Friedrich ZoneAire PZE07K Скачать руководство пользователя страница 29

29

Accessories

PXAA

New Construction Accessories

PDXWSA 

PDXWSEXT18

PDXWSEXT24

PDXWSEXT

WALL SLEEVE

 Galvanized zinc coated steel is prepared in an 11-

step  process,  then  powder    coated  with  a  polyester  finish  and  cured 

in an oven for exceptional durability.  The wall sleeve is insulated for 

sound  absorption  and  thermal  efficiency,  16"  H  x  42"  W  x  13 

3

/

4

" D. 

DEEP WALL SLEEVE

 For walls up to 17 

1

/

2

" D.

DEEP WALL SLEEVE

 For walls up to 23 

1

/

2

" D.

CUSTOM DEEP WALL SLEEVE

 One piece extended wall sleeve for walls 

from 13 

1

/

4

" to 25 

1

/

2

" D are available by special order.

PXSE

SLEEVE EXTENSION RETROFIT KIT

 Galvanized zinc coated steel, 2 

3

/

8

sleeve extension attached to the room side of the sleeve to allow for the 

installation of a PZ-Series Friedrich PTAC in a T-Series sleeve.

PXGA

GRILLE

 Standard, stamped aluminium, anodized to resist chalking and 

oxidation.

PXAA 

PXBG 

PXSC

ARCHITECTURAL GRILLES

 Consist of heavy-gauge 6063-T5 

aluminum alloy: 42" W x 16" H x 1 

1

/

8

" D

PXAA – Clear, extruded aluminum

PXBG – Beige acrylic enamel

PXSC – Also available in custom colors.

PXDR10

CONDENSATE DRAIN KIT

 Attaches to the bottom of the wall sleeve for 

internal draining of condensate or to the rear wall sleeve flange for ex

-

ternal draining. Recommended on all units to remove excess conden-

sate. Packaged in quantities of ten.

PXCJA

CONDUIT KIT WITH JUNCTION BOX

 Hard wire conduit kit with junc-

tion box for 208/230V and 265V units (subbase not required). 

Kit includes a means of quick disconnect for easy removal of the 

chassis.  *Required for 265V installations.

PXFT

B

REPLACEMENT FILTER PACK

 These are original equipment return air 

filters.  They are reusable and can be cleaned by vacuuming, washing, 

or blowing out, and are sold in convenient ten-packs.  (Two filters per 

chassis).

PXGA

Deep wall sleeve PDXWSEXT18 shown with weather panel 

PDXWSA

Содержание ZoneAire PZE07K

Страница 1: ...Installation and Operation Manual PTAC Packaged Terminal Air Conditioners Heat Pumps ZoneAire...

Страница 2: ...n Instructions 12 Chassis Install Preparation 16 Chassis Installation 18 Friedrich PTAC Digital Control and Unit Features 19 System Configuration 21 Digital Control User Input Configuration 22 Digital...

Страница 3: ...ling is weak and you have verified that the filter is clean and the controls are properly set the unit may need service and you should call your Friedrich service provider to check the unit 7 Keep bli...

Страница 4: ...therboard Check for proper wall sleeve installation in accordance with the wall sleeve installation instructions Check for a subbase kit or other means of structural support which is required for ALL...

Страница 5: ...tions such as lamp poles or small shrubbery a clearance of 12 from the outdoor louver should be maintained TYPICAL BUILDING PLAN VIEW For major obstructions such as a solid fence wall or other heat r...

Страница 6: ...in depth 1 The PXDR10 Drain Kit optional for new construction see page 10 if applicable must be installed before the wall sleeve is installed into the wall 2 The External Drain for new construction or...

Страница 7: ...for proper drainage In applications where the drain holes on the PTAC wall sleeve are not exposed beyond the wall an internal drain system is recommended It is the installer s responsibility to ensur...

Страница 8: ...IN A B C Dimension Allow for wall finishing Allow for floor finishing Allow for proper drainage Minimum Min Max Front to Back C No Accessories With Subbase 1 3 5 With Lateral Duct Wall Sleeve Tilt B W...

Страница 9: ...ater leave the weatherboard and center support in place otherwise remove and dispose of them See Figure 13 Page 12 8 Provide a support lintel if the wall sleeve is installed in a concrete or masonry w...

Страница 10: ...tion the assembly beneath the drilled holes and secure it with 10 24x machine screws and lock nuts provided Seal the tops of the screws with silicone caulking 5 Use ID copper tube PVC pipe or vinyl ho...

Страница 11: ...to the remaining drain hole Make certain the large flange on the plate is positioned at the bottom of the sleeve 5 Discard the additional cover plate gasket machine screws and locknuts NOTICE If the...

Страница 12: ...ng maneuver the grille through the wall sleeve and pull toward you until the screw heads are inserted into the keyhole slots at the top of the wall sleeve Tighten the two screws completely 5 Insert th...

Страница 13: ...tacles NEMA Receptacle 6 20R 6 30R 7 20R NEMA Plug 6 20P 6 30P 7 20P WARNING Electrical Shock Hazard Turn off electrical power before service or installation ALL electrical connections and wiring MUST...

Страница 14: ...installed on all hardwire units If installing a flush floor mounted unit make sure the chassis can be removed from the sleeve for service and maintenance To install the line voltage power leads and c...

Страница 15: ...te the cut ends of the power cord through the elbow connector at the other end of the conduit Tighten screws on elbow connect or to secure conduit sleeve 5 Fasten and secure the elbow connector to the...

Страница 16: ...etween the condenser air baffles and around the indoor mounting flange is recommended In some cases additional gaskets or baffling may be required Suffocation Hazards Keep bag away from babies and chi...

Страница 17: ...sent See Fig 21 Figure 21 Shipping Screw Location Figure 20 ShippingTapeLocation REMOVE SHIPPING SCREW IF PRESENT 5 Remove front panel See Figure 22 Figure 22 RemovingFrontPanel FRP020 FRP022 Pull out...

Страница 18: ...result in back or other injury NOTICE FRP023 2 Locate the four supplied chassis mounting screws Insert the screws through the chassis mounting flange holes that are aligned with the speed nuts in the...

Страница 19: ...se of a wall mounted thermostat All new Friedrich PTACs may be switched from unit control to remote thermostat control easily without the need to order a special model or accessory kit INTERNAL DIAGNO...

Страница 20: ...r from damage in the event that airflow is reduced or low outdoor temperatures cause the indoor coil to freeze When the indoor coil reaches 33 F the compressor is disabled and the fan continues to ope...

Страница 21: ...set to OPEN some outdoor air will be drawn into room This may reduce heating or cooling efficiency Figure 25 Air Vent Control Location FRP025 Adjusting Air To adjust air direction 1 Remove front panel...

Страница 22: ...atus as before power cut Moving Dip Switch 6 to OFF will disable this feature smart center will no more remember settings 7 Switch 7 Medium fan speed for indoor fan ON when press the HIGH fan speed ou...

Страница 23: ...ends on the Constant Fan selection See Constant Fan section When the outdoor coil temperature falls below 26 F for 3 minutes the unit will operate the electric strip instead of heat pump Only when the...

Страница 24: ...heat thermostat with an B reversing valve control The Friedrich RT6 thermostat can be configured for either model To control the unit with a wall mounted thermostat follow the steps below 1 Unplug the...

Страница 25: ...ation If the unit detects 24Vac on this input it will automatically turn itself off If no voltage is detected on the input the unit will run normally NOTE It is the installer s responsibility to ensur...

Страница 26: ...filters and lift out of the front cabinet Reverse the procedure to reinstall the filters Clean the filters with a mild detergent in warm water and allow them to dry thoroughly before reinstalling Coi...

Страница 27: ...emote Thermostat and Control Panel in the senior settings section Indoor fan outdoor fan not function or run slowly Fan is locked by something or the power wires are not fixed well fan capacitor is no...

Страница 28: ...re Outdoor coil temperature sensor open circuit or short circuit Check the sensor connecting If the sensor is bad replace a new one E8 Overheating protection defrosting Indoor fan failure dirty filter...

Страница 29: ...um anodized to resist chalking and oxidation PXAA PXBG PXSC ARCHITECTURAL GRILLES Consist of heavy gauge 6063 T5 aluminum alloy 42 W x 16 H x 1 1 8 D PXAA Clear extruded aluminum PXBG Beige acrylic en...

Страница 30: ...ase 265V 15A Electrical Subbase 265V 20A Electrical Subbase 265V 30A RT6 RT6P DIGITAL REMOTE THERMOSTATS RT6 Wired single stage cool single stage heat for PDE models or single stage cool dual stage he...

Страница 31: ...ICH in exchange for the replacement part Reasonable proof must be presented to be new or remanufactured Replacement parts and labor are only warranted for any unused portion of the unit s warranty We...

Отзывы: