Thank you for purchasing the Fuji module type temperature controller. Once you have 

confirmed that this is the product you ordered, please use it in accordance with the 

following instructions.For detailed information on operating this equipment, please refer 

to the separate user's manual. Please keep this Instruction Manual within easy reach of 

persons using this equipment

Model : PUMCL

Instruction Manual (Installation)

Multi-loop Module Type Temperature Controller

Enhanced Communication Module

(CC-Link)

CAUTION

The contents of this manual are subject to change without notice. This manual is 

complied with possible care for the purpose of accuracy, however, Fuji Electric 

Systems shall not be held liable for any damages, including indirect damage, 

caused by typographical errors, absence of information or use of information in 

this manual.

Confirming Specifications and Accessories

Before using the product, confirm that it 

matches the type ordered.

(For model code, please refer to page 4.)

Confirm that all of the following 

accessories are included.

Temperature Controller Enhanced 
Communication Module (CC-Link)  

1 Unit

Instruction Manual 

1 copy

Internal Communication Termination  

Resistance (100 Ω) 

1 Unit

Related Information

Refer to "Module Type Temperature 

Controller Enhanced Communication 

Module (CC-Link) User's Manual" for 

details about the items described in this 

manual.

Content

Material 

name

Material No.

Specification

Catalog

ECNO 1162

Operating 

instruction

CC-Link 

Module

User’s 

Manual

INP-

TN5A0200-E

Please Read First (Safety Warnings)

Please read this section thoroughly before using, and observe the mentioned safety 

warnings fully.

Safety warnings are categorized as “Warning”, “Caution” or “Risk of Electrical Shock”.

 Warning Improper use of the equipment may result in death or serious injuries.

 Caution

Improper use of the equipment may cause injury to the user or property 

damage.

  Risk of

Electrical

 

Shock

Indicates that a risk of electrical shock is present and the associated 

warning should be observed.

 Warning

1-1  Installation and Wiring

 

-

This equipment is intended to be used under the following conditions.

Ambient temperature

-10 to 50 degree C

Ambient humidity

90% RH or below (with no condensation)

Vibration

10 to 70Hz less than 9.8m/s² (1G)

Warm-up time

30 min. or more

Installation category

IEC1010-1: class II

Pollution level

IEC1010-1: degree 2

 

-

Note that the insulation class for this equipment is as follows. Before installing, 

please confirm that the insulation class for the equipment meets usage requirements.

 

Power 

SLD/FG terminal (CC-Link connecting terminal)

 

Loader communication 

CC-Link communication

Functional insulation (AC1000V)

Functional insulation (AC500V)

Functional insulation (AC50V)

 

-

In cases where damage or problems with this equipment may lead to serious 

accidents, install appropriate external protective circuits.

 

-

To prevent damage and failure of the equipment, provide the rated power voltage.

 

-

To prevent electric shock and equipment failure, do not turn the power ON until all 

wiring is complete.

 

-

Before turning the power ON, confirm that clearance space has been secured to 

prevent shock or fire.

 

-

Do not touch the terminal while the machine is ON. Doing so risks shock or 

equipment errors.

 

-

Never disassemble, convert, modify or repair this equipment. Doing so risks abnormal 

operation, shock or fire.

 

-

All of the wiring should be class 1 type wiring or the low voltage wires are routed 

separately from the hazardous voltage wires to ensure separation of circuits.

 

-

When using a AWG-16 cable, you should use the crimp terminal that material 

thickness is 0.9mm or less.

1-2  Maintenance

 

-

When installing or removing the equipment, turn the power OFF. Otherwise, shock, 

operational errors or failures may be caused.

 

-

Periodic maintenance is recommended for continuous and safe use of this 

equipment.

 

-

Some parts installed on this equipment have a limited life and/or may deteriorate with 

age.

 

-

The warranty period for this unit (including accessories) is one year, if the product is 

used properly.

 Caution

2-1  Cautions when Installing

For install in UL listed enclosure only.

Please avoid installing in the following locations.

 

-

Locations in which the ambient temperature falls outside the range of 0 to 50 degree 

C when equipment is in use.

 

-

Locations in which the ambient humidity falls outside the range of 45 to 85% RH 

when equipment is in use.

 

-

Locations with rapid temperature changes, leading to dew condensation.

 

-

Locations with corrosive gases (especially sulfide gas, ammonia, etc.) or flammable 

gases.

 

-

Locations with vibration or shock directly.

 

-

Locations in contact with water, oil, chemicals, steam or hot water.

 

(If the equipment gets wet, there is a risk of electric shock or fire, so have it inspected 

by Fuji distributor.)

 

-

Locations with high concentrations of atmospheric dust, salt or iron particles.

 

-

Locations with large inductive interference, resulting in static electricity, magnetic 

fields or noise.

 

-

Locations in direct sunlight.

 

-

Locations that build up heat from radiant heat sources, etc.

 

-

A switch or circuit Breaker shall be included in the building installation.

 

Please be it in close proximately to the equipment and within easy reach of the 

operator, and mark it as the disconnecting device for the equipment.

2-2  Cautions when Attaching to DIN rails

 

-

In case of mounting the temperature controllers to DIN rails, remember to push up 

the locking tabs to fasten the controllers onto DIN rail.

 

-

To connect controllers, first release all locking tabs. Then, connect controllers and 

push up all locking tabs. Make sure that all locking tabs are fastened.

 

-

Never fail to turn the power OFF, before detaching the terminal block or removing the 

main unit from the base part.

 

-

In order to aid heat dissipation, do not block the top and the bottom of the equipment.

 

-

When mounting / dismounting controllers to / from DIN rails, 30mm of clearance 

above and under the controllers should be provided.

 

-

Do not use the terminal screws other than those supplied with this product.

2-3  Cautions for Wiring

 

-

For wiring to terminal blocks, apply crimp terminals for M3 screw.

Screw size 

: M3 x 7 (with square washer)

Screw tightening torque : 0.78 N•m (8 kgf•cm)

 

-

To avoid noise conductor effects, input signal wires should be separated from electric 

power lines or load lines.

 

-

To comply with CE marking (EMC), we recommend to attach ferrite core to 

communication cable and power cable.

2-4  Error Operation

 

-

The alarm function does not work properly when an error occurs unless the settings 

are made correctly. Always verify its setting before operation.

2-5  Others

 

-

Please do not wipe the equipment with organic solvents such as alcohol or benzene, 

etc. If wiping is necessary, use a neutral cleaning agent.

 

-

Do not use mobile phones near this equipment (within 50cm). Otherwise a 

malfunction may result.

 

-

Malfunctions may occur if the equipment is used near a radio, TV, or wireless device.

 

-

This equipment requires approx. 20 seconds before it starts to output.

 

-

Before installing and wiring, take necessary measures for electrostatic discharge 

(ESD).

- 1 -

Part names and Functions

 

-

Enhanced communication module controller

LOADER

PUM-C

LED indicator

Loader communication port

Station No. 
Configuration switch
See [Setting]

Input/output 
terminal block
See [Wiring]

PWR

BUS

L.RUN

L.ERR

SD

RD

STATION No.

7

6

5

4

3

2

1

0

9

8

x10

7

6

5

4

3

2

1

0

9

8

x1

LED indicator

Three color LED lamps indicate the following operational conditions.

LED

Green

Red

Orange

PWR

(In priority order)

OFF:  Power is OFF

Flash:  In a (0.4-second) 

cycle:

 

1: Modules detected 

by initial polling: 0

 

2: After initial polling, 

an inter-module 

communication 

error occurs

Flash:  In a (0.1 second) 

cycle: Initial polling

ON:  Running

BUS

ON:  Receiving by 

inter-module 

communication 

ON:  Transmitting by 

inter-module 

communication

L. RUN

ON:  Data linking

OFF:  H/W resetting, or 

data linking not 

performed

L.ERR

ON:  Communication error 

(CRC error, Station 

number setting error, 

communication 

speed setting error)

OFF:  Receiving normally, 

or while H/W 

resetting

Flash:  Setting switches 

during the power ON

SD

ON:  Transmitting the 

 

CC-Link data

RD

ON:  Receiving the 

 

CC-Link data

 

-

Base part

Mounting screw hole

Module connector

Mounting screw hole

See  [Mounting]

Locking tab

Power terminal block
See [Wiring] 

Module connector
(Connect modules laterally)

Setting

 

-

Setting CC-Link Station No.

Station No. of CC-Link can be set using the Station No. configuration switch. Setting 

range is 1 to 61.

Apply a fine tip flat-head screwdriver to turn the Station No. configuration switch.

x10 :
High order setting
(set value x 10)

x1 :
Low order setting
(set value x 1)

Setting range :
1 to 61
(factory-set value = 0)

STATION No.

7

6

5

4

3

2

1

0

9

8

x10

7

6

5

4

3

2

1

0

9

8

x1

LOADER

PUM-C

PWR

BUS

L.RUN

L.ERR

SD

RD

STATION No.

7

6

5

4

3

2

1

0

9

8

x10

7

6

5

4

3

2

1

0

9

8

x1

 

-

CC-Link communication can not perform with the factory-set value (0). Make sure to 

set the Station No..

 

-

When selected 0 or over 62, a Station No. selection error will occur and [L.ERR] LED 

will be ON. 

 

-

Setting CC-Link Communication speed.

Communication speed of CC-Link can be set using the station number configuration 

switch on the back of the controller.

Apply a fine tip flat-head screwdriver to turn the Station No. configuration switch.

0 1

 2 3 4

 5 6

 7 

CC-Link

communication

speed setting

Communication speed and maximum transmission distance 

 

(when using Ver.1.10 compliant CC-Link special cable)

Communication speed 

setting

Communication speed

Max. transmission distance

 (Max. Network Length)

0

156kbps

1200m

1

625kbps

900m

2

2.5Mbps

400m

3

5Mbps

160m

4

10Mbps

100m

 

-

When 5 to 9 are selected, a communication speed sellection error will occur and 

[L.ERR] LED will be ON.

 

-

Setting No.of stations occupied / Extended cyclic

No.of stations occupied/Extended cyclic can be set using the dip switch (SW1 to SW4) 

on the back of the controller.

1    2    3    4    5    6

No.of stations occupied / 

Extended cyclic setting

SW1

SW2

SW3

SW4

No.of stations occupied, Extended cyclic 

(No.of Ch)

Compliant 

Ver.

OFF

OFF

OFF

OFF

4 stations occupied x 1  (8Ch)

Ver.1

ON

OFF

OFF

OFF

4 stations occupied x 1  (16Ch)

OFF

ON

OFF

OFF

4 stations occupied x 2  (16Ch)

Ver.2

ON

ON

OFF

OFF

4 stations occupied x 2  (32Ch)

OFF

OFF

ON

OFF

4 stations occupied x 4  (32Ch)

ON

OFF

ON

OFF

4 stations occupied x 4  (64Ch)

 

-

If the setting of the dip switch is other than those above, the actual setting will be "4 

stations occupied x 1 (8Ch)"

- 2 -

INP-TN1PUMCLb-E