CS1030
Module for communicating with the frequency converters and for communicating in cascades and
Modbus systems. A X2X link cable is required for custom assembly.
⇨ See "Cascade / Modbus" [page 138]
LED
Colour
Status
Description
r
Green
Off
Not in operation (no power supply)
Quick flashes
Reset mode
Flashing
Preoperative mode
On
Module in operation
e
Red
Off
No error / no supply to module
On
Error or reset status
e+r
Red illuminated (e) / Green flashing (r)
Incorrect firmware
Tx
Yellow
On
The module is sending data via the RS485/RS422 interface
Rx
Yellow
On
The module is receiving data via the RS485/RS422 interface
T
Yellow
On
The terminating resistor integrated in the module is switched on
CS1030
1-1
1-2
1-3
1-4
1-5
1-6
2-1
2-2
2-3
2-4
2-5
2-6
DATA + (A)
DATA - (B)
-
GND
-
-
-
GND
-
-
-
-
Electric components and wiring
7
PLC
Service manual SPS 4000 | B0960622_en
105