7. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit
*
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H
H
7-1. Model: AOYG36KBTA5
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
¢
Indoor unit: 7,000 Btu/h
Cooling
Pipe length
m
2.5
5
10
15
20
25
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
15
—
—
—
0.955
0.941
0.927
10
—
—
0.976
0.962
0.949
0.935
5
—
0.992
0.984
0.970
0.956
0.942
2.5
0.996
0.996
0.988
0.974
0.960
0.946
0
1.000
1.000
0.992
0.978
0.964
0.950
Indoor unit is lower
than outdoor unit *2
-2.5
1.000
1.000
0.992
0.978
0.964
0.950
-5
—
1.000
0.992
0.978
0.964
0.950
-10
—
—
0.992
0.978
0.964
0.950
-15
—
—
—
0.978
0.964
0.950
Heating
Pipe length
m
2.5
5
10
15
20
25
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
15
—
—
—
0.976
0.957
0.938
10
—
—
0.991
0.976
0.957
0.938
5
—
1.000
0.991
0.976
0.957
0.938
2.5
1.000
1.000
0.991
0.976
0.957
0.938
0
1.000
1.000
0.991
0.976
0.957
0.938
Indoor unit is lower
than outdoor unit *2
-2.5
0.998
0.997
0.989
0.974
0.955
0.936
-5
—
0.995
0.986
0.971
0.952
0.933
-10
—
—
0.981
0.966
0.947
0.929
-15
—
—
—
0.961
0.943
0.924
- 426 -
7-1. Model: AOYG36KBTA5
7. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOYG36KBTA5
OUTDOOR UNIT
AOYG36KBTA5