EN-US
The Basic menu
Accessing the
Basic Menu
The Basic menu is displayed.
Use the ‘plus’ or ‘minus’ keys
to select the desired entry
Press the ‘Enter’ key
to edit the selected entry
Press the ‘Esc’ key
Basic Menu En-
tries
Press the ‘Menu’ key
The menu level is displayed.
Press the unassigned ‘Menu/Esc’ key
5 times
In the "CODE" menu, the "Access Code" is dis-
played; the first digit flashes.
Enter code 22742: Use the ‘plus’ or ‘minus’
keys
to select the first digit of the code
Press the ‘Enter’ key
The second digit flashes.
Repeat steps 3 and 4 for the second, third,
fourth, and fifth digit of the code until...
the set code flashes.
Press the ‘Enter’ key
1
2
3
4
Access Code
5
6
7
8
9
The Basic menu contains the following parameters important for the installation and op-
eration of the inverter:
MPP Tracker 1
-
DC operating mode: MPP AUTO / FIX / MPP USER
-
MPP AUTO: normal operating status; the inverter automatically searches for the
optimal operating point
-
FIX: enter a fixed DC voltage used by the inverter. Enter the fixed voltage value
in the fixed voltage point.
-
MPP USER: enter the lower MPP voltage from which the inverter searches for
its optimal operating point. Enter this start value for the MPPT start voltage.
-
Dynamic Peak Manager: ON/OFF
-
Fixed voltage: enter the fixed voltage for the FIX function
-
MPPT start voltage: enter the start voltage for the MPP USER function