PID SET UP WITH FRENIC Eco series inverter. 

8

Note: if these functions are set up with the same data, the operation priority is given 
in the following order E61 > E62 > E63.  
 
J03. PID control (P-gain). 
This parameter is used to set the proportional (P) gain of the PID controller. 
This parameter has to be tuned on site, the value depends on the application. 
Factory setting is 0.10. 
 
J04. PID control (I-gain). 
This function is used to set the integral (I) time of the PID controller. 
This function has to be tuned on site, the value depends on the application. 
Factory setting is 0.0 s; with this value the PID will not work properly. 
 
J05. PID control (D-gain). 
This function is used to set the derivative (D) gain of the PID controller. 
This function has to be tuned on site, the value depends on the application. 
Factory setting is 0.00 s. 
 
J06. PID control (Feedback filter). 
This function is used to set the time constant of the filter for PID control feedback 
signal, in seconds. 
This function has to be tuned on site, the value depends on the application. 
Factory setting is 0.5 s. 
 
The following 3 parameters are especially designed for pump applications. 
These function codes specify the data for the slow flowrate stop in pump control, a 
feature that stops the inverter when there is no water consumption. 
 

Slow flowrate stop function 

 
When the discharge pressure has increased, decreasing the reference frequency 
(output of the PID processor) below the stop frequency for slow flowrate level (J15) 
for more than the elapsed stopping time on slow flowrate level stop latency (J16), the 
inverter decelerates to stop, while PID control itself continues to operate. When the 
discharge pressure decreases, increasing the reference frequency (output of the PID 
processor) above the starting frequency (J17), the inverter resumes operation. 
If we need to have a signal indicating the state in which the inverter is stopped due to 
the slow flowrate stop feature, we have to assign PID-STP function (Inverter stopping 
due to slow flowrate under PID control ) to one of the general-purpose output terminal 
(function code data = 44).  
 
J15. PID Control (Stop frequency for slow flowrate).  
Specifies the frequency which triggers slow flowrate stop of inverter. 
Factory setting is 0 Hz. 
 
J16. PID Control (Slow flowrate level stop latency). 
Specifies the elapsed time from when the inverter stops operation due to slow 
flowrate level condition. 
Factory setting is 30 s. 
 

Содержание Frenic Eco Series

Страница 1: ...ng more Preferably 1 5 times more i e 3 Bar Does it have an output signal that can be connected directly to the FRENIC Eco input FRENIC Eco has inputs for 0 10 V and 4 20 mA signals 3 PID Basics 3 1 P...

Страница 2: ...P part only depends on the momentary difference error between the set value and the feedback The drawback using only a P controller is that the more the feedback signal approaches the set value the sm...

Страница 3: ...t Base frequency 1 This function sets the rated value of the voltage output to motor 1 in volts Note that a voltage greater than the supply input voltage cannot be output Factory setting is 400 V F06...

Страница 4: ...miter Low This function sets the lower limit for the setting frequency in Hz Recommended value for PID control is zero or at least very low Factory setting is 0 Hz Motor parameters P01 Number of motor...

Страница 5: ...d current This function sets the no load exciting current of motor 1 in Amperes Factory setting depends on the inverter size P07 Motor 1 R1 setting This function sets the primary resistance R1 of moto...

Страница 6: ...Function This function is used to setup the function that will be displayed in the LED display during operation The alternatives related with the PID controller are 10 PID process command value 12 PID...

Страница 7: ...ommand 1 3 Enable terminal command up down control 4 Command via communication link When setting J02 to 1 we have to specify the source of this command In order to do so we have to program one of the...

Страница 8: ...gned for pump applications These function codes specify the data for the slow flowrate stop in pump control a feature that stops the inverter when there is no water consumption Slow flowrate stop func...

Страница 9: ...f the system is 4 Bar Measure or estimate the time lag between the process control and the feedback signal of the process It is important to anticipate on the time lag of the process or instability ca...

Страница 10: ...ment To check that PID command and or PID feedback signals are connected properly to the inverter select option 4 I O CHECK from the Multifunction Keypad TP G1 menu and then go to the fifth screen pus...

Страница 11: ...ime 1 E40 7 00 7 bar max E41 0 00 0 bar min E43 10 PID set point value PID parameters J01 1 PID active forward operation J02 0 PID set value from keypad E62 5 PID feedback value by current input C1 J0...

Страница 12: ...parameters J01 1 PID active forward operation J02 1 PID set point by PID process command 1 E62 3 PID process command 1 assigned to terminal 12 E63 5 PID feedback value assigned to terminal C1 J03 PID...

Отзывы: