5
30" ELECTRIC SLIDE-IN RANGE INSTALLATION INSTRUCTIONS
Four Conductor Wire Connection to Range
(mobile homes)
1. Remove the 3 screws at the lower end of the rear
wire cover, then raise the lower end of the rear wire
cover (access cover) upward to expose range
terminal connection block (see figure 3).
2. Remove the 3 loose nuts (after you remove the
rubber band) on the terminal block using a 3/8" nut
driver or socket.
3. Remove the ground strap from the terminal block
and from the appliance frame.
4. Connect the ground wire (green) of the copper
power supply cord to the frame of the appliance
with the ground screw, using the hole in the frame
where the ground strap was removed (see Figure 5).
5. Connect the neutral of the copper power supply cord
to the center silver-colored terminal of the terminal
block, and connect the other wires to the outer
terminals. Match wires and terminals by color (red
wires connected to the right terminal, black wires
connected to the left terminal).
6. Replace the 3 nuts on the terminal block (see figure
5).
7. Lower the terminal cover and replace the 3 screws.
Direct Electrical Connection to the Circuit
Breaker, Fuse Box or Junction Box
If the appliance is connected directly to the circuit
breaker, fuse box or junction box, use flexible, armored
or nonmetallic sheathed copper cable (with grounding
wire). Supply a U.L. listed strain-relief at each end of the
cable. At the appliance end, the cable goes through the
Direct Connection Hole (see Figure 5) on the Cord
Mounting Plate. Wire sizes
(copper wire only)
and
connections must conform to the rating of the appliance.
Where local codes permit connecting the appliance-
grounding conductor to the neutral (white) wire
(see Figure 6):
(The 3-conductor cord or cable must be replaced with a
4-conductor cord or cable where grounding through the
neutral conductor is prohibited in new installations,
mobile homes, recreational vehicles or in other areas
where local codes do not permit neutral grounding)
1. Disconnect the power supply.
2. In the circuit breaker, fuse box or junction box:
a) Connect the green (or bare copper) wire, the
white appliance cable wire, and the neutral (white)
wire together.
b) Connect the 2 black wires together.
c) Connect the 2 red wires together.
Figure 5
Terminal Block
Silver Colored Terminal
Red
Wire
Neutral
(White Wire)
Ground (Bare
Copper Wire)
To 240 V Receptacle
A User Supplied
Strain-relief Must
Be Installed at
This Location
Black Wire
1 1/8" (2.9 cm)
Dia. Direct
Connection
Hole. Punch
Out Knockout
for 1 3/8 (3.5
cm) Dia. Cord Kit
Hole.
NOTE
: Be sure to remove the
supplied grounding strap.
Figure 6
3-Wire (Grounded Neutral) Electrical System
(Example: Junction Box)
Cable from Residence
Junction
Box
White Wire
U.L.-listed Conduit
Connector (or CSA
listed)
Cable from
Appliance
Green
(or Bare Copper)
Wire
Red
Wires
Neutral
(white) Wire
Black
Wires