2-2. Local setting procedure
NOTE:
Before performing the function setting, be sure to stop the operation of the air conditioner.
¢
Low noise mode
1.
Press the MODE switch button (S134) for 3 seconds or more to switch to “Local setting mode”.
2.
After confirming the LED lamp of POWER/MODE blinks 9 times, press the ENTER switch but-
ton (S132).
POWER
MODE
ERROR
(L1)
(L2)
(L3)
(L4)
(L5)
(L6)
PUMP
DOWN
LOW NOISE
PEAK CUT
Blinks
(9 times
)
Sign “
”: Lights off
3.
Press the SELECT switch button (S133), and adjust the LED lamp as shown below. Then the
LED lamp indicates the current setting.
(L2)
(L3)
LOW NOISE
Blink
LOW NOISE
MODE
4.
Press the ENTER switch button (S132).
(L2)
(L3)
LOW NOISE
LOW NOISE
MOD
E
Sign “ ”: Lights on
5.
Press the SELECT switch button (S133), and adjust the LED lamps as shown below.
PEAK CUT
MODE 1: Low
MODE 2: Lower
Blink
Blink
(L4)
(L5)
(L6)
6.
Press the ENTER switch button (S132) and fix it.
PEAK CUT
MODE 1: Low
MODE 2: Lower
(L4)
(L5)
(L6)
7.
To return to “Operating status display (Normal operation)”, press the EXIT switch button
(S131).
In case of missing how many times you pressed the SELECT and ENTER switch buttons:
1. To return to “Operation status display (Normal operation)”, press the EXIT switch button once.
2. Restart from the beginning of setting procedure.
NOTE:
In case of missing how many times you pressed the SELECT and ENTER switch buttons,
you must redo the setting procedure. Return to “Operation status display (Normal opera-
tion)” by pressing the EXIT switch button once, and restart from the beginning of the setting
procedure.
2-2. Local setting procedure
- (05-8) -
2. Function settings for outdoor unit
FIELD
WORKING
FIELD
WORKING
Содержание ABYG36KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB009EF_02 ...
Страница 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB009EF_02 ...
Страница 37: ...3 TROUBLESHOOTING 2020 07 21 SR_CH03_AB009EF_01 ...
Страница 40: ......
Страница 102: ...5 2 Outdoor unit 03 62 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 103: ...4 CONTROL AND FUNCTIONS 2020 07 21 SR_CH04_AB009EF_01 ...
Страница 105: ...8 8 High temperature and high pressure release control 04 31 CONTENTS continued ...
Страница 106: ......
Страница 139: ...5 FILED WORKING 2020 07 21 SR_CH05_AB009EF_01 ...