Fujitsu AIRSTAGE AJH072LALBH Скачать руководство пользователя страница 22

En-21

7. 7.   Resistance measurement of transmission cable 

(Measure with breaker OFF)

CAUTION

Do not turn on the power if the resistance between the terminals of the transmis-
sion cable is abnormal. Otherwise, the circuit board may be damaged.

Measure the resistance between 2 terminals of a transmission cable.

(1)  Transmission cable connecting indoor units, outdoor units, and signal 

ampli

fi

 ers

Measure the resistance of the signal ampli

fi

 er terminal and the terminal of the 

indoor and outdoor units connected farthest away from the device where terminal 
resistor is measured.
A value from the table is displayed, depending on the distance from the signal 
ampli

fi

 er and the device where the terminal resistor is set.

This value is an estimate.

(2)  Transmission cable connecting outdoor units in a refrigerant system

The resistance between the terminals of the transmission cable is 45-60

Ω

.

This value is an estimate.

Distance from termination resistor (m)

0 ~100

~ 200

~ 300

~400

~500

Approximate resistance (

Ω

)

0 ~ 50

A short circuit somewhere or 2 or more termination 
resistors are connected

50
60
70
80
90

100

110

120
130
140
150
160
170
180

190 ~

Faulty contact or wiring length over 500 m

1K ~

Faulty contact, open circuit, or no termination resistor

8.  PIPE INSTALLATION II

Fig. A  Connection  system

 A)  In case of connecting 1 outdoor unit

Outdoor unit

Pressure gauge

Vaccum 

pump

Scale

Pressure regulating 

valve

Nitrogen

Indoor 

unit

Indoor 

unit

 B)  In case of connecting multiple outdoor units

Pressure regulating valve

Pressure gauge

Outdoor unit

Outdoor unit

Nitrogen

Scale

Vaccum 

pump

Indoor 

unit

Indoor 

unit

Fig. B

Charging cap

Valve

Cap

Close

Hexagon 

wrench

Close

Open

Open

Spindle

Table. A

Valve type

Spindle

Cap

Charging cap

Liquid

9.0 to 12.0 N·m 
(90 to 120 kgf·cm)

20.0 to 24.0 N·m 
(200 to 240 kgf·cm)

12.5 to 16.0 N·m 
(125 to 160 kgf·cm)

Gas

27.0 to 33.0 N·m 
(270 to 330 kgf·cm)

25.0 to 30.0 N·m 
(250 to 300 kgf·cm)

12.5 to 16.0 N·m 
(125 to 160 kgf·cm)

8. 1.  Sealing test

CAUTION

•  Use only nitrogen gas.

Never use refrigerant gas, oxygen, in 

fl

 ammable gas or poisonous gas to pressur-

ize the system. (If oxygen is used. There is danger of an explosion.)

•  Do not shock during sealing test.

It can rupture the pipes and cause serious injury.

•  Do not turn on the power unless all operations are complete.

•  Do not block the walls and the ceiling until the sealing test and charging of the 

refrigerant gas have been completed.

After connecting the pipes, perform a sealing test.
Recheck that the spindle of the 3-way valve are closed before performing a sealing 
test. (Fig. B)
Pour nitrogen gas through both the liquid pipe and the gas pipe.
Pressurize nitrogen gas to 4.2 MPa to perform the sealing test.

Check all 

fl

 are connection areas and brazed areas.

Then, check that the pressure has not decreased.
Compare the pressures after pressurizing and letting it stand for 24 hours, and check 
that the pressure did not decreased.

*  When the outdoor temperature changes 5 °C, the test pressure changes 0.05 

MPa.
If the pressure has dropped, the pipe joints may be leaking.

If a leakage is found, immediately repair it and perform a sealing test again.

* Decrease the pressure of nitrogen gas before brazing

After completing the sealing test, release the nitrogen gas from both valves.
Release the nitrogen gas slowly.

8. 2.  Vacuum process

CAUTION

Do not turn on the power unless all operations are complete.

If the system is not evacuated properly, its performance will drop.

•  If moisture enter the piping, follow below. (i.e., if doing work during the rainy 

season, if the actual work takes long enough that condensation may form on the 
inside of the pipes, if rain might enter the pipes during work, etc.)

• After 

operating 

the 

vacuum 

pump 

for 

hours, pressurize to 0.05 MPa (i.e., 

vacuum breakdown) with nitrogen gas, then depressurize down to -100.7kPa 
(-755mmHg) for an hour using the vacuum pump (vacuum process).

•  If the pressure does not reach -100.7kPa (-755mmHg) even after depressurizing 

for at least 2 hours, repeat the vacuum breakdown - vacuum process.

After vacuum process, maintain the vacuum for an hour and make sure the pres-
sure does not rise by monitoring with a vacuum gauge.

Evacuation procedure

 1)  Remove the caps of the gas pipe and liquid pipe and check that the valves are 

closed.

 2)  Remove the charging cap.

 3)  Connect a vacuum pump and a pressure gauge to a charging hose and connect 

it to the charging port.

 4)  Activate the vacuum pump and vacuum the indoor unit and connection piping 

until the pressure gauge becomes -100.7kPa (-755mmHg).

Evacuate from both the gas pipe and the liquid pipe.

 5)  Continue evacuating the system for 1 hour after the pressure gauge reads 

-100.7kPa (-755mmHg).

 6)  Remove the charging hose and reinstall the charging cap.

9378945180-02_IM.indb   21

9378945180-02_IM.indb   21

2014/11/10   19:39:58

2014/11/10   19:39:58

Содержание AIRSTAGE AJH072LALBH

Страница 1: ...service personnel only INSTALLATIONSANLEITUNG Nur für autorisiertes Fachpersonal MANUEL D INSTALLATION MANUAL DE INSTALACIÓN Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado MANUALE DI INSTALLAZIONE A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO Apenas para técnicos autoriza...

Страница 2: ...ll create a hazardous gas Electrical work must be performed in accordance with this Installation manual by a person certified under the national or regional regulations Be sure to use a dedi cated circuit for the unit An insufficient power supply circuit or improperly performed electrical work can cause serious accidents such as electric shock or fire For wiring use the prescribed type of cables c...

Страница 3: ...n R410A model with a new refrigerant R410A model always replace the conventional piping and flare nuts with the R410A piping and flare nuts Models that use refrigerant R410A have a different charging port thread diameter to prevent erroneous charging with R22 R407C and for safety Therefore check beforehand The charging port thread diameter for R410A is 1 2 UNF 20 threads per inch Be more careful t...

Страница 4: ...ems even if the drain water is discharged from the unit Otherwise provide drainage that would not affect people or objects Install the unit in an area that has no heat sources vapors or the risk of the leakage of flammable gas in the vicinity Install the unit in an area that is away from the exhaust or vent ports that discharge vapor soot dust or debris Install the indoor unit outdoor unit power s...

Страница 5: ...s L5 200 mm When H5 is 500 mm or more L5 200 h5 2 mm Fig 4 h3 1500 L3 L4 500 h4 H3 H4 Side view Front Rear Wall Wall Fig 5 L5 L5 500 h5 500 h5 H5 H5 Front view Wall Wall Fig 6 Top view 800mm or more 800mm or more 20mm or more 20mm or more L4 L3 L5 L5 Fig 7 Top view 500mm or more 1000mm or more 20mm or more 20mm or more L4 L3 L5 L5 3 3 2 When install near unlimited height wall 1 Single and multiple...

Страница 6: ...ce that includes the discharge duct resistance the other additional resistance like discharge grill and so on 2 Refer to the section on Push Switch Setting in Chapter 7 Field Setting 3 4 Transportation the outdoor unit Product mass kg AJ 072LALBH 252 AJ 090LALBH 252 AJ 108LALBH 275 AJ 126LALBH 275 AJ 144LALBH 275 AJ 162LALBH 275 Hoisting method When hanging the outdoor unit and conveying it to ins...

Страница 7: ...it on the refrigerant pipe as the master unit When connecting multiple outdoor units install the outdoor unit with the largest nominal system capacity nearest to the indoor unit on the refrigerant pipe fol lowed by those with less nominal system capacities Capacity Master Slave Always keep to the limit on the total amount of refrigerant Exceeding the limit on the total amount of refrigerant when c...

Страница 8: ...3300 C1220T H or equivalent 1 Allowable tensile stress 33 N mm2 2 Allowable tensile stress 61 N mm2 3 Endurance pressure of the pipes 4 2MPa Please select the pipe size in accordance with local rules Table A1 Between outdoor unit and outdoor unit branch kit HP Outdoor unit cooling capacity kW Outside diameter mm Branch kit 4 Liquid pipe Gas pipe 8 22 4 12 70 1 2 22 22 7 8 UTP CX567A 10 28 0 12 70 ...

Страница 9: ...capacity kW Outside diameter mm Liquid pipe Gas pipe 8 22 4 12 70 1 2 9 52 3 8 22 22 7 8 19 05 3 4 10 28 0 12 70 1 2 9 52 3 8 22 22 7 8 12 33 5 12 70 1 2 28 58 1 1 8 14 40 0 12 70 1 2 28 58 1 1 8 16 45 0 12 70 1 2 28 58 1 1 8 18 50 0 15 88 5 8 28 58 1 1 8 B between outdoor unit branch kits or outdoor unit branch kit and first separation tube Allowable pipe length actual pipe length Between master ...

Страница 10: ...hand or more If a pipe is brazed without applying nitrogen gas it will create an oxidation film This can degrade performance or damage the parts in the unit such as the com pressor or valves Do not use flux to braze pipes If the flux is the chlorine type it will cause the pipes to corrode In addition if the flux contains fluoride it will affect the refrigerant piping system due to deterioration of...

Страница 11: ...d the pipe at a radius of 70mm or greater Do not bent pipe many times at same part to prevent break After completing all the pipe connection by brazing perform the indoor unit pipe con nection with a flare joint When removing the pinch pipe or brazing the joint pipe carry out the work while cooling down the 3 way valve sufficiently Braze the joint pipe onto the 3 way valves at the liquid and gas s...

Страница 12: ...kit 0 to 26 mm 0 to 26 mm 4 For details refer to the Installation Instruction Sheet of the outdoor unit branch kit Fig Examples of multiple unit installation Example 1 Master unit Slave unit1 Slave unit2 Example 3 Master unit Slave unit1 Slave unit2 Example 2 Master unit Slave unit1 Slave unit2 CAUTION To prevent the oil from settling in the stopped unit install the pipes between the outdoor units...

Страница 13: ...sure the power supply is OFF Be sure to install an earth ground leakage breaker Otherwise it will cause electric shock or fire Be sure to install a breaker of the specified capacity When selecting breaker please comply with the laws and the regulations of each country One breaker must be installed on the power supply of the outdoor unit Wrong selection and setup of the breaker will cause electric ...

Страница 14: ...e values are recommended data 2 Specification Use conformed cord with Type 60245 IEC66 3 Max wire length Set a length so that the voltage drop is less than 2 Increase the wire diameter when the wire length is long Fig In case of connected outdoor unit GOOD Transmission cable Remote controller cable Breaker 400 V 3ø 50 Hz Breaker 230 V 1ø 50 Hz Outdoor unit Power supply cable Indoor unit Power supp...

Страница 15: ... refrigerant system Example Disable Automatic Address setting Refrigerant system 1 Refrigerant system 2 Refrigerant system 3 Transmission line Transmission line Transmission line Example Enable Automatic Address setting Refrigerant system 1 Refrigerant system 2 Refrigerant system 3 Transmission line Transmission line Transmission line 6 6 Wiring procedure Remove the cover of the electrical compart...

Страница 16: ...insulation tape to prevent short circuit Use one side of the twisted pair cable Connect both ends of sealed cable to earth Be sure to use one side of a twisted pair cable when using transmission cable with 2 sets of twisted pair cables RB IN Cable clip Cable tie Accessory 40 mm or more 8 to 10 mm 6 7 External input and external output 6 7 1 Terminal position Input 5 CN135 ORANGE Outdoor unit PC bo...

Страница 17: ...d indoor unit s Normal or Error status Operation status Master unit only This output indicates the outdoor unit s Operation status Connector Output voltage Status CN136 Black 0 V Normal DC 12 to 24 V Error CN137 Blue 0 V Stop DC 12 to 24 V Operation 1 2 5 6 7 P C B CN136 Black or CN137 Blue DC power supply External 12 to 24 V Connected load Operation Indicator or Error Indicator connected unit 5 P...

Страница 18: ... When setting the terminal resistor of a signal amplifier refer to the installation manual of the signal amplifier When setting multiple terminal resistors take note of the following items 1 How many network segments are there in a VRF system 2 Where will you set the terminal resistors in a network segment Condition for 1 segment Total number of outdoor and indoor units and signal amplifiers is le...

Страница 19: ...iven to administrative indoor unit Priority is given to the operation mode of the administrative indoor unit which is set by the wired remote control ler 22 Snow falling protection fan mode 1 Valid 2 2 0 0 Invalid 0 1 This mode operates the fans of outdoor units in order to prevent the units from stop ping operation when they are covered by snow 23 Interval setting for snow falling protection fan ...

Страница 20: ...ODE LED101 GREEN MODE EXIT SELECT ENTER SW107 SW108 SW109 LED102 RED 2 Setting method Use the MODE EXIT SELECT and ENTER buttons to configure settings accord ing to the procedures below If no setting is made the factory default setting will be displayed Press the MODE EXIT button Press the SELECT button Press the ENTER button Press the ENTER button for more than 3 seconds MODE EXIT SELECT ENTER EN...

Страница 21: ...or unit wiring example Connect the indoor and outdoor units of the same refrigerant system as shown below 2 12 8 21 4 1 26 3 3 1 4 25 6 8 17 11 28 12 18 1 10 23 4 22 8 9 2 3 4 Refrigerant system1 Refrigerant system2 Refrigerant system3 Master unit Master unit Master unit 1 Signal amplifier 1 Signal amplifier NOTE The automatic address function can be used for a maximum of 64 indoor units installed...

Страница 22: ...the walls and the ceiling until the sealing test and charging of the refrigerant gas have been completed After connecting the pipes perform a sealing test Recheck that the spindle of the 3 way valve are closed before performing a sealing test Fig B Pour nitrogen gas through both the liquid pipe and the gas pipe Pressurize nitrogen gas to 4 2 MPa to perform the sealing test Check all flare connecti...

Страница 23: ... a Additional amount for outdoor unit kg AJ 072LALBH 8HP 11 70 0 AJ 090LALBH 10HP 11 70 0 AJ 108LALBH 12HP 11 80 3 30 AJ 126LALBH 14HP 11 80 3 30 AJ 144LALBH 16HP 11 80 3 30 AJ 162LALBH 18HP 11 80 3 30 Diameter of liquid pipe mm b Additional amount for pipe length kg m Ø6 35 0 021 Ø9 52 0 058 Ø12 70 0 114 Ø15 88 0 178 Ø19 05 0 268 1 Calculation of additional amount for outdoor unit A a Outdoor uni...

Страница 24: ...tes for the system to start operating after settings for the test run are complete After the test run settings are complete all the outdoor units and the connected indoor units will start operating Room temperature control will not activate during test operation continuous operation If a knocking sound can be heard in the liquid compression of the compressor stop the unit immediately and then ener...

Страница 25: ...door unit discharge temp thermistor 2 error E 7 2 1 Outdoor unit compressor temp thermistor 1 error E 7 2 2 Outdoor unit compressor temp thermistor 2 error E 7 3 4 Outdoor unit heat ex 1 gas temp thermistor error E 7 3 5 Outdoor unit heat ex 1 liquid temp thermistor error E 7 3 6 Outdoor unit heat ex 2 gas temp thermistor error E 7 3 7 Outdoor unit heat ex 2 liquid temp thermistor error E 7 4 1 Ou...

Страница 26: ... 9 Air circulation Air circulation 10 Noise level Noise level 11 Refrigerant Refrigerant type and initial charging amount 12 Max pressure HP LP Means pressure of High Pressure side Low Pressure side 13 Protection Protection level against dust and water 14 Working temperature Working temperature 15 Condition of cooling heating Dry bulb temperature and wet bulb temperature under standard cooling hea...