2-31. E: A5. Low pressure error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: A5
Detective actuator
Outdoor unit main PCB
Protection stop by suction pressure ≥ 0.02 MPaG
continued 5 minutes repeats 5 times within 24 hours.
Suction pressure sensor
Forecast of cause
3-way valve not opened
Outdoor unit ambient temperature too low
Outdoor unit operation failure, foreign matter on heat
exchanger
EEV defective, strainer clogged
Solenoid valve defective
Low pressure sensor characteristics defective
Insufficient refrigerant
Main PCB failure
Check point 1. Check if 3-way valve is open
If the 3-way valve is closed, open the 3-way valve and check operation.
NOTE:
For cooling operation, check gas side of the 3-way valve.
For heating operation, check liquid side of the 3-way valve.
↓
Check point 2. Check the outdoor unit ambient temperature (Only when heating operation)
Outdoor unit ambient temperature lower than operating range?
↓
Check point 3. Check the outdoor unit fan and heat exchanger (Only when heating operation)
•
No foreign object in air passage?
•
Heat exchanger fins clogged?
•
Fan rotes?
•
Check the motor. (Refer to outdoor unit fan motor in
↓
Check point 4. Check the electronic expansion valve (EEV) and strainer
•
Check if EEV open.
Refer to outdoor unit Electronic Expansion Valve (EEV) in
•
Check the strainer clogging.
↓
Check point 5. Check the suction pressure sensor
Check the suction pressure sensor characteristics.
NOTE:
For the characteristics of the thermistor, refer to suction pressure sensor in
↓
2-31. E: A5. Low pressure error (Outdoor unit)
- (03-37) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание ABYG18KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB004EF_03 ...
Страница 24: ...2 2 Outdoor unit 01 18 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 25: ...2 TECHNICAL DATA AND PARTS LIST 2020 12 09 SR_CH02_AB004EF_05 ...
Страница 71: ...3 TROUBLESHOOTING 2020 07 01 SR_CH03_AB004EF_01 ...
Страница 74: ......
Страница 138: ...5 2 Outdoor unit 03 64 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 139: ...4 CONTROL AND FUNCTIONS 2020 07 01 SR_CH04_AB004EF_01 ...
Страница 141: ...8 8 High temperature and high pressure release control 04 42 CONTENTS continued ...
Страница 142: ......
Страница 187: ...5 FILED WORKING 2020 07 01 SR_CH05_AB004EF_01 ...