2-26. E: 86. High pressure switch error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: 86
Detective actuator
Outdoor unit main PCB
30 seconds or more after power-on, when pressure
sensor detection value detects the condition below
continuously for 30 seconds or more.
Ps ≤ 0 or Ps ≥ 5 [MPa]
High pressure switch
Forecast of cause
Connector connection failure
Pressure sensor failure
Main PCB failure
Check point 1. Check connection of the pressure sensor
•
Check if the terminal connection is loose.
•
Check if connector is removed.
•
Check erroneous connection.
•
Check if cable is open.
-> Upon correcting the removed connector or mis-wiring, reset the power.
↓
Check point 2. Check output voltage of main PCB
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor
(DC 5.0 V ± 5%).
NOTE:
For details of thermistor connector, refer to
TECHNICAL DATA AND PARTS LIST on page 02-13.
If the voltage is not correct, replace main PCB.
↓
Check point 3. Check output voltage of pressure sensor
Make sure circuit diagram of outdoor unit and check terminal voltage. Voltage is refer
to the following graph.
4.5
0.5
0
5
Pressure [MPa]
Voltage [V]
If the voltage is not correct, replace pressure sensor.
↓
End
2-26. E: 86. High pressure switch error (Outdoor unit)
- (03-31) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание ABHG54KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 04 16 SR_CH01_AB007EG_01 ...
Страница 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB007EG_02 ...
Страница 31: ...3 TROUBLESHOOTING 2020 07 29 SR_CH03_AB007EG_01 ...
Страница 34: ......
Страница 95: ...4 CONTROL AND FUNCTIONS 2020 07 29 SR_CH04_AB007EG_01 ...
Страница 97: ...8 8 High temperature and high pressure release control 04 29 CONTENTS continued ...
Страница 98: ......
Страница 129: ...5 FILED WORKING 2020 07 29 SR_CH05_AB007EG_01 ...