En-2

 CAUTION

This mark indicates procedures which, if improperly per-
formed, might possibly result in personal harm to the user, or 
damage to property.

This unit must be installed by qualified personnel with a capacity certificate for handling 
refrigerant fluids. Refer to regulation and laws in use on installation place.

The installation must be carried out in compliance with regulations in force in the place 
of installation and the installation instructions of the manufacturer.

This unit is part of a set constituting an air conditioner. It must not be installed alone or 
with non-authorized by the manufacturer.

This unit contains no user-serviceable parts. Always consult authorized service person-
nel to repairs.

When moving, consult authorized service personnel for disconnection and installation 
of the unit.

Be sure to use a dedicated power circuit. 
Never use a power supply shared by another appliance.

This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc 
is greater than or equal to 2.832 MVA at the interface point between the user's supply 
and the public system. It is the responsibility of the installer or user of the equipment 
to ensure, by consultation with the distribution network operator if necessary, that the 
equipment is connected only to a supply with a short-circuit power Ssc than or equal to 
2.832 MVA.

Do not install the unit in the following areas:
• For the installation conditions if installing in an area of high salt damage such as the 

coast, follow the Design & Technical Manual.

• Area filled with mineral oil or containing a large amount of splashed oil or steam, such 

as a kitchen. 
It will deteriorate plastic parts, causing the parts to fall or the unit to leak water. 

• Area that generates substances that adversely affect the equipment, such as sulfuric 

gas, chlorine gas, acid, or alkali. 
It will cause the copper pipes and brazed joints to corrode, which can cause refriger-
ant leakage.

• Area containing equipment that generates electromagnetic interference. 

It will cause the control system to malfunction, preventing the unit from operating 
normally.

• Area that can cause combustible gas to leak, contains suspended carbon fibers or 

flammable dust, or volatile inflammables such as paint thinner or gasoline. 
If gas leaks and settles around the unit, it can cause a fire.

• Avoid installing the unit at places where it will come into contact with animals’ urine or 

ammonia.

The units are not explosion proof and therefore should not be installed in explosive 
atmosphere.

Do not use the unit for special purposes, such as storing food, raising animals, growing 
plants, or preserving precision devices or art objects. It can degrade the quality of the 
preserved or stored objects.

Ground the unit. Do not connect the ground cable to a gas pipe, water pipe, lightning 
rod, or a telephone ground cable. Improper grounding may cause electric shock.

Perform draining for the unit according to the Installation manual. Check that the water 
is properly drained.
If the drain processing is improperly installed, water may drip down from the unit, wet-
ting the furniture.

Do not touch the fins with bare hands.

Be sure not to start or stop the operation of air conditioning with power breaker. Other-
wise, it may cause malfunction or water leakage.

When setting it up near the equipment that generates electromagnetic waves and the 
equipment that generates the higher harmonics wave, be sure to take measures against 
noise. Otherwise, it may cause malfunction or failure.

When energizing to the crankcase heater, please turn on the power 12 hours or earlier 
before operation begins. When the energizing time is short, it may cause failure. Be-
sides, please do not turn off power during the busy season.

This appliance is not intended for use by persons (including children) with reduced 
physical, sensory or mental capabilities, or lack of experience and knowledge, unless 
they have been given supervision or instruction concerning use of the appliance by a 
person responsible for their safety. Children should be supervised to ensure that they 
do not play with the appliance.

2.  ABOUT THIS PRODUCT

2.1.  Precautions for using R410A refrigerant

Pay careful attention to the following points:

Since the working pressure is 1.6 times higher than that of R22 models, some of the 
piping and installation and service tools are special. (See the table in the SPECIAL 
TOOLS FOR R410A section.)
Especially, when replacing a conventional refrigerant (other than R410A) model with 
a new refrigerant R410A model, always replace the conventional piping and flare nuts 
with the R410A piping and flare nuts.

Models that use refrigerant R410A have a different charging port thread diameter to pre-
vent erroneous charging with R22, R407C and for safety. Therefore, check beforehand. 
[The charging port thread diameter for R410A is 1/2 UNF 20 threads per inch.]

Be more careful than the installation of the refrigerant (other than R410A) models, not 
to enter foreign matters (oil, water, etc.) and other refrigerant into the piping. Also, when 
storing the piping, securely seal the openings by pinching, taping, etc.

When charging the refrigerant, take into account the slight change in the composition 
of the gas and liquid phases, and always charge from the liquid phase side whose 
composition is stable.

2.2.  Special tools for R410A

Tool name

Contents of change for R22 tool

Gauge manifold

Pressure is huge and cannot be measured with a conven-
tional gauge. To prevent erroneous mixing of other refriger-
ants, the diameter of each port has been changed.
It is recommended to use a gauge manifold with a high 
pressure display range -0.1 to 5.3 MPa and a low pressure 
display range -0.1 to 3.8 MPa.

Charging hose

To increase pressure resistance, the hose material and base 
size were changed.

Vacuum pump

A conventional vacuum pump can be used by installing a 
vacuum pump adapter.
• A conventional vacuum pump can be used by installing a 

vacuum pump adapter. 

• Be sure that the pump oil does not back flow into the 

system. Use one capable for vacuum suction of -100.7kPa 
(5 Ton, -755mmHg).

Gas leakage detector

Special gas leakage detector for HFC refrigerant R410A.

2.3. Accessories

Use connecting parts as required.
Do not throw away the connecting parts until the installation has been complete.

Name and shape

Q’ty

Application

Specifications 
manual

1

Installation manual

1

(This manual)

Drain cap

9

For outdoor unit drain piping work

Drain pipe

1

For outdoor unit drain piping work

Joint pipe A-L

1

For connecting gas pipe 
(L type)

Joint pipe B-L

1

For connecting gas pipe 
(Straight type)

Push mount cable tie

2

For binding transmission cable

Grommet edging

2

For power supply cable and con-
nection cable installation.
Attach to the knockout hole.

9380545248-02_IM.indb   2

9380545248-02_IM.indb   2

2018/1/24   9:36:30

2018/1/24   9:36:30

Содержание AIRSTAGE AJH126LELAH

Страница 1: ...Й МОДУЛЬ For authorized service personnel only Только для авторизованного обслуживающего персонала PART No 9380545248 02 AJY126LELAH AJY144LELAH AJH126LELAH AJH144LELAH Original instructions 9380545248 02_IM indb i 9380545248 02_IM indb i 2018 1 24 9 36 29 2018 1 24 9 36 29 ...

Страница 2: ...stall the electrical box cover on the unit An improperly installed electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Do not turn ON the power until all work has been completed Turning ON the power before the work is completed can cause serious accidents such as electric shock or fire After the installation make sure there is no refrig...

Страница 3: ... near the equipment that generates electromagnetic waves and the equipment that generates the higher harmonics wave be sure to take measures against noise Otherwise it may cause malfunction or failure When energizing to the crankcase heater please turn on the power 12 hours or earlier before operation begins When the energizing time is short it may cause failure Be sides please do not turn off pow...

Страница 4: ... 1 meter away from a television or radio The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping of the indoor and outdoor units within the allowable range For maintenance purposes do not bury the piping 3 2 Drain processing CAUTION Perform ...

Страница 5: ... more 500 or more 600 or more 1500 or more 3000 or more 3 4 Transporting the unit WARNING Do not touch the fins Otherwise personal injury could result CAUTION When carrying the unit hold the handles on the right and left sides and be careful If the outdoor unit is carried from the bottom hands or fingers may be pinched Hoisting method When hoisting the outdoor unit hook the rope on the outside of ...

Страница 6: ...ordance with local rules 1 Allowable tensile stress 33 N mm2 2 Allowable tensile stress 61 N mm2 3 Endurance pressure of the pipes 4 2MPa 3 5 Installing the unit Please install the outdoor unit without slant within 0 3 degrees Install 4 anchor bolts at the locations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base su...

Страница 7: ...n 1 month Pinch or tape pipes Indoor Pinch or tape pipes Protect the pipes to prevent the entry of moisture and dust Especially pay attention when passing the pipes through a hole or connecting the end of a pipe to the outdoor unit 5 PIPE INSTALLATION 5 1 Brazing CAUTION If air or another type of refrigerant enters the refrigera tion cycle the internal pressure in the refrigeration cycle will beco...

Страница 8: ...Opening 1 Insert the hexagon wrench into the valve shaft and turn it counterclock wise 2 Stop turning when the valve shaft can no longer be turned Open position Closing 1 Insert the hexagon wrench into the valve shaft and turn it clockwise 2 Stop turning when the valve shaft can no longer be turned Closed position Opening direction Hexagon wrench Seal blank cap installation portion Liquid pipe Gas...

Страница 9: ...ot exposed to high temperatures If the temperature surrounding the breaker is too high the amperage at which the breaker cuts out may decrease Use a breaker Included with earth leakage circuit breaker that is capable of handling high frequencies Because the outdoor unit is inverter controlled a high frequency earth leakage circuit breaker is necessary to prevent a malfunction of the breaker itself...

Страница 10: ...door unit Indoor unit Signal Amplifier System Controller Touch Panel Controller Transmission line Terminal resistor Terminal resistor NS 1 NS 2 NOTES Do not use loop wiring This may lead to parts damage and erroneous operation 6 4 3 Enabling Disabling automatic address setting You can enable disable automatic address setting for the indoor unit and the signal ampli fier To enable automatic address...

Страница 11: ...e shielded wire of the transmission cable to the earth ground terminal of the equipment or to the earth ground screw near the terminal Be sure to use one side of a twisted pair cable when using transmission cable with 2 sets of twisted pair cables Wind with insulation tape to prevent short circuit Use one side of the twisted pair cable Connect both ends of shielded wire to earth Ground 6 6 Externa...

Страница 12: ...heater Output signal ON when the outdoor temperature goes down below 2 C and signal OFF at the outdoor temperature 4 C Voltage power supply input voltage cable 0 82 mm2 18AWG P C B Base heater 9 CN115 Black 8 8 Connect to pin 1 and pin 3 No connection pin 2 and pin 4 9 The allowable current is 1 A or less 7 FIELD SETTING CAUTION Discharge the static electricity from your body before setting up the...

Страница 13: ... 9999 7 3 Rotary switch setting The rotary switch REF AD sets the refrigerant circuit address of the outdoor unit Config ure the settings only on the master unit of a refrigerant system If multiple refrigerant systems are connected set the rotary switch REF AD as shown in the table below Refrigerant circuit address Rotary Switch Setting Setting Setting range Type of switch REF AD 10 1 Refrigerant ...

Страница 14: ...r unit on the network Refer to Fig Wiring example for automatic address setting 7 6 1 chapter for the wiring example For manual setting of address refer to the signal amplifier installation manual 7 5 2 Automatic address setting for signal amplifiers When setting the address of the signal amplifier please use the factory setting See the installation manual of the signal amplifier When the system i...

Страница 15: ... to 101 kgf cm 18 0 to 22 0 N m 184 to 224 kgf cm 11 4 to 14 0 N m 116 to 143 kgf cm Gas valve 27 0 to 33 0 N m 275 to 337 kgf cm 22 5 to 27 5 N m 229 to 280 kgf cm 8 1 Sealing test CAUTION Use only nitrogen gas Never use refrigerant gas oxygen in flammable gas or poisonous gas to pressurize the system If oxygen is used there is the danger of an explosion Do not apply shock during sealing test It ...

Страница 16: ... values specified in the Table A To open and close the valves use a specified hexagon wrench 8 3 2 Checking total amount of refrigerant and calculating the amount of refrigerant charge to be added The amount of refrigerant charge to be added is the total value of the basic refrigerant charge amount and the value calculated from the length of the liquid pipe Round up the value to 2 decimal places M...

Страница 17: ...acity error E221 and Indoor unit duplicate address error E261 occurred 1 When the address of the overlap indoor unit is displayed press and hold the ENTER button for more than 3 seconds 2 When errors other than the address of the overlap indoor unit exist press SELECT but ton to switch to the next error If error occurs it will display Ad address number 9 2 Pre check for test run Before the test op...

Страница 18: ... action E 9 8 9 Outdoor unit fan motor 2 driver error E 9 A 1 Outdoor unit coil 1 expansion valve 1 error E 9 A 2 Outdoor unit coil 2 expansion valve 2 error Refrigerant system error E A 1 1 Outdoor unit discharge temperature 1 error perma nent stop E A 3 1 Outdoor unit compressor 1 temperature error E A 4 1 Outdoor unit high pressure error E A 4 2 Outdoor unit high pressure protective action 1 E ...

Страница 19: ...g condition refer to item 15 8 Max Current Maximum electric current Test condition IEC60335 2 40 9 Refrigerant Refrigerant type and initial charging amount 10 Max pressure HP LP Means pressure of High Pressure side Low Pres sure side 11 Protection Protection level against dust and water 12 Condition of cooling heating Dry bulb temperature and wet bulb temperature under standard cooling heating con...

Отзывы: