![Fronius Tauro 50-3-D Скачать руководство пользователя страница 8](http://html1.mh-extra.com/html/fronius/tauro-50-3-d/tauro-50-3-d_quick-start-manual_2339251008.webp)
Spread strings evenly
on all input sections
Eco 99-3-D / Eco 100-3-D
String Input
each max. 14.5 A
PV1 / PV2 / PV3
each max. 75 A
PV1 + PV2 + PV3
max. 175 A
Max. short-circuit current
(I
SC
PV = I
SC
max):
20 A
Eco 50-3-D
String Input
each max. 14.5 A
PV1 / PV2
each max. 75 A
PV1 + PV2
max. 87.5 A
50-3-D
String Input
each max. 14.5 A
PV1 / PV2 / PV3
36A / 36A / 72A
PV1 + PV2 + PV 3
max. 134 A
32b
DC= Variant MC4
31
DC=
Max. PV array to earth capacitance (nF)
Tauro 50-3-D / Tauro 50-3-P /
Tauro Eco 50-3-D / 50-3-P
10000 nF
Tauro Eco 99-3-D /
Tauro Eco 99-3-P
19998 nF
Tauro Eco 100-3-D /
Tauro Eco 100-3-P
20000 nF
DC OFF
PV lines must be fused in a combiner
box before the inverter!
Max. short-circuit current per Input
(I
SC
PV1 / PV2 / PV3 = I
SC
max): 125 A
Eco 50-3-P
PV1 / PV2
each max. 75 A
PV1 + PV2
max. 87.5 A
50-3-P
PV1 / PV2 / PV3
36A / 36A / 72A
PV1 + PV2 + PV 3
max. 134 A
Eco 99-3-P / Eco 100-3-P
PV1 / PV2
each max. 100 A
PV1 + PV2
max. 175 A
33a
34a
DC= Variant Precombined
35a
36a
DC OFF
Cable cross section:
25 - 95 mm²
32a
Содержание Tauro 50-3-D