FROMM
CH12-TI-FS250.EN10
How to change the inverters parameters.
When the inverter is in running mode the LED on is FREF (
1
)
In order to enter in programm mode push the cycle button (
2
) until the LED PRGM (
3
) becomes ON
On the display there is now
n01
, in order to enter another parameter push on the button (
4
) and (
5
)
Pushing the button (
6
) we enter in the actual parameter program, in order to change the values use
the buttons (
4
) and (
5
) and memorize it with (
6
)
With the button (
2
) you can turn-off the LED PRGM (
3
) and turn-on FREF (
1
)
STANDARD INVERTER SETTINGS
INVERTER OMRON
SETTINGS
Turntable
Carriage
Pre - stretch
N01 Initialization
1
1
1
N02
Selection for the run control
1
1
1
N03
Selection for reference frequency
2
2
2
N09
Max. output frequency
55.00
60.00
90
N10
Max. voltage
230
230
230
N16
Acceleration ramp time
6.00
0.3
0.3
N17 Deceleration
ramp
time
3.00
0.1
0.3
N30
Upper output frequency limit
100
100
100
N31
Lower output frequency limit
8
30
0
N40
Assignment for the multifunctional exit
0
0
0
After installation of a NEW inverter please do not forget to start the inverter
first!
Otherwise the inverter will never work!!!
Start up procedure to decrease the intervent threshold with alarm Uul
N01 = 15
N97 = 2 + 10 = 12
N01 = 20
N01 = 12
Usefull to know !
Before maintenance ore trouble shooting always check the digital inputs of the machine. No digital
input mostly the connect switch is broken en has to be replaced. Always check the connections very
thoroughly.
Or check the latest version at the website
www.fromm-stretch.com
Instruction FLASH MCU Programmer for F2MC-16LX.pdf
INVERT
E
R SETTING FS 250 - 270