Performing a re-
set after a rapid
shutdown
To restart the PV system after a rapid shutdown:
-
If the signal line to the inverter is closed, there must be an AC connection
present to restart the PV system.
-
Open the switch that was used to trigger the rapid shutdown
-
Check all other external switches in the signal loop to see if they are closed.
Self-test
A self-test of the rapid shutdown function (RSD) can only be performed manu-
ally. The self-test only affects the discharge circuit of the Rapid Shutdown Box.
Manual self-test sequence:
A manual self-test can be triggered by an interruption of the AC connection (e.g.:
AC breaker).
The discharge of the Rapid Shutdown Box must be measured and checked using
a multimeter.
The Error-Code
“AC_SystemFailure”
is shown on the display of the inverter.
10
Содержание Rapid Shutdown Box Duo
Страница 2: ......
Страница 13: ...Attaching the Rapid Shutdown Box to the wall 1 2 3 Fasteners not included 4 5 13 EN US...
Страница 14: ...Connecting the Rapid Shutdown Box Wiring of the Rapid Shutdown Box Duo 1 2 3 8 10 4 5 6 14...
Страница 24: ...24...
Страница 35: ...Montage de la Rapid Shutdown Box sur le mur 1 2 3 Mat riel de fixation non inclus 4 5 35 FR...
Страница 36: ...Raccorder la Rapid Shutdown Box C bler la Rapid Shutdown Box Duo 1 2 3 8 10 4 5 6 36...
Страница 46: ...Raccordement de 5 cha nes de modules solaires au Fronius Primo GEN24 208 240 46...
Страница 57: ...Fijar la Caja de cierre r pido a la pared 1 2 3 No se incluyen los sujetadores 4 5 57 ES MX...
Страница 58: ...Conexi n de la Caja de cierre r pido Cableado de la Caja de cierre r pido Duo 1 2 3 8 10 4 5 6 58...
Страница 69: ...69 ES MX...
Страница 70: ...70...
Страница 71: ...71 ES MX...
Страница 72: ......