SERVICE PARTS INFORMATION 5
Check Point : ABU18/ 24RULX
Red
Pink
Red
White
Read Wire
131
8%
107
8%
Purple
237
8%
46.4
8%
46.4
8%
Resistance value
(AC)
Thermal protector
Pr
BLUE
PURPLE
PINK
RED
BLACK
WHITE
Check Point : ABU36RSLX
22.8
10%
31.9
10%
Resistance value
(AC)
Thermal protector
239 257
°F
(115 125
°C)
Pr
1
1
3
2
3
The connector
inserting numbers
2
3
at 68
°F(
20
°C)
at 68
°F(
20
°C)
275 293
°F
(135 145
°C)
Indoor Unit Fan Motor
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
02-33
- Red
- Black
- Pink
- Purple
- Blue
Содержание ABU18RULX
Страница 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A Universal Floor Ceiling Large Ceiling type INVERTER ...
Страница 25: ...2 TROUBLE SHOOTING R410A INVERTER Universal Floor Ceiling Large Ceiling type ...
Страница 59: ...3 REPLACEMENT PARTS R410A INVERTER Universal Floor Ceiling Large Ceiling type ...