EXTERNAL INPUT & OUTPUT
11.
Connector
INPUT
OUTPUT
REMARKS
CN14
Control input
-
See external input/output
settings for details.
CN20
-
Operation status output
CN21
-
Error status output
EXTERNAL INPUT
11-1.
CONTROL INPUT (Operation/Stop or Forced stop)
The air conditioner can be remotely operated by means of the following on-site work.
"Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor unit.
Unit operation is started at the following contents by adding the contact input of a commercial ON/OFF switch to a
connector on the external control PC board and turning it ON.
Unit operation
Initial setting after power is ON
Starting mode other than initial setting
Operation mode
Auto changeover
Mode at previous operation
Set temperature
24°C
Temperature at previous operation
Air flow mode
AUTO
Mode at previous operation
Up-down air direction (swing)
Standard air direction (swing OFF)
Air direction at previous operation
Left-right air direction (swing)
Standard air direction (swing OFF)
Air direction at previous operation
Circuit diagram example
z
Indoor unit
control PC board
Connector
1
3
Signal
Field supply
10m*
Connected unit
Ex.) Switch
Contact capacity : 24VDC or more, 10mA or more.
* Make the distance from the PC board to the connected unit within 10m.
When function setting is in "Operation/Stop" mode
●
Operation
Stop
ON
OFF
Input signal
Indoor unit
When function setting is "Forced stop" mode
●
Remote controller
ON
ON
ON
Input signal
ON
OFF
Indoor unit
Operation
Stop
Command
Forced stop
Normal
Remote control
operation invalidity
Содержание AG G09LVCB series
Страница 2: ...1 INDOOR UNIT FLOOR TYPE AG G09LVCB AG G12LVCB AG G14LVCB DTR_AG004E_03 2013 01 21 ...
Страница 33: ...2 OUTDOOR UNIT SINGLE TYPE AO G09LVCN AO G12LVCN AO G14LVCN DTR_AO094E_02 2013 01 21 ...
Страница 39: ... 02 05 OUTDOOR UNIT AO G09 14LVCN OUTDOOR UNIT AO G09 14LVCN WIRING DIAGRAMS 444 MODEL AO G09LVCN AO G12LVCN ...
Страница 40: ... 02 06 OUTDOOR UNIT AO G09 14LVCN OUTDOOR UNIT AO G09 14LVCN MODEL AO G14LVCN ...
Страница 47: ... 02 13 OUTDOOR UNIT AO G09 14LVCN OUTDOOR UNIT AO G09 14LVCN SOUND LEVEL CHECK POINT 88888 ...