E codes (Extension terminal functions)
2.3.2
E01 to E08
Command Assignment to [X1] to [X8]
E98 and E99
(Command Assignment to [FWD] and [REV])
E01 to E08, E98 and E99 allow you to assign commands to terminals [X1] to [X8], [FWD], and
[REV] which are general-purpose, programmable input terminals.
These function codes may also switch the logic system between normal and negative to define how
the inverter logic interprets either ON or OFF status of each terminal. The default setting is normal
logic system "Active ON." Following table show the commands that can be assigned with the
general-purpose programmable input terminals [X1] to [X8], [FWD], and [REV]. Explanations for
the commands that follow are given in normal logic system "Active ON."
To the general-purpose programmable input terminals, you can assign commands to the switching
means for the run command and its operation, the reference speed (pre-ramp) and the motor drive
power.
Be aware of that switching of any of such signals may cause a sudden start (running) or an abrupt
change in speed.
An accident or physical injury may result.
Function code data
Terminal commands assigned
Symbol
Active ON
Active OFF
0
1000
Select multistep speed 1
SS1
1
1001
Select multistep speed 2
SS2
2
1002
Select multistep speed 4
SS4
3
1003
Select multistep speed 8
SS8
7
1007
Enable coast-to-stop
BX
8
1008
Reset alarm
RST
1009
9
Enable external alarm trip
THR
10
1010
Enable jogging operation
JOG
24
1024
Enable communications link via RS485 or CAN
LE
25
1025
Universal DI
U-DI
27
1027
Enable PG vector control
PG/Hz
60
1060
Select torque bias 1
TB1
61
1061
Select torque bias 2
TB2
62
1062
Hold torque bias
H-TB
63
1063
Enable battery operation
BATRY
64
1064
Start creepless operation
CRPLS
65
1065
Check brake control
BRKE
1066
66
Force to decelerate
DRS
67
1067
Start unbalance load compensation
UNBL
69
-
Magnetic pole position offset tuning command
PPT
80
1080
Customizable logic Cancel
CLC
81
1081
Customizable logic All timer clear
CLTC
98
-
Run forward (Exclusively assigned to [FWD] and
[REV] terminals by E98 and E99)
FWD
99
-
Run reverse (Exclusively assigned to [FWD] and
[REV] terminals by E98 and E99)
REV
100
-
No function assigned
NONE
2-50
Содержание Frenic lift
Страница 1: ...LM2A series Reference Manual INR SI47 1909a E...
Страница 7: ......
Страница 13: ......
Страница 51: ...2 38...
Страница 221: ......
Страница 242: ...3 4 Programming Mode Chap 3 OPERATION USING TP A1 LM2 Figure 3 14 Screen transition for Op Monitor display example 3 21...
Страница 252: ......
Страница 254: ...URL http www fujielectric com...