OPERATION INSTRUCTION 

TECHNICAL SPECIFICATION 

1. Before  operating,  please  make  sure  the  voltage  of  power  network  is 

within  the  range  of  input  voltage  permitted  by  this  equipment,  then 
connect  the  wires  according  to  the  symbol  on  front  and  back  panel 
carefully  and  do  not  make  mistake,  make  sure  firm  grounding  .(  Input 
wire of voltage regulator of single - 500VA ~5KVA is power line) 
 

2. Turn  on  the  power  switch  of  the  voltage  regulator,  the  output  voltage 

indication of single -phase voltage regulator shall be 220V. 
 

3. When  single  -  phase  voltage  regulator  outputs  220V  and  110V  at  the 

same time, the sum of load current can't exceed the rated value. 
 

4. If  the  mains  voltage  is  lower  than198V  (see  diagram1  and  diagram  2): 

please  use  it  through  reducing  the  power  referring  to  curve  of  output 
capacity.  
 

5. When  it  is  inductive load (such  as  air  -  conditioner and  refrigerator),  as 

the  starting  current  of  inductive  load  is  very  heavy,  please  choose 
voltage regulator whose output capacity is 3-5 times of load power. For 
other  capacitive  loads,  please  leave  enough  allowance  for  output 
capacity of voltage regulator. 
 

6. After the voltage regulator is not used, please turn off the power switch 

of consumer first, then the power switch of voltage regulator. 
 

7. When mains failure happens (include loss of phase) or the input voltage 

is too high, please turn off the voltage regulator and the power switch of 
consumer in time. 
 

 
 

Product Name: 

Fujidenzo Automatic Voltage Regulator 

Model No.: 

FVR2000SC 

Rated Input Voltage: 

140V a.c. ~ 263V a.c. 

Output Voltage: 

110V a.c. ~ 220V a.c. 

Accuracy of Voltage 
Stabilization: 

220V±3%, 110V±6% 

Over-voltage Protection Value 

246±4V 

Under-voltage Indication 
Value: 

184±4V 

Frequency: 

50~60Hz 

Waveform Distortion: 

No additional waveform distortion 

Load Power Factor: 

0.8 

Efficiency: 

≥90% 

Adjusting Time: 

≤1.5s (when the input voltage has a 
change of 10%) 

Time Delay: 

Long-time delay: 5±2mins;  
Short-time delay: 5±s 

Enclosure Protection Degree: 

IP20 

Insulation Thermal Endurance 
Class: 

Class B 

Electric Strength: 

No flashover or breakdown at 2000V/min 

Insulation Resistance: 

≥5MΩ 

Содержание FVR-2000SC

Страница 1: ...t Damages caused by insects rodents accidents fire flood or other acts of God Development of rust stains cracks in any part of the body that is a normal consequence of operation The warranty is void if the serial number of the unit is removed altered or defaced If the warranty applies proof of purchase e g sales invoice or delivery receipt must be presented to the authorized service center for ver...

Страница 2: ...rt fingers foreign objects such as forks spoons etc into the AVR outlet Place the unit on a flat and stable surface Always unplug the AVR after use Always disconnect the unit from the supply if it is left unattended and before assembling disassembling or cleaning When unplugging the power cord make sure to hold the power cord Missuse of the unit can likely lead to injury Outdoor use can be dangero...

Страница 3: ...al electric worker shall be invited to clear away the dust in the machine regularly to keep the clean between carbon brush and coil grinding surface and adjust the contact pressure between them to get a fine contact against flashover if the carbon brush is worn seriously please change it in time to prevent the equipment being damaged Please repair the voltage regulator and change the parts in the ...

Страница 4: ... turn off the Delay Time Selector switch the stabilizer is under long time delay The normal work light on when it is power on the delay light out after 5 2min then the stabilizer starts to output When in the state of Over voltage protection and Under voltage indication it also takes 5 2 min for the delay light out in long time delay mode then the stabilizer back to normal output voltage Note If th...

Страница 5: ...hoose voltage regulator whose output capacity is 3 5 times of load power For other capacitive loads please leave enough allowance for output capacity of voltage regulator 6 After the voltage regulator is not used please turn off the power switch of consumer first then the power switch of voltage regulator 7 When mains failure happens include loss of phase or the input voltage is too high please tu...

Отзывы: