9
ENGINEERING DATA
MODEL
75
100
125
150
200
250
300
400
500
SPECIFICATIONS
Rated Capacitya
- (scfm)
75
100
125
150
200
250
300
400
500
Inlet /Outlet Connections - (inches)
3/4
1
1
1
1-1/2
1-1/2
1-1/2
2
2
Dimensions
Height - (inches)
20.1
20.6
20.6
20.6
30.0
30.0
29.9
29.9
31.5
Length - (inches)
19.7
28.3
28.3
28.3
35.4
35.4
37.4
37.4
41.3
Width - (inches)
18.9
13
13
13
16.1
16.1
19.3
19.3
23.2
Power Supply - (V/Ph/Hz)
115/1/60 115/1/60 115/1/60 115/1/60 460/3/60 460/3/60 460/3/60 460/3/60 460/3/60
Refrigerant Compressor Capacity
c
-
(BTU / hr)
3,414
3,953
3,953
5,406
8,787
13,969
13,969
17,574
22,151
Input Power - (kW)
0.72
0.74
0.76
1.11
1.42
1.98
2.05
2.50
3.06
Refrigerant Type
b
R-134a
R-134a
R-134a
R-134a
R-134a
R-134a
R-134a
R-134a
R-134a
a Rating c
onditions are 100°F inlet temperature, 100 psig inlet pressure, 100% inlet relative humidity, 100°F ambient temperature @ 60Hz. Per CAGI ADF-100.
b
Refer to dryer data plate for refrigerant charge.
c
Compressor capacity @35°F evaporating temperature, 130°F condensing temperature
.
MINIMUM - MAXIMUM OPERATING CONDITIONS
ALL MODELS
Min.-Max. Inlet Air Pressure (compressed air at inlet to dryer)
10 - 232 psig
Min.-Max. Inlet Air Temperature (compressed air at inlet to dryer)
40°F - 120°F
Min.-Max. Ambient Temperature
40°F - 110°F
NOTE:
Continuous operation in the above maximum and minimum operation conditions is not allowable.
SUCTION PRESSURE
REFRIGERANT PRESSURE SWITCH SETTINGS
Refrigerant
Without Airflow
Models 75 to 500
R-134a
31 psig
Fan Cycle Control
Fan Pressure Switch Setting
R-134a
Cut-In
Cut-Out
199 psig
142 psig
Models 200 to 500
Refrigerant Compressor Control
High Pressure Switch Setting
Sensor Location
R-134a
Cut-Out
Cut-In
Compressor Discharge
298 psig
Manual Reset
201 psig
Содержание RNP Series
Страница 15: ...15 ...