background image

OUTDOOR UNIT

OUTDOOR UNIT INSTALLATION

FINISHING

(1) Insulate between pipes.

For rear, right, and bottom piping, overlap the connection pipe heat insu-
lation and indoor unit pipe heat insulation and bind them with vinyl tape
so that there is no gap.

For left and left rear piping, butt the connection pipe heat insulation and
indoor unit pipe heat insulation together and bind them with and vinyl
tape so that there is no gap.

For left and left rear piping, wrap the area which accommodates the rear
piping housing section with cloth tape.

For left and left rear piping, bind the connection cord to the top of the
pipe with vinyl tape.

For left and left rear piping, bundle the piping and drain hose together by
wrapping them with cloth tape over the range within which they fit into
the rear piping housing section.

(2) Temporarily fasten the connection cord along the connection pipe with vinyl

tape. (Wrap to about 1/3 the width of the tape from the bottom of the pipe so
that water does not enter.)

(3) Fasten the connection pipe to the outside wall with saddles, etc.
(4) Fill the gap between the outside wall pipe hole and the pipe with sealer so

that rain water and wind cannot blow in.

(5) Fasten the drain hose to the outside wall, etc.

FRONT PANEL REMOVAL AND INSTALLATION

THE INTAKE GRILLE REMOVAL

(1) Open the intake grille.
(2) Pull down the knob.
(3) Lift the intake grille upward, until the axle at the top of the

intake grille is removed.

THE INTAKE GRILLE INSTALLATION

(1) The fixing axle of the intake grille is installed on the Panel.
(2) Lay down the intake grille.

THE FRONT PANEL REMOVAL

(1) Remove intake grille (Reference the intake grille removal.)
(2) Remove six screws.
(3) The thumb is hung on the lower part as shown in the figure,

and it pulls to the front, pushing [-] mark , and bottom hooks
(two position) is removed from wall hook bracket.

(4) The front panel is pulled to the front, raising the upper sur-

face, and a front panel is removed.

THE FRONT PANEL INSTALLATION

(1) Firstly, fit the lower part of the front panel, and insert top and

bottom hooks. (Three top sides)

(2) Six screws is attached.
(3) The intake grille is attached.

POWER

Transmitter section

Test run button

TEST RUNNING

Perform test operation and check items 1 and 2 below.

For the test operation method, refer to the operating manual.

The outdoor unit, may not operate, depending on the room temperature. In this case, press the test run button on the remote control unit
while the air conditioner is running, (Point the transmitter section of the remote control unit toward the air conditioner and press the test run
button with the tip of a ball-point pen, etc.)

To end test operation, press the remote control unit START/STOP button.
(When the air conditioner is run by pressing the test run button, the OPERATION indicator lamp and TIMER indicator lamp will simultane-
ously flash slowly.)

1. INDOOR UNIT

(1) Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?
(3) Do the air flow-direction louver operate normally?
(4) Is the drain normal?

2. OUTDOOR UNIT

(1) Is there any abnormal noise and vibration during operation?
(2) Will noise, wind, or drain water from the unit disturb the neighbors?
(3) Is there any gas leakage?

REMOTE CONTROL UNIT INSTALLATION

1. REMOTE CONTROL UNIT HOLDER INSTALLA-

TION

Install the remote control unit with a distance of 23
ft(7 m) between the remote control unit and the pho-
tocell as the criteria. However, when installing the re-
mote control unit, check that it operates positively.

Install the remote control unit holder to a wall, pillar,
etc. with the tapping screw.

 

WARNING

(1) Install the unit where it will not be tilted by more than 3°. However, do not install the unit with it tilted

towards the side containing the compressor.

(2) When installing the outdoor unit where it may exposed to strong wind, fasten it securely.

Overlap the insulation

Bind the pipes together so
that there is no gap.

Connection pipe
(heat insulation)

Vinyl tape

Indoor unit pipe
(heat insulation)

Check the following:

GOOD

Lifted up

Saddle

Wave

End in water

BAD

BAD

BAD

Drain hose

For connection from the left rear

Connection cord

Wall pipe

Connection pipe

Drain hose

Left piping

Connection cord

Pipe

Drain hose

Pipe

Drain hose

Cloth tape

Wrap with
cloth tape

Pipe

(Saddle)

(Outside wall cap)

(Sealer putty)

(Outdoors)

Wall

 WARNING

(1) The rated voltage of this product is 208/230 V AC

60 Hz.

(2) Before turning on the power, check if the voltage

is within the 208 V 

-

10 % to 230 V +10% range.

(3) Always use a special branch circuit and install a

special receptacle to supply power to the room
air conditioner.

(4) Use a circuit breaker and receptacle matched to

the capacity of the air conditioner.

(5) Do not extend the power cord.

(6) Perform wiring work in accordance with stand-

ards so that the air conditioner can be operated
safely and positively.

(7) Install a leakage circuit breaker in accordance with

the related laws and regulations and electric com-
pany standards.

 CAUTION

(1) The power source capacity must be the sum of

the air conditioner current and the current of other
electrical appliances. When the current contracted
capacity is insufficient, change the contracted ca-
pacity.

(2) When the voltage is low and the air conditioner is

difficult to start, contact the power company the
voltage raised.

CUSTOMER GUIDANCE

Explain the following to the customer in accordance with the operat-
ing manual:
(1) Starting and stopping method, operation switching, temperature

adjustment, timer, air flow switching, and other remote control unit
operations.

(2) Air filter removal and cleaning, and how to use the air louvers.
(3) Give the operating and installation manuals to the customer.

 CAUTION

(1) Check that the indoor unit correctly receives the

signal from the remote control unit, then install
the remote control unit holder.

(2) Select the remote control unit holder selection

site by paying careful attention to the following:
Avoid places in direct sunlight.
Select a place that will not be affected by the heat
from a stove, etc.

Remote control unit
holder fixing

Remote control
unit holder

Tapping
screw
(small)

Remote control
unit mounting

Remote
control unit

Push

Set

Front panel

Bearing

Mounting shaft

Intake grille

Intake grille

Knob

Top hooks
(two sides)

Top holes (two sides)

Top hole (center)

Top hook (center)

Front panel

Indoor unit

 

CAUTION

Install the front panel and INTAKE GRILLE securely. If installation is imperfect, the front panel or INTAKE GRILLE
may fall off and cause injury.

Wall hook bracket

Front panel

Push

[-] mark

Screws (6 position)

Push

Front panel

PUMP DOWN OPERATION (FORCED COOLING OPERATION)

To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal, recover refrigerant by doing the cooling operation
or forced cooling operation according to the following procedure. (When the cooling operation cannot start in winter, and so on, start the
forced cooling operation.)

(1) Do the air purging of the charge hose by connecting the charging hose of gauge manifold to the charging port of 3 way valve (large) and

opening the low-pressure valve slightly.

(2) Close the valve stem of 3 way valve (small) completely.
(3) Start the cooling operation or following forced cooling operation.

When using the remote control unit
Press the TEST RUN button after starting the cooling operation by the remote control unit.
The operation indicator lamp and timer indicator lamp will begin to flash simultaneously during test run.
When using the MANUAL AUTO button of the indoor unit (The remote control unit is lost, and so on.)
Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds.
(The forced cooling operation cannot start if the MANUAL AUTO button is not kept on pressing for more than 10 seconds.)

(4) Close the valve stem of 3 way valve (large) when the reading on the compound pressure gage becomes 0.05~0 MPa (0.5~0 kg/cm

2

).

(5) Stop the operation.

• Press the START/STOP button of the remote control unit to stop the operation.
• Press the MANUAL AUTO button when stopping the operation from indoor unit side.
  (It is not necessary to press on keeping for more than 10 seconds.)

 

CAUTION

Install heat insulation around both the gas and liquid pipes. Failure to do so may cause water leaks.
Use heat insulation with heat resistance above  248 °F. (Reverse cycle model only)
In addition, if the humidity level at the installation location of the refrigerant piping is expected to exceed 70%, install heat insula-
tion around the refrigerant piping. If the expected humidity level is 70-80%, use heat insulation that is 15 mm or thicker and if the
expected humidity exceeds 80%, use heat insulation that is 20 mm or thicker.
If heat insulation is used that is not as thick as specified, condensation may form on the surface of the insulation.
In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less (at 68 °F).

 

CAUTION

During the pump-down operation, make sure that the compressor is turned off before you remove the refrigerant piping.

Do not remove the connection pipe while the compressor is in operation 3 way valve open. This may cause abnormal pressure in the
refrigeration cycle that leads to breakage and even injury.

AIR PURGE

Lo

Hi

Gauge manifold

Service hose

Vacuum pump

Connecting pipe

Blank cap

Hexagon wrench

3-way valve

Charging port

Cap

Service hose
with valve core

Outdoor unit

Use a 4 mm
hexagon wrench.

t

(1) Remove the cap, and connect the gauge manifold and the vacuum

pump to the charging valve by the service hoses.

(2) Vacuum the indoor unit and the connecting pipes until the pressure

gauge indicates –0.1 MPa (–76 cmHg).

(3) When –0.1 MPa (–76 cmHg) is reached, operate the vacuum pump

for at least 60 minutes.

(4) Disconnect the service hoses and fit the cap to the charging valve to

the specified torque.

(5) Remove the blank caps, and fully open the spindles of the 3-way valves

with a hexagon wrench [Torque: 6~7 N·m (60 to 70 kgf·cm)].

(6) Tighten the blank caps of the 3-way valve to the specified torque.

 CAUTION

Use a clean gauge mani-
fold and charging hose
for R410A exclusively.

ELECTRICAL WIRING (OUTDOOR UNIT)

(1) Service cover removal

Remove the two mounting screws.

Remove the service cover by pushing downwards.

(2) Fasten the power supply cord and the connection cord to the conduit

holder using the lock nut.
(open the knock out holes if necessary)

(3) Connect the power supply cord and the connection cord to terminal.
(4) Fasten the power supply cord and connection cord with cord clamp.

Direction of the service
panel removal

Service cover

Hook
(3 places)

Power supply
cord or connec-
tion cord

30 mm (1-3/16")

40 mm (1-9/16")

or more

 Earth wire

Keep the earth wire longer than the other wires.

 CAUTION

Be sure to comply with local codes while running the wire
from the indoor unit to the outdoor unit (size of wire and
wiring method, etc. ).

Every wire must be connected firmly.

No wire should be allowed to touch refrigerant tubing, the
compressor or any moving part.

Loose wiring may cause the terminal to overheat or result
in unit malfunction. A fire hazard may also exist. There-
fore, be sure all wiring is tightly connected.

Connect wires to the matching numbers of terminals.

1
2
3

4
5

(L)
(N)

1
2
3

G

G

INDOOR

INDOOR UNIT

OUTDOOR UNIT

TERMINAL

DISCON-
NECT
SWITCH
(FIELD
SUPPLY)

Grounding
line

14AWG
(Inter-unit)
Power lines

230/208 V

230/208 V

230/208 V

TERMINAL

Power supply line

Single-phase, 230/208 V

CIRCUIT
BREAKER
OR FUSE
(FIELD
SUPPLY)

G

G

Control box

Terminal

Power supply cord

Connection cord
(indoor unit and
outdoor unit
connection cord)

Cord clamp

Earth screw

Indoor unit
terminal block

Outdoor unit
terminal block

Disconnect switch

Earth screw

Power supply line

G

1

2

3

4

1

2

3

4

5

G

G

 CAUTION

When connecting the power supply cord, make sure that
the phase of the power supply matches with the phase of
the terminal board. If the phases do not match, the
compressor will rotate in reverse and will not be able to
compress.

 WARNING

Disconnect switch and circuit breaker for over current pro-
tection given in the table below is to be installed between
the indoor unit and the outdoor unit.

Disconnect switch

Circuit breaker (or Fuse)

20A

240 V - 5A

Plug

Lock
nut

Inter-unit line

Power supply

(1) Outdoor unit to be fasten with bolts at the four places indicated by the

arrows without fail.

Bottom side

Drain pipe
mounting place

650 mm

(25-19/32")

4-ø 12 hole

370 mm

(14-9/16")

(2) Fix securely with bolts on a solid block. (Use 4 sets of commercially

available M10 bolt, nut and washer.)

Bolt

Nut

Block

20 to 25 N·m (200 to 250 kgf·cm)

30 to 35 N·m (300 to 350 kgf·cm)

10 to 12 N·m (100 to 120 kgf·cm)

Tightening torque

Charging port cap

9.52 mm (3/8 in.)

15.88 mm (5/8 in.)

Blank

cap

 CAUTION

1

Do not purge the air with refrigerants, but use a vacuum
pump to vacuum the installation! There is no extra re-
frigerant in the outdoor unit for air purging!

2

Use a vacuum pump and gauge manifold and charg-
ing hose for R410A exclusively. Using the same vacuum
for different refrigerants may damage the vacuum
pump or the unit.

3

After connecting the piping, check the all joints for gas
leakage with gas leak detector.

4

When inspecting gas leakage, always use the vacuum
pump for pressure. Do not use nitrogen gas.

Earth screw

05M109_9315342089_En

2006.1.12, 13:48

2

Отзывы: