![Fuji Electric POD UG Series Скачать руководство пользователя страница 66](http://html1.mh-extra.com/html/fuji-electric/pod-ug-series/pod-ug-series_user-manual_2341805066.webp)
7
1. Error Message
7-1
Error Co
1.
Error Message
There are five kinds of error messages displayed on the POD:
1.
Communication error
2.
Check
3.
Warning
4.
SYSTEM ERROR
5.
Touch switch is active
1.
Communication Error
* If the above error messages are displayed on the unit without establishing communication
between POD and PLC, test the solution of remark “1.”
If the error occurs suddenly in communication, test the solution of remark “2.”
SYSTEM
F2
F3
F4
F5
F1
POWER
MENU
Communication Error
Time-Out
SYSTEM
F2
F3
F4
F5
F1
POWER
* When you go to [Comm. Parameter], bring
up the [Detail] tab window and set [Continue]
for [Comm. Err. Handling], a screen like the
one shown below is displayed.
Error Message
Contents
Solution
Remarks
Time-Out
Although a request to send is given to
the PLC, no answer is returned within
the specified time.
1. Check the communication parameters.
2. Check the cables and wiring.
1
3. Data may be disrupted because of noise.
Fix noise.
2
Parity
An error occurred in parity check.
1. Check the cables and wiring.
1
2. Data may be disrupted because of noise.
Fix noise.
2
Framing
Although the stop bit must be [1], it is
detected as [0].
1. Check the communication parameters.
2. Check the cables and wiring.
1
3. Data may be disrupted because of noise.
Fix noise.
2
Overrun
After one character is received, the next
character is received before internal
processing is completed.
1. Check the communication parameters.
1
2. Data may be disrupted because of noise.
Fix noise.
2
Check Code
The check code in the PLC response
was not correct.
1. Check the communication parameters.
1
2. Data may be disrupted because of noise.
Fix noise.
2
Содержание POD UG Series
Страница 9: ...11 Features 2 Models and Peripheral Equipment 3 System Composition Overview...
Страница 15: ...1 6 3 System Composition Please use this page freely...
Страница 28: ...2 12 5 Modular Jack MJ1 Please use this page freely...
Страница 29: ...31 Mounting Procedure 2 Power Supply Cable Connection Installation...
Страница 32: ...41 Coin type Lithium Battery UG221H SR4 and LR4 only 2 DIP Switch Setting 3 Function Switches Instructions...
Страница 48: ...61 Operational Procedures 2 Main Menu Screen Simple POD Operations...
Страница 65: ...71 Error Messages 2 Troubleshooting Error Correction...
Страница 72: ...81 Inspection and Maintenance 2 Warranty Policy Inspection and Maintenance...