2-15. E: 57. Damper (Open/Close) detection limit switch error
Indicator
Wired remote
controller
Error code
E: 57
Detective actuator
Indoor unit main PCB
•
When limit switch were not able to detect the close
though the damper close.(Upper air flow)
•
When limit switch were not able to detect the open
though the damper open.(Upper & Lower air flow)
Limit switch
Damper
Forecast of cause
Limit switch failure
Shorted connector/wire
Damper faulure
Controller PCB failure
Check point 1. Check limit switch
•
Check operation of limit switch. (any blocking by dust, etc.)
•
Remove limit switch and check ON/OFF switching operation by using a meter.
-> If limit switch is detective, replace it.
↓
Check point 2. Check connector (CN18)/wire
Check loose contact of CN18/shorted wire (pinched wire).
-> Replace limit switch if the wire is abnormal
↓
Check point 3. Check Damper
•
Check the obstruction of damper movement.
•
Check the damper movement.
-> Replace damper if the damper is abnormal
↓
Check point 4. Replace main PCB
If Check Point 1 and 3 do not improve the symptom, change main PCB.
↓
End
2-15. E: 57. Damper (Open/Close) detection limit switch error
- (03-19) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание ABYG18KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB004EF_03 ...
Страница 24: ...2 2 Outdoor unit 01 18 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 25: ...2 TECHNICAL DATA AND PARTS LIST 2020 12 09 SR_CH02_AB004EF_05 ...
Страница 71: ...3 TROUBLESHOOTING 2020 07 01 SR_CH03_AB004EF_01 ...
Страница 74: ......
Страница 138: ...5 2 Outdoor unit 03 64 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 139: ...4 CONTROL AND FUNCTIONS 2020 07 01 SR_CH04_AB004EF_01 ...
Страница 141: ...8 8 High temperature and high pressure release control 04 42 CONTENTS continued ...
Страница 142: ......
Страница 187: ...5 FILED WORKING 2020 07 01 SR_CH05_AB004EF_01 ...