONAL PARTS ...

Страница 880: ...ut voltage DC 12 2 V Permissible current 50 mA Indoor unit PCB CNB01 L Relay Fuse Power Fan other Locally purchased 1 2 3 4 5 6 L Make the distance from the PCB to the Relay unit within 82 ft 25 m Operation status Operation Stop 12 V 0 V Indoor unit fan External output Wire External output 3 Wire color Red Wire color White 1 2 3 4 5 6 7 3 Fresh air intake kit for compact cassette type 10 28 7 Opti...

Страница 881: ...tput 1 1 Chamber 1 Wire External output 2 1 Wire cover 1 Wire External output 3 1 Screw 4 Bolt 4 Extension wire for louver White Red 1 set Cable tie 1 Extension wire for receiver kit 1 7 3 Fresh air intake kit for compact cassette type 10 29 7 Optional parts installation OPTIONAL PARTS OPTIONAL PARTS ...

Страница 882: ...elow 32 F 0 C into the Fresh air intake kit The upper limit of the product s temperature range should respond to the outdoor temperature range About duct fan When installing the duct fan connect the drive relay locally purchased and operate with the indoor unit Ensure the intake air volume is below 10 of the product s air volume High When the intake air volume becomes too large there the operating...

Страница 883: ... in mm 9 7 16 to 9 21 32 240 to 245 Metal hanging fastener Ceiling Indoor unit Fresh air intake kit Installation of Fresh air intake kit CAUTION Installing the Fresh air intake kit with wrong direction is a cause of water leakage 1 Attach the Fresh air intake kit to the main body using the bolts provided as shown below Metal fittings Bolt 4 DRAIN PIPE DRAIN PIPE 7 3 Fresh air intake kit for compac...

Страница 884: ... fittings Ø3 15 16 in 100 mm When using the Insulation kit for high humidity UTZ KXGC first cut off and remove the heat insulation as shown in the figure Install the Insulation kit for high humidity according to the installation instruction sheet provid ed 3 1 8 80 1 3 16 30 Cut off Unit in mm 7 3 Fresh air intake kit for compact cassette type 10 32 7 Optional parts installation OPTIONAL PARTS OPT...

Страница 885: ...reme bends Highly repetitive bends Making the connecting duct diameters smaller Completion figure Band locally purchased Vinyl tape locally purchased Duct locally purchased Indoor unit Hanging band for duct locally purchased Fresh air intake kit NOTE When wiring of the duct fan is required refer to Fresh air control output on page 10 28 7 3 Fresh air intake kit for compact cassette type 10 33 7 Op...

Страница 886: ...ith the fasteners provided and insert into the hole of the Fresh air intake kit 3 Install the wire cover provided on the Fresh air intake kit 4 Install decoration panel according to the installation instruction sheet provided Metal fittings Screw 2 Cable tie Extension wire Connect 7 3 Fresh air intake kit for compact cassette type 10 34 7 Optional parts installation OPTIONAL PARTS OPTIONAL PARTS ...

Страница 887: ...ng duct locally purchased Air filter locally purchased Hood locally purchased Fresh air Case 2 Intake by duct fan Fresh air intake kit Outler air Room air Outler air Duct fan locally purchased Connecting duct locally purchased Air filter locally purchased Hood locally purchased Fresh air 7 3 Fresh air intake kit for compact cassette type 10 35 7 Optional parts installation OPTIONAL PARTS OPTIONAL ...

Страница 888: ...0 Weight Net lb kg 13 2 6 0 Gross 20 9 9 5 Dimensions Unit in mm 33 1 16 840 Inspection hatch 15 3 4 to 17 11 16 400 to 450 2 3 16 55 2 3 16 55 2 3 4 7 0 33 1 16 840 4 3 4 120 11 5 16 288 16 7 16 418 2 13 16 71 36 914 Ø3 15 16 100 Min 17 11 16 450 Inspection hatch Top view Side view Min 17 11 16 450 NOTE When installing this kit inspection hatch is necessary It is necessary when servicing Ei ther ...

Страница 889: ...39 3 8 1 000 Measurement position of shown in the graph For 2 way intake 39 3 8 1 000 For 1 way intake Measurement position of shown in the graph Unit in mm m h Pa 0 0 20 0 40 0 60 0 80 inWG 0 29 59 88 118 CFM 147 177 206 235 7 4 Fresh air intake kit for cassette type 10 37 7 Optional parts installation OPTIONAL PARTS OPTIONAL PARTS ...

Страница 890: ...Output voltage DC 12 2 V Permissible current 50 mA Indoor unit PCB CNB01 L Relay Fuse Power Fan other Locally purchased 1 2 3 4 5 6 L Make the distance from the PCB to the Relay unit within 82 ft 25 m Operation status Operation Stop 12 V 0 V Indoor unit fan External output Wire External output 3 Wire color Red Wire color White 1 2 3 4 5 6 7 4 Fresh air intake kit for cassette type 10 38 7 Optional...

Страница 891: ...tension wire for louver For UTZ VXGA White Red 1 set Screw 16 Extension wire for receiver kit For UTZ VXGA 1 Hook plate 2 set Wire External output 1 For Single split or Multi system 1 Shutter plate 1 Wire External output 2 For UTZ VXGA 1 Insulation 1 2 Wire External output 3 1 Insulation 2 1 Bolt 4 7 4 Fresh air intake kit for cassette type 10 39 7 Optional parts installation OPTIONAL PARTS OPTION...

Страница 892: ...of below 32 F 0 C into the Fresh air intake kit The upper limit of the product s temperature range should respond to the outdoor temperature range About duct fan When installing the duct fan connect the drive relay locally purchased and operate with the indoor unit Ensure the intake air volume is below 10 of the product s air volume High When the intake air volume becomes too large there the opera...

Страница 893: ...ealed plate to apply for different eye holes Apply insulation 1 to the installed duct flange parts Do not apply to sealed areas 2 1 2 1 3 screw 4 screw 4 9 13 16 13 16 0 in 250 20 0 mm Insulation 3 Overlap with each other Insulation 3 Insulation 1 Insulation 1 Insulation 3 Paste start position When pasting make sure that there is no gap between the insulation 2 overlap is allowed Cut the insulatio...

Страница 894: ...t be loosened before installing Screw Hook plate or Attached at UTZ VXGA Attached at UTZ VXRA 3 Install the cover a Remover the drain cover attached to the decorative panel and install onto the Fresh air intake kit Drain cover b Set the cover in position with screws 2 places as shown below Apply the Insulation 4 after installing the cover Screw 4 Screw 4 Insulation 4 Cover 3 16 to 6 16 in 5 10 mm ...

Страница 895: ...oad bearing Completion figure Duct locally purchased T shaped pipe locally purchased Fresh air intake kit Indoor unit Bands for duct use locally purchased NOTE When wiring of the duct fan is required refer to Fresh air control output on page 10 38 Installation of Cassette grille Pre installation preparations 1 Remove the control box cover 2 Remove the connector from the existing temperature sensor...

Страница 896: ...te board of the indoor unit Cassette type Circular flow cassette type CN8 White CN8 White 5 Insert the included extension cable for use with louver to the connector 6 When using the optical receiver unit option insert the included extension wire to the indoor unit 7 Close the control box cover when work is complete Installation procedure 1 After provisional fixing of a cassette grille feed the lou...

Страница 897: ...h air intake kit Outler air Room air Outler air Connecting duct locally purchased Air filter locally purchased Hood locally purchased Fresh air Case 2 Intake by duct fan Fresh air intake kit Outler air Room air Outler air Duct fan locally purchased Connecting duct locally purchased Air filter locally purchased Hood locally purchased Fresh air 7 4 Fresh air intake kit for cassette type 10 45 7 Opti...

Страница 898: ...7 3 0 7 8 3 5 Color White Louver motor Stepping motor Material Flame retardant ABS Accessories Attachment flame Operation range Cooling F C 64 to 90 18 to 32 RH 80 or less Heating F C 60 to 88 16 to 30 Dimension Models UTD GXSA W and UTD GXTA W Unit in mm 25 3 8 645 P7 7 8 3 23 5 16 P200 3 600 Burring hole Hole 4 Ø1 8 3 2 10 3 8 263 2 15 16 74 1 1 8 29 26 7 8 683 21 7 8 555 4 9 16 116 9 13 16 249 ...

Страница 899: ... Hole 2 Ø3 16 5 Burring hole 5 Ø1 8 3 2 18 1 4 463 2 15 16 74 1 1 8 29 1 1 8 29 3 5 16 84 2 15 16 74 1 3 8 35 3 8 9 1 5 8 42 Hole 2 Ø3 16 5 Accessories Part name Exterior Q ty Part name Exterior Q ty Installation manual 1 Screw A 3 8 in 10 mm 16 Operating manual 1 Screw B 3 8 in 10 mm 6 Grille 1 Cable clip 2 Bracket frame 1 Cable tie 3 Bushing 1 7 5 Auto louver grille kit 10 47 7 Optional parts in...

Страница 900: ...y cause condensation on the outlet port Near a wall surface It may cause condensation on the wall during cooling Area filled with mineral oil or containing a large amount of splashed oil or steam such as kitchen The place where it will be exposed to direct sunlight It may cause change in color When the installation area is exposed direct sunlight take measure to block the light such as cov ering t...

Страница 901: ...perating F C 32 to 114 8 0 to 46 Packaged F C 14 to 140 10 to 60 Humidity Packaged 0 to 95 RH No condensation Dimensions H W D in mm 2 9 16 8 7 65 203 178 Weight lb g 1 500 Dimensions This product is comprised of a body and cover Unit in mm 8 203 7 178 4 3 4 120 2 9 16 65 1 5 16 33 6 7 16 163 1 4 6 3 1 4 83 1 5 8 41 7 6 External power supply unit 10 49 7 Optional parts installation OPTIONAL PARTS ...

Страница 902: ... relay with the normally closed contact to external power supply unit 4 Connect the inner and relay power lines to the circuit breaker 5 Connect the power line of the power transformer primary side to the circuit breaker Electrical requirement The following items are necessary to install this product These items are not included with this product and must be purchased separately Name Q ty Descript...

Страница 903: ...the following indoor unit type Circular flow cassette type Compact floor type 2 It is used to connect to the following indoor unit type Floor Ceiling type Installation precautions This product can be installed in the following direction Prohibited To prevent water from entering through the cable do not install this product in the direction shown in the following figure 7 6 External power supply un...

Страница 904: ...d or other countries Intel is a trademark of Intel Corporation in the U S and or other countries Echelon LONWORKS and the Echelon logo are trademarks of Echelon Corporation registered in the United States and other coun tries BACnet is a registered trademark of the American Society of Heating Refrigeration and Air Conditioning Engineers ASHRAE Other company and product names mentioned herein may b...