User Instructions Low Temperature Freezers Model GLE

Livøvej 22 - 8800 Viborg - Tlf. 86 61 34 11 - www.frigor.dk

User Instructions  Low Temperature Freezers Model UNI/LT

9

OA1 Second relay configuration: ALr

: alarm; 

LHt

: auxiliary; 

onF

: always on;

dEF

: do not select it!.; FAn: do not select it!.;

AoP Alarm relay polarity:

 it set if the alarm 

relay is open or closed when an alarm hap-
pens. 

CL

= the relay is closed; 

oP

 = the relay 

is open

i1P Digital input polarity: oP:

 the digital input 

is activated by opening the contact; 

CL

the digital input is activated by closing the 
contact.

i1F Digital input configuration:
EAL

 = external alarm: “EA” message is dis-

played; 

bAL

 = serious alarm “

CA

” message is 

displayed. 

PAL

 = pressure switch alarm, “CA” 

message is displayed; 

dor

 = door switch 

function; 

dEF

 = activation of a defrost cycle; 

LHt

 =switch on the second relay if oA1=LHt; 

Htr

 = kind of action inversion (cooling – heat-

ing).

did:

 (0÷255 min)

with i1F= EAL or i1F = bAL digital input alarm 
delay:

 delay between the detection of the 

external alarm condition and its signalling.

with i1F= dor: door open signalling delay
with i1F = PAL: time for pressure switch func-
tion:

 time interval to

calculate the number of the pressure switch 
activation.

nPS Pressure switch number:

 (0 ÷15) Number 

of activation of the pressure switch, during 
the “did” interval, before signalling the 
alarm event (I2F= PAL). 

If the nPS activation 

in the did time is reached, switch off and on 
the instrument to restart normal regulation.

• 

odc Compressor status when open door:  

   no, Fan

 = normal; 

CPr, F_C

 = Compressor  

   OFF
OTHER

PbC Type of probe:

 it allows to set the kind 

of probe used by the instrument: 

PbC

 = PBC 

probe, 

ntC

 = NTC probe.

• rEL Software release for internal use.
• Ptb Parameter table code: readable only.

DIGITAL INPUT
The free contact digital input is program-
mable in five different configurations by the

i1F

” parameter.

DOOR SWITCH INPUT (i1F = dor)

It signals the door status and the corre-

sponding relay output status through the

odc

” parameter:

 

no, Fan

 = normal (any change);

 

CPr, F_C

 = Compressor OFF;

Since the door is opened, after the delay 
time set through parameter “

did

”, the door 

alarm is enabled, the display shows the mes-
sage “

dA

” and 

the regulation restarts

. The 

alarm stops as soon as the external digital 
input is disabled again. With the door open, 
the high and low temperature alarms are 
disabled.

GENERIC ALARM (i1F = EAL)

As soon as the digital input is activated the 
unit will wait for “did” time delay before
signalling the “

EAL

” alarm message. The 

outputs status don’t change. The alarm
stops just after the digital input is de-acti-
vated.

SERIOUS ALARM MODE (i1F = bAL)

When the digital input is activated, the unit 
will wait for “

did

” delay before signalling the 

CA

” alarm message. The relay outputs are 

switched OFF. The alarm will stop as soon as 
the digital input is de-activated.

PRESSURE SWITCH (i1F = PAL)

If during the interval time set by “

did

” pa-

rameter, the pressure switch has reached
the number of activation of the “

nPS

” pa-

rameter, the “

CA

” pressure alarm message 

will be displayed. The compressor and the 
regulation are stopped. When the digital 
input is ON the compressor is always OFF.

If the nPS activation in the did time is re- 
ached, switch off and on the instrument  
to restart normal regulation.

SWITCHING SECOND RELAY ON (i1F = LHt)

With oA1= LHt it switches on and off the 
second relay.

START DEFROST (i1F = dFr)

It starts a defrost if there are the right condi-
tions. After the defrost is finished, the normal 
regulation will restart only if the digital input 
is disabled otherwise the instrument will wait 
until the “MdF” safety time is expired.

INVERSION OF THE KIND OF ACTION: HEAT-
INGCOOLING (i1F = Htr)

This function allows to invert the regulation of 
the controller: from cooling to heating and 
viceversa.

Содержание GLE

Страница 1: ...User Instructions Low Temperature Freezers Model GLE Livøvej 22 8800 Viborg Tlf 86 61 34 11 www frigor dk Low Temperature Freezers Model GLE User Instructions mODEL gle ...

Страница 2: ...n order to avoid any injuries contact the sup plier for further information Never put naked flames or other igni tion sources inside the appliance Never touch the freezers interior or products in the freezer when the freezer is operating Use gloves or alike in order to avoid injuries frost bite Keep the key to the appliance away from the appliance and out of the reach of children 3 Connection to th...

Страница 3: ...In order for the freezer to work to its maxi mum efficiency the cabinet should be de frosted when a approx 2mm thick ice layer has formed inside the cabinet The ice layer is easily removed with a plastic or wooden scraper Never use a sharp metal object which might will cause damage to the inner liner The defrosting frequency is determined mainly by two factors the usage pattern number of lid opening...

Страница 4: ...safe storage of sensitive products In some situations the GLE freezer is also used for other applications like in laborato ries for different low temperature test Depending on the actual situation it might be necessary to change the controllers off set value in order to get a correspondence between the reading on the display and the actual temperature inside the cabinet The factory setting is an offs...

Страница 5: ...e separated and far enough from each other without crossing or intertwining In case of applications in industrial environments the use of mains filters our mod FT1 in parallel with inductive loads could be useful GENERAL DESCRIPTION Model XR30C format 32 x 74 mm is a digital termostat with off cycle defrost designed for refrigeration applications at normal temper ature It provides two relay outputs ...

Страница 6: ...taken place To see the kind of alarm the max min reached temperature and alarm duration do as follows 1 Push the Up or Down key 2 On the display the following mes sage is shown HAL for high temperature alarm LAL fot the minimum allarm followed by the Maximum mini mum temperature Then the tiM tiMe message is displayed followed by the Dura tion in h mm 3 Then the instrument displays the temperature ...

Страница 7: ...eep pressed the Set n for more than 7s The Pr2 label will be displayed immediately fol lowed from the HY parameter NOW YOU ARE IN THE HIDDEN MENU 3 Select the required parameter 4 Press the SET key to display its value Now only the LED is blinking 5 Use o or n to change its value 6 Press SET to store the new value and move to the following parameter To exit Press SET o or wait 15s without pressing...

Страница 8: ...elsius F Fahrenheit WARNING When the measurement unit is changed the SET point and the values of the parameters Hy LS US Ot ALU and ALL have to be checked and modified if necessary rES Resolution for C in 1 C dE 0 1 C allows decimal point display DEFROST IdF Interval between defrost cycles 0 120h Determines the time interval between the beginning of two defrost cycles MdF Maximum length for defrost...

Страница 9: ...input is program mable in five different configurations by the i1F parameter DOOR SWITCH INPUT i1F dor It signals the door status and the corre sponding relay output status through the odc parameter no Fan normal any change CPr F_C Compressor OFF Since the door is opened after the delay time set through parameter did the door alarm is enabled the display shows the mes sage dA and the regulation resta...

Страница 10: ... suitable external relay PROBE CONNECTION The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration It is recommended to place the thermostat probe away from air streams to correctly measure the average room temperature Place the defrost termination probe among the evaporator fins in the coldest place where most ice is formed far from heaters or from the ...

Страница 11: ... Housing self extinguishing ABS Case XR30C frontal 32x74 mm depth 60mm Mounting XR30C panel mounting in a 71x29mm panel cut out Protection IP20 Frontal protection IP65 with frontal gasket RG C optional Connections Screw terminal block 2 5 mm2 wiring Power supply according to the model 12Vac dc 10 24Vac dc 10 230Vac 10 50 60Hz 110Vac 10 50 60Hz Power absorption 3VA max Display 3 digits red LED 14 2...

Страница 12: ...alarm at start up Alarm relay silencing 2nd relay configuration Second relay polarity oA1 ALr Digital input polarity Digital input configuration Digital input delay Number of activation of pressure switch Compressor status with open door Kind of probe Software release Map code Label Name Range C F 3 0 37 2 0 4 50 0 58 110 230 0 0 0 1 0 0 15 30 CL ºC ºF dE 8 20 it 30 Ab LS US 0 1 25 5ºC 1 255ºF 50º...

Страница 13: ...p Probe selection N A N A Label Set Hy LS US Ot Ods AC CCt COn COF CH CF ldF Mdf dFd dAd Alc ALU ALL Ald dAo PbC Rel Ptb Dixell XR30C 115 volt Setting Celcius 45 3 50 0 0 1 3 0 60 5 CL C 120 0 Set 1 Ab 36 50 120 24 Ptc 3 84 Setting Farenheit 45 3 58 0 0 1 3 0 60 5 CL F 120 0 Set 0 Ab 33 58 120 24 Ptc 3 84 230 volt Ambient temperature Gross volume Gross volume Height on feet Height with open lid Wi...

Страница 14: ... Freezers Model GLE Livøvej 22 8800 Viborg Tlf 86 61 34 11 www frigor dk User Instructions Low Temperature Freezers Model UNI LT 14 Wiring diagrams Censor Power supply 230V 50 60 HZ Power supply 230V 50 60 HZ Censor GLE 10 20 30 40 GLE 50 ...

Отзывы: