11-1. External input
With using external input function, some functions on this product can be controlled from an external
device.
• “Operation/Stop” mode can be selected with function setting of indoor unit.
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 492 ft (150 m).
• The wire connection should be separate from the power cable line.
¢
Control input (Operation/Stop or Forced stop)
Indoor unit type
Connector
Compact cassette
CN102
Slim duct
CN102
Wall mounted
ASU7RLF1, ASU9RLF1, ASU12RLF1, ASU15RLF1
CNA01
ASU9RLS2, ASU12RLS2, ASU15RLS2
CNA01
ASU7RLF, ASU9RLF, ASU12RLF
CN303
ASU18RLF, ASU24RLF
CN14
Floor
AGU9RLF, AGU12RLF, AGU15RLF
CN14
The air conditioner can be remotely operated by means of the following on-site work.
Operation is started at the following contents by adding the contact input of a commercial on/off
switch to a connector on the external control PCB and turning it on.
Unit operation
Initial setting after power is on
Starting mode other than initial setting
Operation mode
Auto changeover
Mode at previous operation
Set temperature
76 °F (24 °C)
Temperature at previous operation
Airflow mode
AUTO
Mode at previous operation
Air direction (swing)
Standard air direction (swing: off)
Air direction at previous operation
- 97 -
11-1. External input
11. External input and output
MULTI TYPE
2, 3, 4 ROOMS TYPE
MULTI TYPE
2, 3, 4 ROOMS TYPE