Fromm FS 250 Скачать руководство пользователя страница 6

FROMM

 

CH12-TI-FS250.EN10

 

 
 
How to change the inverters parameters. 
 

When the inverter is in running mode the LED on is FREF (

1

In order to enter in programm mode push the cycle button (

2

) until the LED PRGM (

3

) becomes ON 

On the display there is now 

n01

, in order to enter another parameter push on the button (

4

) and (

5

Pushing the button (

6

) we enter in the actual parameter program, in order to change the values use  

the buttons (

4

) and (

5

) and memorize it with (

6

With the button (

2

) you can turn-off the LED PRGM (

3

) and turn-on FREF (

1

 
STANDARD INVERTER SETTINGS 
 

  

INVERTER OMRON 

  

SETTINGS 

  

  

  

Turntable 

Carriage 

Pre - stretch 

N01 Initialization 

N02 

Selection for the run control 

N03 

Selection for reference frequency 

N09 

Max. output frequency 

55.00 

60.00 

90 

N10 

Max. voltage  

230 

230 

230 

N16 

Acceleration ramp time 

6.00 

0.3 

0.3 

N17 Deceleration 

ramp 

time 

3.00 

0.1 

0.3 

N30 

Upper output frequency limit  

100 

100 

100 

N31 

Lower output frequency limit 

30 

N40 

Assignment for the multifunctional exit 

 

After installation of a NEW inverter please do not forget to start the inverter 
first! 
Otherwise the inverter will never work!!! 

 

  

Start up procedure to decrease the intervent threshold with alarm Uul 

  

N01 = 15 

 

 

  

  

N97 = 2 + 10 = 12 

 

 

  

  

N01 = 20 

 

 

  

  

N01 = 12 

  

  

  

 

Usefull to know ! 

 
Before maintenance ore trouble shooting always check the digital inputs of the machine. No digital 
input mostly the connect switch is broken en has to be replaced. Always check the connections very 
thoroughly. 
 
Or check the latest version at the website 

www.fromm-stretch.com

 

 
Instruction FLASH MCU Programmer for F2MC-16LX.pdf 

 

 

INVERT

E

R SETTING FS 250 - 270 

Содержание FS 250

Страница 1: ...me 10 0 1 sec Settings between 0 255 We also have the possibility to regulate some parameters This regulation can also be done on the inverter itself In any case it is advisebel the cheque the standar...

Страница 2: ...e B_L D_L Right side B_R D_R Notice ATTENTION NOW YOU ARE IN A SPECIAL MODE DO NOT PRESS STOP DO NOT PRESS EMERGENCY Input value T13 on the left side Input value T14 on the right side then PRESS STOP...

Страница 3: ...RUN Left 9 Turn On the machine Output on the machine display is 9 Start up the programm Flash 16 When you have started the programm you should see the screen at the next page Please see to it that all...

Страница 4: ...ne and will upload the new program which is selected When the computer is ready with the uploading it will display the message ALL OK 9 Select OK on the screen 9 Turn off the stretch wrapping machine...

Страница 5: ...FROMM CH12 TI FS250 EN10 Drawing Cabinet FS250 270 INVERTER SETTINGS FS 250 FS 270 N5 5470 2 5 4 1 6 INVERTER SETTING FS 250 270 3...

Страница 6: ...requency 2 2 2 N09 Max output frequency 55 00 60 00 90 N10 Max voltage 230 230 230 N16 Acceleration ramp time 6 00 0 3 0 3 N17 Deceleration ramp time 3 00 0 1 0 3 N30 Upper output frequency limit 100...

Страница 7: ...THE PHOTO ELECTRIC CELL IS NOT WORKING The arrised problem Possible remidies Photo electric cell is not detecting the pallet Check if the machine is not in program 6 Check parameter 0 pallet overlap C...

Страница 8: ...the emergency mushroom head button THE TURNS AT THE BOTTOM AND AT THE TOP OF THE LOAD ARE NOT REGULATED PROPERLY The arrised problem Possible remidies limit switches 1 not connected properly Check th...

Страница 9: ...le remidies This alarm signals that exerted pressure on the carriage has been detected by the microswitch that interlocks the crush proof guard Check the situation Microswitch incorrectly positioned o...

Страница 10: ...f the alarm persist if the cycle is longer than 8 minutes Increase value N34 from 8 to 12 Pr stretch not working after building in option package 16 8242 Check the connection of the wires Place the in...

Страница 11: ...rd 2 not working Replace the card COUNT SENSOR FOR CARRIAGE PHONIC WHEEL The arrised problem Possible remidies Phonic wheel sensor incorrectly positioned Check for the correct positioning of the senso...

Отзывы: