background image

This air conditioner uses new refrigerant HFC (R410A).

The basic installation work procedures are the same as conventional refrigerant models.
However, pay careful attention to the following points:

1

Since the working pressure is 1.6 times higher than that of conventional refrigerant models, some of the piping and
installation and service tools are special. (See the table below.)
Especially, when replacing a conventional refrigerant model with a new refrigerant R410A model, always replace the
conventional piping and flare nuts with the R410A piping and flare nuts.

2

Models that use refrigerant R410A have a different charging port thread diameter to prevent erroneous charging with
conventional refrigerant and for safety. Therefore, check beforehand. [The charging port thread diameter for R410A is
1/2 UNF 20 threads per inch.]

3

Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with refrigerant models. Also, when
storing the piping, securely seal the openings by pinching, taping, etc.

4

When charging the refrigerant, take into account the slight change in the composition of the gas and liquid phases, and
always charge from the liquid phase side whose composition is stable.

- Continued on back -

Contents of change

Pressure is high and cannot be measured with a conventional gauge. To prevent erroneous mixing of other
refrigerants, the diameter of each port has been changed.
It is recommended the gauge with seals –0.1 to 5.3 MPa (–76 cmHg to 53 kgf/cm

2

) for high pressure. –0.1 to

3.8 MPa (–76 cmHg to 38 kgf/cm

2

) for low pressure.

To increase pressure resistance, the hose material and base size were changed.
A conventional vacuum pump can be used by installing a vacuum pump adapter.
Special gas leakage detector for HFC refrigerant R410A.

Tool name

Gauge manifold

Charge hose

Vacuum pump

Gas leakage detector

CONNECTION PIPE REQUIREMENT

ELECTRICAL REQUIREMENT

•••••

Electric wire size:

2. BENDING PIPES

 CAUTION

1

To prevent breaking of the pipe, avoid sharp bends.
Bend the pipe with a radius of curvature of 150 mm or
over.

2

If the pipe is bent repeatedly at the same place, it will
break.

6.35 mm (1/4 in.)

9.52 mm (3/8 in.)

12.70 mm (1/2 in.)

15.88 mm (5/8 in.)

19.05 mm (3/4 in.)

0.80 mm

0.80 mm

0.80 mm

1.00 mm

1.20 mm

Pipe outside diameter

Thickness

Thicknesses of Annealed Copper Pipes (R410A)

SELECTING THE MOUNTING POSITION

Decide the mounting position with the customer as follows:

1

INSTALLATION PROCEDURE

 

 CAUTION

Install heat insulation around both the gas and liquid pipes. Failure to do so may cause water leaks.
Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only)
In addition, if the humidity level at the installation location of the refrigerant piping is expected to exceed 70%, install heat
insulation around the refrigerant piping. If the expected humidity level is 70-80%, use heat insulation that is 15 mm or thicker
and if the expected humidity exceeds 80%, use heat insulation that is 20 mm or thicker.
If heat insulation is used that is not as thick as specified, condensation may form on the surface of the insulation.
In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less (at 20 °C).

•••••

Use pipe with water-resistant heat insulation.

INDOOR UNIT

(1) Install the indoor unit level on a strong wall which is not subject to vibration.
(2) The inlet and outlet ports should not be obstructed : the air should be able to blow all over the room.
(3) Do not install the unit where it will be exposed to direct sunlight.
(4) Install the unit where connection to the outdoor unit is easy.
(5) Install the unit where the drain pipe can be easily installed.
(6) Take servicing, etc., into consideration and leave the spaces shown in the figure. Also install the unit where the filter can be removed.

 WARNING

Select installation locations that can properly support the weight of the indoor and outdoor units. Install the units securely so
that they do not topple or fall.

 CAUTION

1

Do not install where there is the danger of combustible gas leakage.

2

Do not install the unit near heat source of heat, steam, or flammable gas.

3

If children under 10 years old may approach the unit, take preventive measures so that they cannot reach the unit.

[FOR HALF CONCEALED INSTALLATION]

Ceiling panel

Ceiling panel

INDOOR UNIT

80 or over

150 or over

2

PREPARING INDOOR UNIT

INSTALLATION

REMOVE THE INTAKE GRILLE AND SIDE COVER

(1) Remove the two Air filters.
(2) Remove the two Intake grilles.

For 

4

 Left rear drain and 

5

 Left drain: Remove air filters and intake

grilles at three places. (Refer to “

2

INDOOR UNIT INSTALLATION”.)

(3) Remove the Side cover A (Right side) and Side cover B (Right and

Left side).

For 

5

 Left drain : Remove both the Side cover A (Right and Left

side). (Refer to “

2

 INDOOR UNIT INSTALLATION”.)

(4) This air conditioner can be set up to intake fresh air. For information

about how to install for fresh-air intake, refer to “

7

 FRESH-AIR INTAKE”.

INDOOR UNIT INSTALLATION

You can use the accessory template to help you install the indoor unit.
The template helps you determine the appropriate locations for suspen-
sion bolts and pipe opening (drain pipe and connection cord).

[For Half-Concealed Installation]

•••••

Suspension-bolt pitch should be as shown in the figure.

2. SELECT PIPING DIRECTION

Select connection piping and drain piping directions.

[FOR 

4

 Left rear piping, 

5

 Left piping]

•••••

Transfer the Drain cap and Drain cap seal.

Drain cap seal

Drain cap

Indoor unit

Drain pan

Drain cap seal

Drain cap

Push cap all the way on
(as far as it will go).

4. INSTALLING THE INDOOR UNIT

(1) Lift unit so that suspension bolts pass through the suspension fittings

at the sides (four places), and slide the unit back.

Wall

Ceiling

1. LOCATION OF CEILING SUSPENSION BOLTS

30 mm

Suspension bolt pitch 1600 mm

Dimensions
(Space Required
for Installation)

30 mm

10 mm

155 mm

300 mm

INDOOR UNIT (TOP VIEW)

INDOOR UNIT

Suspension bolt should
extend outward 30 to 75 mm.

3. DRILLING THE HOLES AND ATTACHING THE

SUSPENSION BOLTS

(1) Drill ø25 mm holes at the suspension-bolt locations.
(2) Install the bolts, then temporarily attach Special nuts A and B and a

normal M10 nut to each bolt. (The two special nuts are provided with
the unit. The M10 nut must be obtained locally.) Refer to the figure.

Bolt Strength

980 to 1470 N (100 to 150 kgf)

Ceiling panel

Special nut A (Included)

Special nut B (Included)

M10 Nut (Obtained locally)

10 to 15 mm

INDOOR UNIT

Wall

Ceiling panel

(2) Fasten the indoor unit into place by tightening-up the special “B” bolts

and the M10 nuts. Make sure that unit is secure and will not shift back
and forth.

[For Half-Concealed Installation]

When installing the indoor unit in a semi-concealed orientation, make sure
to reinforce the insulation of the unit on all sides. Drops of water may fall
from the unit if it is not thoroughly insulated.

Glass wool insulate
(10 to 20 mm thick)

INDOOR UNIT

(Top view)

Wall

Ceiling panel

 CAUTION

Install the drain pipe in accordance with the instructions
in this installation instruction sheet and keep the area
warm enough to prevent condensation. Problems with the
piping may lead to water leaks.

•••••

Install the drain pipe with downward gradient (1/50 to 1/100) and so
there are no rises or traps in the pipe.

•••••

Use general hard polyvinyl chloride pipe (VP25) [outside diameter
38 mm].

•••••

During installation of the drain pipe, be careful to avoid applying
pressure to the drain port of the indoor unit.

•••••

When the pipe is long, install supporters.

•••••

Do not perform air bleeding.

•••••

Always heat insulate (8 mm or over thick) the indoor side of the drain
pipe.

(1) Install insulation for the drain pipe.

Cut the included insulation material to an appropriate size and adhere
it to the pipe.

Drain pipe

Insulation for drain pipe
(To be obtained locally. Length
should be at least 8 mm.)

Drain pipe insulation (accessories)

Indoor unit (drain port)

(2) If “

1

 Right rear piping” : fasten the drain pipe with VT wire so that the

pipe slopes correctly within the indoor unit.

Indoor unit (rear view)

VT wire

Drain hose

Drain pipe insulation

Drain pipe

No gap

10 mm or over

Indoor unit

3. CONNECTION PIPES

Indoor unit

(1) Detach the caps and plugs from the pipes.

 CAUTION

1

Be sure to apply the pipe against the port on the in-
door unit correctly. If the centering is improper, the flare
nut cannot be tightened smoothly. If the flare nut is
forced to turn, the threads will be damaged.

2

Do not remove the flare nut from the indoor unit pipe
until immediately before connecting the connection
pipe.

(2) Centering the pipe against port on the indoor unit, turn the flare nut

with your hand.

To prevent gas leakage, coat the flare
surface with alkylbenzene oil (HAB).
Do not use mineral oil.

(3) Remove the filter guide.

Indoor unit

Filter guide

(4) Attach the connection pipe.

Connection pipe (Liquid)

Indoor unit

Connection pipe (Gas)

For 

2

 Top piping and 

3

 Right piping connections, use the Auxiliary

pipe (Gas pipe) provided.

2

 Top piping

Connection pipe (Gas)

Indoor unit (rear)

Connection pipe (Gas)

3

 Right piping

Auxiliary pipe (Gas pipe)

(5) When the flare nut is tightened properly by your hand, use a torque

wrench to finally tighten it.

Torque wrench

Holding spanner

Body side

 CAUTION

Hold the torque wrench at its grip, keeping it in the right
angle with the pipe, in order to tighten the flare nut
correctly.

Flare nut

Tightening torque

6.35 mm (1/4 in.) dia.

9.52 mm (3/8 in.) dia.

12.70 mm (1/2 in.) dia.

15.88 mm (5/8 in.) dia.

19.05 mm (3/4 in.) dia.

1

Right rear piping

5

Left piping
(Drain pipe only)

4

Left rear piping
(Drain pipe only)

2

Top piping
(Connection pipe only)

3

Right
piping

Cut off the piping outlet cutting groove
with a hacksaw, etc.

INDOOR UNIT (TOP VIEW)

Air filter

Intake grille

Tapping screw

INDOOR UNIT

Side cover A (Right side)

Side cover B

(Left side)

Side cover B (Right side)

Diameter

Gas

15.88 mm (5/8 in.)

Drilling position for Suspension bolt

Ceiling

Wall

Template

Drilling position for piping

40 mm

Ceiling Opening: 1580 mm

40 mm

Ceiling panel

Ceiling Opening: 640 mm

15 mm

Suspension bolt should
extend outward 30 to 50 mm.

INDOOR UNIT

Ceiling panel

 CAUTION

In order to check the drainage, be sure to use a level
during installation of the indoor unit. If the installation site
of the indoor unit is not level, water leakage may occur.

5. DRAIN PIPING

 CAUTION

The maximum/minimum lengths of this product, refer to the installation instruction sheet supplied with the outdoor unit. If
the units are further apart than this, correct operation can not be guaranteed.

The pipes are shaped by your hands. Be careful not to collapse them.

Do not bend the pipes in an angle more than 90

°

.

When pipes are repeatedly bend or stretched, the material will harden,

making it difficult to bend or stretch them any more. Do not bend or

stretch the pipes more than three times.

14 to 18 N·m (140 to 180 kgf·cm)

33 to 42 N·m (330 to 420 kgf·cm)

50 to 62 N·m (500 to 620 kgf·cm)

63 to 77 N·m (630 to 770 kgf·cm)

100 to 110 N·m (1000 to 1100 kgf·cm)

•••••

Use conformed cord with Type 245 IEC57.

•••••

Install all electrical works in accordance to the standard.

•••••

Install the disconnect device with a contact gap of at least 3 mm in all poles nearby the units. (Both indoor unit and outdoor unit)

It is necessary to use seamless copper pipes and it is desirable that the
amount of residual oil is less than 40 mg/10 m. Do not use copper pipes
having a collapsed, deformed or discolored portion (especially on the interior
surface). Otherwise, the expansion valve or capillary tube may become
blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using
conventional refrigerant, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in the table.
Never use copper pipes thinner than that in the table even when it is
available on the market.

Liquid

9.52 mm (3/8 in.)

MIN.

1.5

Connection cord (mm )

MAX.

2.5

2

4. HEAT INSULATION ON THE PIPE JOINTS

(INDOOR SIDE ONLY)

After checking for gas leaks, insulate by wrapping insulation around the
two parts (Gas and Liquid) of the indoor unit coupling, using the coupler
heat insulation.
After installing the coupler heat insulation, wrap both ends with vinyl tape
so that there is no gap.
Secure both ends of the heat insulation material using nylon fasteners.
And finally fix connection pipe (Liquid) to connection pipe (Gas) by rolling
vinyl tape over coupler heat insulation (Gas) and coupler heat insulation
(Liquid).

Indoor unit

Indoor unit

Indoor unit

Coupler heat insulation (Large)

Connection pipe (Gas)

Connection pipe (Liquid)

Coupler heat insulation (Small)

Nylon fastener (Large)

No gap

Coupler heat
insulation

Nylon fastener (Small)

Connection pipe (Gas)

Connection pipe (Liquid)

Vinyl tape

When using an auxiliary pipe, make sure that the fastener used is insu-
lated in the same way.

 CAUTION

There should be no gaps between the insulation and the
product.

 WARNING

1

Before starting work, check that power is not being
supplied to the indoor unit and outdoor unit.

2

Match the terminal board numbers and connection
cord colors with those of the outdoor unit.
Erroneous wiring may cause burning of the electric
parts.

3

Connect the connection cords firmly to the terminal
board. Imperfect installation may cause a fire.

4

Always fasten the outside covering of the connection
cord with the cord clamp. (If the insulator is chafed,
electric leakage may occur.)

5

Always connect the ground wire.

6

Install the remote controller wires so as not to be di-
rect touched with your hand.

HOW TO  CONNECT WIRING TO THE
TERMINALS

A. For solid core wiring

(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip

the insulation to about 25 mm to expose the solid wire.

(2) Using a screwdriver, remove the terminal screw(s) on the terminal

board.

(3) Using pliers, bend the solid wire to form a loop suitable for the

terminal screw.

(4) Shape the loop wire properly, place it on the terminal board and

tighten securely with the terminal screw using a screwdriver.

B. For strand wiring

(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip

the insulation to about 10 mm to expose the strand wiring.

(2) Using a screwdriver, remove the terminal screw(s) on the terminal

board.

(3) Using a round terminal fastener or pliers, securely clamp a round

terminal to each stripped wire end.

(4) Position the round terminal wire, and replace and tighten the

terminal screw using a screwdriver.

A. Solid wire

Str

ip 25 mm

Insulation

Loop

B. Strand wire

Str

ip 10 mm

Round
terminal

Wire

Screw with
special washer

Round terminal

Terminal
board

Wire

Screw with
special washer

Round
terminal

Terminal block

4

ELECTRICAL WIRING

1. CONNECTION DIAGRAMS

3. INDOOR UNIT

Indoor unit

Control box

Tapping screw

(2) Remove the Cover A and install the Connection cord.
(3) Reattach Cover A. Then fasten the control box back into its original

position using the two tapping screws.

Cover A

Control box

(4) After wiring is complete, clamp the Connection cord with the Cord

clamp.

2. CONNECTION CORD PREPARATION

Power supply cord
or connection cord

Cable clip

Connection cord

 CAUTION

Use care not to mistake the power supply cord and
connection wires when installing.

(1) Remove the two tapping screws and pull the control box downward.

30 mm

40 mm or more

For earth

(5) Attach the connection cord and cable clips. Make sure that they are

positioned so that they will not interfere with opening and closing of
the intake grille or with removal and installation of the air filters.

STANDARD PARTS

The following installation parts are furnished.
Use them as required.

INDOOR UNIT ACCESSORIES

Q’ty

1

1

2

1

Name and Shape

Drain hose insulation

VT wire

Coupler heat insulator (large)

Coupler heat insulator (small)

Nylon fastener

Special nut A
(large flange)

Special nut B
(small flange)

Installation
template

Auxiliary pipe assembly

Application

Adhesive type 70 

×

 230

For fixing the drain hose
L 280 mm

For indoor side pipe joint
(Gas pipe)

For indoor side pipe joint
(Liquid pipe)

For fixing the coupler heat
insulator

For installing indoor unit

For installing indoor unit

For positioning the indoor
unit

For connecting the piping

Large

4

Small

4

4

4

1

1

OPTIONAL PARTS

The following options are available.

•••••

DRAIN PUMP UNIT: UTR-DPB241 (P/N 9034087001)

•••••

ROUND DUCT: UTD-RF204 (P/N 9093160004)

3

CONNECTING THE  PIPE

 CAUTION

1

Do not use mineral oil on flared part. Prevent mineral
oil from getting into the system as this would reduce
the lifetime of the units.

2

While welding the pipes, be sure to blow dry nitrogen
gas through them.

1. FLARING

(1) Cut the connection pipe to the necessary length with a pipe cutter.
(2) Hold the pipe downward so that cuttings will not enter the pipe and

remove the burrs.

(3) Insert the flare nut (always use the flare nut attached to the indoor

and outdoor units respectively) onto the pipe and perform the flare
processing with a flare tool.
Use the special R410A flare tool, or the conventional flare tool.

When using conventional flare tools to flare R410A pipes, the dimension
A should be approximately 0.5 mm more than indicated in the table (for
flaring with R410A flare tools) to achieve the specified flaring. Use a thick-
ness gauge to measure the dimension A.

Pipe outside

diameter

Width across flats

of Flare nut

Width across flats

Check if [L] is flared uniformly
and is not cracked or scratched.

B

Die

A

Pipe

6.35 mm (1/4 in.)

9.52 mm (3/8 in.)

12.70 mm (1/2 in.)

15.88 mm (5/8 in.)

19.05 mm (3/4 in.)

0 to 0.5

Pipe outside diameter

Dimension A

 

(mm)

Flare tool for R410A, clutch type

6.35 mm (1/4 in.)

9.52 mm (3/8 in.)

12.70 mm (1/2 in.)

15.88 mm (5/8 in.)

19.05 mm (3/4 in.)

9.1

13.2

16.6

19.7

24.0

Pipe outside diameter

Dimension B

 

      (mm)

0

 -0.4

6.35 mm (1/4 in.)

9.52 mm (3/8 in.)

12.70 mm (1/2 in.)

15.88 mm (5/8 in.)

19.05 mm (3/4 in.)

17 mm

22 mm

26 mm

29 mm

36 mm

INSTALLATION
INSTRUCTION SHEET

(PART NO. 9378042018)

For authorized service personnel only.

Ceiling Type

 DANGER

This mark indicates procedures which, if improperly performed, are most likely to result in the death of or
serious injury to the user or service personnel.

 WARNING

This mark indicates procedures which, if improperly performed, might lead to the death or serious injury of
the user.

 CAUTION

This mark indicates procedures which, if improperly performed, might possibly result in personal harm to
the user, or damage to property.

Copper pipes

Special tools for R410A

 DANGER

Never touch electrical components immediately after the power supply has been turned off. Electrical shock may occur. After
turning off the power, always wait 5 minutes or more before touching electrical components.

(3) If the drain hose will not be connected to the right rear piping, cut the

hole cover at the points indicated in Fig. (a), and attach it to the piping
hole as shown in Fig. (b).

Drain pipe

Arrange the drain pipe
lower than this portion.

Lifted up

Wave

End in water

Supporter

1.5 to 2 m

3

2

1

3

2

1

Connection cord
(To outdoor unit)

Wired remote controller cord
(Option)

(a)

Cut x 5

Hole cover

(b)

Wired remote controller (option)

3
2
1

3

2

1

Indoor unit
side terminal

Power line

Control line

Outdoor unit

Red

White

Black

(Unit : mm)

Ceiling

INDOOR UNIT

80 or over

Ceiling

150 or over

10 or over

Obstruction

2300 or o

v

er

1000 or o

v

er

Floor

Floor

10 or over

Obstruction

2300 or o

v

er

1000 or o

v

er

Good

Bad

Bad

Red

White

Black

*

*

 Ground the remote controller if it has ground wire.

Power

Remote

Wired remote controller cord

9378042018_IM_front.p65

11/1/07, 9:57

1

Отзывы: