11.2.3 Leakage current of EMC-complaint filter (optional)
Table 11.1 Leakage Current of EMC-compliant Filter (optional)
Inverter type
Leakage current (mA)
*1 to *4
For Japan
For other countries
Filter type
Normal
Worst
FRN5.5C2S-2J
FRN0025C2S-2U
FRN7.5C2S-2J
FRN0033C2S-2U
FS5956-53-52
11
*1
11
*1
FRN11C2S-2J
FRN0047C2S-2U
FRN15C2S-2J
FRN0060C2S-2U
EFL-15SP-2
20
*1
20
*1
FRN5.5C2S-4J
FRN0013C2S-4U
FRN7.5C2S-4J
FRN0018C2S-4U
FS21559-24-07-1
4
*2
59
*2
FRN11C2S-4J
FRN0024C2S-4U
FRN15C2S-4J
FRN0030C2S-4U
FS21312-44-07 4
*3
167
*3
*1) The values are calculated assuming the power supplies of three-phase 240 V (50 Hz).
*2) The values are calculated assuming the power supplies of three-phase 400 V (50 Hz).
*3) The values are calculated assuming the power supplies of three-phase 480 V (50 Hz).
*4) The worst condition includes a phase loss in the supply line.
11.4 Compliance with the Low Voltage Directive in the EU
11.4.1 General
General-purpose inverters are regulated by the Low Voltage Directive in the EU. Fuji Electric has
obtained the proper certification for the Low Voltage Directive from the official inspection agency. Fuji
Electric states that all our inverters with CE marking are compliant with the Low Voltage Directive.
11.4.2 Points for consideration when using the FRENIC-Mini series in a system to be
certified by the Low Voltage Directive in the EU
If you want to use the FRENIC-Mini series of inverters in systems/equipment in the EU, refer to the
guidelines given below.