En-2

2.  ABOUT THIS PRODUCT

2.1.  Precautions for using the R410A refrigerant

 WARNING

Do not introduce any substance other than the prescribed refrigerant into the refrigera-
tion cycle. 
If air enters the refrigeration cycle, the pressure in the refrigeration cycle will become 
abnormally high and cause the piping to rupture.

If there is a refrigerant leakage, make sure that it does not exceed the concentration 
limit. 
If a refrigerant leakage exceeds the concentration limit, it can lead to accidents such as 
oxygen starvation.

Do not touch refrigerant that has leaked from the refrigerant pipe connections or other 
area. Touching the refrigerant directly can cause frostbite.

If a refrigerant leakage occurs during operation, immediately vacate the premises and 
thoroughly ventilate the area. 
If the refrigerant comes in contact with a flame, it produces a toxic gas.

2.2.  Special tool for R410A

 

WARNING

To install a unit that uses the R410A refrigerant, use dedicated tools and piping materi-
als that have been manufactured specifically for R410A use. 
Because the pressure of the R410A refrigerant is approximately 1.6 times higher than 
the R22, failure to use dedicated piping material or improper installation can cause 
rupture or injury. 
Furthermore, it can cause serious accidents such as water leakage, electric shock, or 
fire.

Tool name

Contents of change

Gauge manifold

Pressure is huge and cannot be measured with a conventional (R22) 
gauge. To prevent erroneous mixing of other refrigerants, the diam-
eter of each port has been changed.
It is recommended to use a gauge manifold with a high pressure 
display range 500 microns to 768 psi (–0.1 to 5.3 MPa) and a low 
pressure display range 500 microns to 551 psi (–0.1 to 3.8 MPa).

Charging hose

To increase pressure resistance, the hose material and base size 
were changed.

Vacuum pump

A conventional (R22) vacuum pump can be used by installing a 
vacuum pump adapter.
Be sure that the pump oil does not backflow into the system. Use 
one capable for vacuum suction of 500 microns (–100.7 kPa).

Gas leakage 
detector

Special gas leakage detector for HFC refrigerant R410A.

2.3.  Accessories

 WARNING

For installation purposes, be sure to use the parts supplied by the manufacturer or other 
prescribed parts. 
The use of non-prescribed parts can cause serious accidents such as the unit to fall, 
water leakage, electric shock, or fire.

The following installation parts are furnished. Use them as required.

Keep the Installation Manual in a safe place and do not discard any other accessories 
until the installation work has been completed.

Do not discard any accessories needed for installation until the installation work has been 
completed.

Name and Shape

Q’ty

Application

Operating manual

1

Installation manual

1

(This book)

Cable tie (large)

4

For fixing the connection pipe 
(large and small)

Cable tie (medium)

2

For transmission and remote 
controller cable binding.

Coupler heat 
insulation (small)

1

For indoor side pipe joint (small)

Name and Shape

Q’ty

Application

Coupler heat 
insulation (large)

1

For indoor side pipe joint (large)

Special nut A (large 
flange)

4

For installing indoor unit

Special nut B 
(small flange)

4

For installing indoor unit

Template 
(carton top)

1

For ceiling openings cutting 
Also used as packing

Drain hose

1

For installing drain pipe
(Ø 3/4 in [I.D.]; Ø 1-1/16 in [O.D.])

Hose band

1

For installing drain hose

Drain hose 
insulation

1

For installing drain hose

Cassette grille accessories

Name and Shape

Q’ty

Application

Connector cover

1

For covering connector

Tapping screw
(M5 × 12mm)

4

For mounting cassette grille

Tapping screw 
(M4 × 12mm)

1

For mounting connector cover

2.4.  Optional parts

Description

Model

Application

Air outlet shutter plate UTR-YDZB

Install the plate at outlet when carrying out 
3-way direction operation.

Insulation kit for high 
humidity

UTZ-KXGC

Install when the condition under the roof is 
over 80% in humidity and over 86 °F (30 °C) 
in temperature.

Fresh air intake kit

UTZ-VXAA

To take fresh air.

External connect kit

UTY-XWZXZC

For output function
(Output terminal / CNB01)

UTY-XWZXZB

For control input function
(Apply voltage terminal / CNA01)

UTY-XWZXZD

For control input function
(Dry contact terminal / CNA02)

UTY-XWZXZ7

For forced thermostat off function
(Apply voltage terminal / CNA03)

UTY-XWZXZE

For forced thermostat off function
(Dry contact terminal / CNA04)

Wireless LAN adapter UTY-TFSXZ*

For wireless LAN control.

MODBUS® convertor UTY-VMSX

For connecting a single indoor unit system to 
the Modbus® network.

External power sup-

ply unit

UTZ-GXXA

Supply power to the indoor unit PCB when 
the indoor unit is turned off to prevent errors.

2.5.  About unit of the length

This product is manufactured to metric units and tolerances. United States customary 
units are provided for reference only. In cases where exact dimensions and tolerances are 
required, always refer to metric units.

9371022659-02_L3.indb   Sec1:2

9371022659-02_L3.indb   Sec1:2

9/24/2019   11:10:54 AM

9/24/2019   11:10:54 AM

Содержание AirStage AUUA12TLAV2

Страница 1: ... AUUA7TLAV2 AUUA9TLAV2 AUUA12TLAV2 AUUA14TLAV2 AUUA18TLAV2 AUUA24TLAV2 INSTALLATION MANUAL For authorized service personnel only MANUEL D INSTALLATION MANUAL DE INSTALACIÓN Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado 9371022659 02_L3 indb 1 9371022659 02_L3 indb 1 9 24 2019 11 10 53 AM 9 24 2019 11 10 53 AM ...

Страница 2: ...s and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct operation to the customer using the operating manual DANGER Never touch electrical components immediately after the power supply has been turned off Electrical shock may occur After ...

Страница 3: ...following installation parts are furnished Use them as required Keep the Installation Manual in a safe place and do not discard any other accessories until the installation work has been completed Do not discard any accessories needed for installation until the installation work has been completed Name and Shape Q ty Application Operating manual 1 Installation manual 1 This book Cable tie large 4 ...

Страница 4: ... where the drain pipe can be easily installed 8 Install the unit where noise and vibrations are not amplified 9 Take servicing etc into consideration and leave the spaces Also install the unit where the filter can be removed 3 2 Installation dimensions Leave the space specified in Fig A so that the air from the blower will cover the entire room Install the indoor unit on a place having a sufficien...

Страница 5: ...o choose adequate materials Thicknesses of copper pipes used with R410A are as shown in the table Never use copper pipes thinner than those indicated in the table even if they are avail able on the market Thicknesses of Annealed Copper Pipes R410A Pipe outside diameter in mm Thickness in mm 1 4 6 35 0 032 0 80 3 8 9 52 0 032 0 80 1 2 12 70 0 032 0 80 5 8 15 88 0 039 1 00 3 4 19 05 0 039 1 20 4 2 P...

Страница 6: ... side After installing the coupler heat insula tion wrap both end with vinyl tape so that there is no gap After affixing the coupler heat insula tion secure it with 2 cable ties large one on each end of the insulation Make sure that the cable ties overlap the heat insulation pipe Coupler heat insulation accessories Cable tie large accessories Heat insulation Heat insu lation Cover this portion wit...

Страница 7: ...ic parts Securely connect the connection cables to the terminal board In addition secure the cables with wiring holders Improper connections either in the wiring or at the ends of the wiring can cause a malfunction electric shock or fire Always fasten the outside covering of the connection cable with the cable clamp If the insulator is chafed electric discharge may occur We suggest installing GFEB...

Страница 8: ...6 3 1 Power supply cable Adjust the length of power supply cable to avoid excessive tension with referring figure below Conduit connector Earth Ground wire 2 3 4 in 70 mm 1 3 4 in 45 mm A For solid core wiring 1 To connect the electrical terminal follow the below diagram and connect after looping it around the end of the cable 2 Use the specified cables connect them securely and fasten them so tha...

Страница 9: ...and install each connection cable Screw Control box cover 2 Connect the connection cable with the cable tie Conduit connector L1 L2 N Power supply cable Y1 Y2 Remote controller cable Cable tie medium accessories X1 X2 Transmission cable Attach the conduit connector Lock nut Earth Ground 3 Install control box cover 4 Fix the conduit with the supporters as shown below Conduit power supply cable Supp...

Страница 10: ...ad resistance DC power supply 12 to 24 V Connected unit P C B 1 Make the power supply DC 12 to 24 V Select a power supply capacity with an ample surplus for the connected load Do not impress a voltage exceeding 24 V across pins 1 2 and 1 3 a The allowable current is DC 5 mA to 10 mA Recommended DC 5 mA Provide a load resistance such that the current becomes DC 10 mA or less Select very low current...

Страница 11: ... For the fan setting details see the Design Technical Manual ON ON 7 FIELD SETTING There are 3 methods for address setting by FIELD SETTING as follows Set by either of the methods Each setting method is described 1 to 3 below 1 IU AD REF AD SW settings This section 7 1 Setting the address 2 Remote controller settings Refer to the wired or wireless remote controller manual for detailed setting info...

Страница 12: ...mote controller Code change Indoor unit Remote controller Confusion A B C D A B C D Custom code setting for indoor unit Set the DIP switch SET3 SW1 2 referring to the figure and table below IU AD REF AD RC AD 10 1 10 1 SET3 SET4 DIP switch SET3 SW 1 SW 2 SW 3 SW 4 ON OFF DIP switch SET3 DIP switch SET3 Custom code A Factory setting B C D SW1 OFF ON OFF ON SW2 OFF OFF ON ON 7 3 Function setting FUN...

Страница 13: ...03 30 seconds External heater use in defrost ing 4 75 00 Disable Enables or disables the external heater use in defrosting 01 Enable 1 Auto restart is an emergency function such as for power failure etc Do not start and stop the indoor unit by this function in normal operation Be sure to operate by the control unit converter or external input device 2 Inappropriate setting may cause an external de...

Страница 14: ...n address 00 to 99 For use with a remote controller set all rotary switches to 0 and refer to 7 1 Setting the address for details All switches are set to 0 at the factory 2 Others Indication pattern Indicator Name Indication pattern OPERATION indicator lamp Green Function number tens place 0 5s ON 0 5s OFF TIMER indicator lamp Orange Function number ones place 0 5s ON 0 5s OFF FILTER indicator lam...

Страница 15: ...t and stop air conditioner op eration by remote control unit or external device No operation After installation is completed has the proper operation and handling been explained to the user 11 ERROR CODES If you use a wired type remote controller error codes will appear on the remote controller display If you use a wireless remote controller the lamp on the photodetector unit will output error cod...

Отзывы: