Refrigerant charging

 waRning:

Single Packaged Heat Pumps are shipped fully 
charged with R-410a refrigerant and ready 
for installation. when a system is installed 
according to these instructions, no refrigerant 
charging is required. if repairs make it necessary 
for evacuation and charging, it should only be 
done by qualified, trained personnel thoroughly 
familiar with this equipment. Some local codes 
require licensed installation/service personnel 
to service this type of equipment. under no 
circumstances should the owner attempt to 
install and/or service this equipment. Failure to 
comply with this warning could result in property 
damage, personal injury, or death.

The system refrigerant charge can be checked and 
adjusted through the service ports provided at the front 
panel. Use only gauge lines which have a Schrader 
depression device present to actuate the valve.

noTeS:

• 

The unit must be charged while both first and second 
stages are operating.

• 

The refrigerant charging charts (Figures 13 - 16, 
pages 20 & 21) are applicable to listed assemblies of 
equipment and at listed airflows for the indoor coil. 

charging an R-410a unit in ac mode at outdoor 
Temperatures above 65F.
1.   With the system operating at steady-state, measure 

the liquid refrigerant pressure in psig at the service 
valve.

2.   Measure the liquid refrigerant temperature in 

Fahrenheit at the service valve.

3.    For the temperature measured, determine the required 

liquid refrigerant pressure from the appropriate 
charging charts in Figures 13 - 16.

4.  If the pressure measured in step 1 is greater than 

the required liquid refrigerant pressure determined in 
step 4, then there is too much charge in the system. 
Remove refrigerant and repeat steps 1 through 3 until 
the system is correctly charged.

System Heating
If the unit has been equipped with optional electric heater 
kits, set the thermostat's system mode to EM HEAT and 
the fan mode to AUTO. Verify the compressor and outdoor 
fan are not energized but that the blower and heaters are. 
Feel the air being circulated by the indoor blower and verify 
that it is warmer than ambient temperature. Listen for any 
unusual noises. If unusual sounds occur, determine the 
source of the noise and correct as necessary.

5.  If the pressure measured in step 1 is less than the 

required liquid refrigerant pressure determined in 
step 4, then there is too little charge in the system. 
Add refrigerant and repeat steps 1 through 3 until the 
system is correctly charged.

charging an R-410a unit in Heating mode
1.  Evacuate the refrigerant system.
2.  Weigh in the proper charge based on the charge 

level noted on the rating plate. Unit charge MUST be 
verified in cooling season.

3.  Verify the unit is operating properly as outlined in 

System Heating.

HeaT PumP mainTenance

 waRning:

To prevent electrical shock, personal injury, or 
death, disconnect all electrical power to the unit 
before performing any maintenance or service. 
The unit may have more than one electrical 
supply.

Proper maintenance is important to achieve optimum 
performance from the heat pump. The ability to properly 
perform maintenance on this equipment requires certain 
mechanical skills and tools. If you do not possess these 
skills, contact your dealer for maintenance. Consult your 
local dealer about the availability of maintenance contracts. 
Routine maintenance should include the following:

•  Inspect and clean or replace air filters at the beginning 

of each heating and cooling season, or more frequently 
if required.

•  Inspect the condensate drain and outdoor coil at the 

beginning of each cooling season. Remove any debris. 
Clean the outdoor coil as necessary using a mild 
detergent and water. Rinse thoroughly with water.

•  Inspect the electrical connections for tightness at the 

beginning of each heating and cooling season. Service 
as necessary.

 cauTion:

The unit should never be operated without a 
filter in the return air system. Replace disposable 
filters with the same type and size.

•  The motors for the circulating air blower and the outdoor 

fan are pre-lubricated at the factory. No further oiling 
is required for the life of this product.

Содержание Q4SE Series

Страница 1: ...tions and follow recommendations given If these suggestions don t eliminate your problem call your servicing contractor These instructions are primarily intended to assist qualified individuals experienced in the proper installation of this appliance Some local codes require licensed installation service personnel for this type of equipment Please read all instructions carefully before starting th...

Страница 2: ...14 Startup Adjustments 14 Pre Start Checklist 14 Start up Procedure 14 Air Circulation 14 Short Cycle Protection 14 System Cooling 14 System Heating 15 Refrigerant Charging 15 Charging an R 410A Unit in AC Mode 15 Charging an R 410A Unit in Heating Mode 15 Heat Pump Maintenance 15 Figures Tables 16 Figure 9 Q4SE Heat Pump Dimensions 16 Table 7 Center of Gravity Shipping Weights 16 Electrical Infor...

Страница 3: ... the fan mode to AUTO See Figure 1 2 Set the temperature selector to the desired temperature level The outdoor fan compressor and blower motor will all cycle on and off to maintain the indoor temperature at the desired cooling level NOTE If the temperature level is re adjusted or the system mode is reset the fan and compressor in the outdoor unit may not start immediately A protective timer circui...

Страница 4: ...s is included with the heat pump Carefully review these responsibilities with your dealer or service company The manufacturer will not be responsible for any costs found necessary to correct problems due to improper setup improper installation adjustments improper operating procedure on the part of the user etc Some specific examples of service calls which are not included in the limited warranty ...

Страница 5: ...refrigerant underhighpressure Installationorservicingshouldonly beperformedbyqualifiedtrainedpersonnelthoroughly familiar with this type equipment All electrical wiring must be completed in accordance with local state and national codes and regulations and with the National Electric Code ANSI NFPA 70 or in Canada the Canadian Electric Code Part 1 CSA C 22 1 Installation of equipment may require br...

Страница 6: ...use and or improper maintenance can shorten the life of the appliance and create unsafe hazards Toachieveoptimumperformanceandminimizeequipment failure it is recommended that periodic maintenance be performed on this unit The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools Pre Installation Check Before you install this unit the cooling load of...

Страница 7: ...al Remove the shipping carton and User s Manual from the equipment Takecarenottodamagethetubingconnections whenremovingthecarton Forrooftopinstallations remove and discard the two supports attached beneath the unit Rigging and Hoisting WARNING To avoid the risk of property damage personal injury or death it is the rigger s responsibility to ensure that whatever means are used to hoist the unit are...

Страница 8: ...f the electrical box of the outdoor unit The installer should becomefamiliarwiththewiringdiagram schematicbefore making any electrical connections to the outdoor unit Line Voltage It is recommended that the line voltage to the unit be supplied from a dedicated branch circuit containing the correct fuse or circuit breaker for the unit An electrical disconnect must be located within sight of and rea...

Страница 9: ...t upandshut downcharacteristics thesystemcan be optimized for energy efficiency humidity control and comfort The delay profile is selected by setting switches 7 8 See Table 3 page 10 Select Delay A or Delay B for highest energy efficiency Delay A has a two step ON delay The blower will begin operation at 31 airflow for 30 seconds The second step operation is 75 airflow for 30 seconds After the two...

Страница 10: ... 0 1 0 1 5 T O N 1650 1 0 0 0 1705 0 0 1 0 1710 1 1 0 1 1800 0 1 0 0 1815 1 0 1 0 1900 1 1 0 0 1980 0 1 1 0 2090 1 1 1 0 NOTE Switch settings 0 OFF 1 ON Table 3 Delay Settings all models Delay Description Switch Number 1 2 3 4 5 6 7 8 Delay A 0 0 Delay B 0 1 No Delay 1 0 De Hum 1 1 NOTE Switch settings 0 OFF 1 ON Table 2 Minimum Electric Heat Airflow all models Nominal KW CFM Switch Number 1 2 3 4...

Страница 11: ...cond compressor time delay in defrost the delay is reduced to 10 seconds in TEST mode Optional Comfort AlertTM Diagnostics Module TheComfortAlertTM DiagnosticsModuleisabreakthrough innovation for troubleshooting heat pump and air conditioning system failures The module installs easily in the electrical box of the outdoor unit near the compressor contactor By monitoring and analyzing data from the ...

Страница 12: ...LED Description POWER LED Green indicates voltage is present at the power connection of the module ALERT LED Yellow communicates an abnormal system condition through a unique flash code NOTE TheALERTLEDwillflashconsecutively pause andthenrepeattheprocess Thenumberofconsecutive flashes referred to as the Flash Code correlates to a particular abnormal condition Detailed descriptions of these ALERT F...

Страница 13: ...24VACthermostatshouldbeusedwhenanelectric heater kit is installed As previously noted a field installed circuit breaker kit is available as a means of electrical disconnect for the unit Install the heater kits as directed by the instructions supplied with the heater kit Follow all cautions and warnings as directed NOTE If installing a 10kw heater kit in the 2 or 3 ton capacity units the 145 limit ...

Страница 14: ...nt protection is sized properly Verify that the thermostat is wired correctly The thermostat function switch should be set to OFF and the thermostat fan switch should be set to AUTO Start Up Procedure Close all electrical disconnects to energize the system Air Circulation Leave the thermostat system mode on OFF and set the fan mode to ON Blower should run continuously Check the air delivery at the...

Страница 15: ...outdoor fan are not energized but that the blower and heaters are Feeltheairbeingcirculatedbytheindoorblowerandverify that it is warmer than ambient temperature Listen for any unusual noises If unusual sounds occur determine the source of the noise and correct as necessary 5 If the pressure measured in step 1 is less than the required liquid refrigerant pressure determined in step 4 then there is ...

Страница 16: ...UCT OPENING 4 0 CONDENSING COIL 5 0 8 4 00 Table 7 Center of Gravity Unit Shipping Weights Model Number Q4SE PPH1SE Unit Weight Center of Gravity Height C in inches A B with base rails without base rails X24 450 28 0 25 5 39 0 35 3 X36 460 28 0 25 5 39 0 35 3 X48 570 29 5 26 0 43 0 39 3 X60 580 29 5 26 0 43 0 39 3 Side View 1 1 4 Ø Power Entry 1 3 4 Ø Power Entry Capped 22 25 Ø Control Wiring Entr...

Страница 17: ...AMBIENT SENSOR COIL SENSOR TEST L R C Y O W2 IN W2 OUT COND FAN AMBIENT AMBG COILG COIL DEMAND DEFROST CONTROL BOARD M PRESS SW REV VALVE Demand Defrost Board Terminal Strip Optional Outdoor Thermostat Indoor T Stat Sub Base 1 2 3 4 5 6 7 8 9 Brown Orange Accessory Heat Plug G C L W1 R Y2 E O Y1 AMBIENT SENSOR COIL SENSOR TEST L R C Y O W2 IN W2 OUT COND FAN AMBIENT AMBG COILG COIL DEMAND DEFROST ...

Страница 18: ...ncerning accessory Heat Kits and other options DEFROST BOARD OPERATION Heat Pump operates in heating mode until the combination of outdoor ambient and outdoor coil temperatures initiate a defrost cycle The outdoor coil temperature must be at or below 32 F before the defrost cycle begins There must be a minimum of 20 minutes between defrost cycles After this time temperature conditions must call fo...

Страница 19: ...at Kits and other options Heat pump operates in heating mode until the combination of outdoor ambient and outdoor coil temperatures initiate a defrost cycle The outdoor coil temperature must be at or below 32 F before the defrost cycle begins There must be a minimum of 20 minutes between defrost cycles After this time temperature conditions must call for defrost continuously for 4 1 2 minutes befo...

Страница 20: ...ssure psig Add refrigerant when below curve Remove refrigerant when above curve Q4SE X36 Charging Chart Cooling 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Pressure psig Liquid Temperature F Add refrigerant when below curve Remove refrigerant when above curve Figure 14 Charging Chart for 3 Ton Units Figur...

Страница 21: ...Temperature F Add refrigerant when below curve Remove refrigerant when above curve Q4SE X60 Charging Chart Cooling 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 620 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Pressure psig Liquid Temperature F Add refrigerant when below curve Remove refrigerant when above curve Figure 15 Charging Chart for 4 Ton Units Figure...

Страница 22: ...k for excessively low thermostat setting Check evaporator airflow coil blockages or return airfilter Check ductwork or registers for blockage Faulty metering device Check TXV bulb installation size location and contact Check if TXV fixed orifice is stuck closed or defective Condenser coil is dirty Liquid line restriction filter drier blocked if present in system Thermostat is malfunctioning Soleno...

Страница 23: ... compressor protector reset time due to extreme ambient temperature Compressor windings are damaged Check compressor motor winding resistance Yellow ALERT Flash Code 6 Open Start Circuit Current only in run circuit Run capacitor has failed Open circuit in compressor start wiring or connections Check wiring and connectors between supply and the compressor S terminal Compressor start winding is dama...

Страница 24: ...d to 24VAC at contactor coil Verify voltage at contactor coil falls below 0 5VAC when off ALERT Flash Code 5 6 or 7 displayed incorrectly Open Circuit Open Start Circuit or Open Run Circuit Verify the compressor run and start wires are routed through the module s current sensing holes Verify the Y terminal is connected to 24VAC at contactor coil Verify voltage at contactor coil falls below 0 5VAC ...

Отзывы: