- 2 - 

 

Preface 

Thank you for purchasing our SX bus interface card "OPC-VG1-SX." 

The  interface  card  is  used  to  connect  our  high-performance,  vector  control  FRENIC-VG  series  of  inverters  to  a 
SX-BUS network. Mounting this interface card on your FRENIC-VG allows you to connect the FRENIC-VG to a Fuji 
MICREX-SX series of programmable logic controllers and control it as a slave unit using run and speed commands, 
and accessing function codes. 

This interface card can be connected to D-port of option connection ports on the FRENIC-VG. 

This instruction manual does not contain the description of function codes, troubleshooting information, or handling 
instructions  of  the  inverter  and  the  MICREX-SX  series.  Read  through  this  manual  in  conjunction  with  the 
FRENIC-VG Instruction Manual and User's Manual to become familiar with proper handling and operation. Improper 
handling might result in incorrect operation, a short life, or even a failure of the interface card. 

Keep this manual in a safe place. 

Related Publications 

Listed below are the other materials related to the use of the SX bus interface card "OPC-VG1-SX." Read them in 
conjunction with this manual as necessary. 

•  FRENIC-VG User's Manual 
•  FRENIC-VG Instruction Manual 

The materials are subject to change without notice. Be sure to obtain the latest editions for use. 

 

•  Read  through  this  instruction  manual  to  become familiar with  this product  before proceeding with  installation, 

connections (wiring), operation, or maintenance and inspection. 

•  Improper handling might result in incorrect operation, a short life, or even a failure of this product as well as the 

motor. 

•  Deliver  this  manual  to  the  end  user  of  this  product.  Keep  this  manual  in  a  safe  place  until  this  product  is 

discarded. 

 

 Safety precautions 

Read  this  manual  thoroughly  before  proceeding  with  installation,  connections  (wiring),  operation,  or  maintenance 
and inspection. Ensure you have sound knowledge of the device and familiarize yourself with all safety information 
and precautions before proceeding to operate the inverter. 
Safety precautions are classified into the following two categories in this manual. 

 

Failure  to  heed  the  information  indicated  by  this  symbol  may  lead  to  dangerous 
conditions, possibly resulting in death or serious bodily injuries. 

 

Failure  to  heed  the  information  indicated  by  this  symbol  may  lead  to  dangerous 
conditions,  possibly  resulting in minor  or  light bodily  injuries  and/or  substantial  property 
damage. 

 

Failure to heed the information contained under the CAUTION title can also result in serious consequences. These 
safety precautions are of utmost importance and must be observed at all times. 
 

Installation and wiring 

 

 

•  Before starting installation and wiring, 

turn OFF the power and wait at least five minutes for inverters of 22 

kW or  below,  or  at  least  ten  minutes  for  those  of  30  kW  or  above

.  Make  sure  that  the  LED  monitor  and 

charging lamp are turned OFF. Further, make sure, using a multimeter or a similar instrument, that the DC link 
bus voltage between the terminals P(+) and N(-) has dropped to the safe level (+25 VDC or below). 

•  Qualified electricians should carry out wiring. 
 

Otherwise, an electric shock could occur. 

•  In  general,  sheaths  of  the  control  signal  wires  are  not  specifically  designed  to  withstand  a  high  voltage  (i.e., 

reinforced  insulation  is  not  applied).  Therefore,  if  a  control  signal  wire  comes  into  direct  contact  with  a  live 
conductor of the main circuit, the insulation of the sheath might break down, which would expose the signal wire 
to a high voltage of the main circuit. Make sure that the control signal wires will not come into contact with live 
conductors of the main circuit. 

 

Doing so could cause an accident or an electric shock. 

•  Do not use the product that is damaged or lacking parts. 
 

Doing so could cause a fire, an accident, or injuries. 

Содержание OPC-VG1-SX

Страница 1: ...1 FRENIC VG SX OPC VG1 SX FRENIC VG SX SX FRENIC VG INR SI47 1601 JE...

Страница 2: ...2 SX OPC VG1 SX FRENIC VG MICREX SX FRENIC VG FRENIC VG D port MICREX SX FRENIC VG OPC VG1 SX FRENIC VG FRENIC VG 22kW 30kW 10 LED P N DC 25V...

Страница 3: ...3 SX SX SX SX BX STOP1 STOP2 STOP3 22kW 30kW 10 LED P N DC 25V...

Страница 4: ...4 1 1 1 1 OPC VG1 SX 2 3 M3 3 3 SX MICREX SX CPU 1 2 OPC VG1 SX 1 2 1...

Страница 5: ...5 1 3 1 3 1 1 3 1 1 25 70 5 95 2 0 01 mg cm2 86 106 kPa 70 106 kPa 1 2 1 2 1 3 1 3 1 3 2 1 2 70 3 1 3 1 1 3 3 1 2...

Страница 6: ...6 2 2 1 CHARGE OFF 30A 30B 30C Y5A Y5C OFF FRN22VG1S 2J 4J 22kW FRN30VG1S 2J 4J 30kW 2 1 1 a 1 2 1 2 b 2 2 1 1 FRN22VG1S 2J 4J 22kW 2 1 2 FRN30VG1S 2J 4J 30kW a b...

Страница 7: ...7 2 2 1 CN1 D port 2 16bit a 2 b 4 3 2 1 1 2 1 2 2 2 1...

Страница 8: ...8 2011 11 141 0032 11 2 URL http www fujielectric co jp 513 8633 5520 2011 11...

Страница 9: ...dling might result in incorrect operation a short life or even a failure of this product Deliver this manual to the end user of this product Keep this manual in a safe place until this product is disc...

Страница 10: ...installation connections wiring operation or maintenance and inspection Ensure you have sound knowledge of the device and familiarize yourself with all safety information and precautions before proce...

Страница 11: ...s error occurs when the inverter is controlled via the SX bus it may cause the inverter to fail to recognize a stop command via the SX bus Make an emergency stop measure using BX Coast to a top or STO...

Страница 12: ...ccessories are also contained in the package Three screws M3 Three spacers If you suspect the product is not working properly or if you have any questions about your product contact the shop where you...

Страница 13: ...the interface card in an airtight vinyl sheet or the like for storage 3 If the interface card is to be stored in a high humidity environment put a drying agent such as silica gel in the airtight pack...

Страница 14: ...tion of electric shock Shut down the power of the external equipment for prevention of electric shock Remove the front cover from the inverter as shown below The removal procedure differs depending on...

Страница 15: ...so that connector CN1 on the card comes to be connected to connector D port on the control PCB 2 Secure the interface card with two screws a that come with the option through holes and then set four s...

Страница 16: ...mprovement The purpose of this instruction manual is to provide accurate information in handling setting up and operating of the SX bus interface card Please feel free to send your comments regarding...