— Replacement of the refrigeration cycle.

1. When replacing the refrigeration cycle, be sure to

Discharge the refrigerant system using a Freon

TM

recovery System.
If there is no valve to attach the recovery system,
install one (such as a WATCO A-1) before venting
the Freon

TM

Remove the valve when finished.

2. After discharging the unit completely, remove the

desired component, and unbraze the pinch-off
tubes.

3. Solder service valves into the pinch-off tube ports,

leaving the valves open.

4

. Evacuate as follows.

1) Connect the vacuum pump, as illustrated figure

16A.

2) Start the vacuum pump, slowly open manifold 

valves A and B with two full turns
counterclockwise and leave the valves open.
The vacuum pump is now pulling through valves
A and B up to valve C by means of the manifold

and entire system.

3) Operate the vacuum pump for 20 to 30 minutes, 

until 600 microns of vacuum is obtained. Close 
valves A and B, and observe vacuum gauge for 
a few minutes. A rise in pressure would 
indicate a possible leak or moisture remaining in
the system. With valves A and B closed, stop 

the vacuum pump.

4) Remove the hose from the vacuum pump and

place it on the charging cylinder. See figure
16B.
Open valve C.
Discharge the line at the manifold connection.

5) The system is now ready for final charging.

5

. Recharge as follows :

1) Refrigeration cycle systems are charged from

the High-side. If the total charge cannot be put 
in the High-side, the balance will be put in the 
suction line through the access valve which you 
installed as the system was opened.

2) Connect the charging cylinder as shown in figure 

16B.
With valve C open, discharge the hose at the
manifold connection.

3) Open valve A and allow the proper charge to 

enter the system. Valve B is still closed.

4) If more charge is required, the high-side will not 

take it. Close valve A.

5) With the unit running, open valve B and add the 

balance of the charge.
a. Do not add the liquid refrigerant to the Low-

side.

b. Watch the Low-side gauge; allow pressure to 

rise to 30 lbs.

c. Turn off valve B and allow pressure to drop.
d. Repeat steps b. and c. until the balance of the 

charge is in the system.

6) When satisfied the unit is operating correctly, 

use the pinch-off tool with the unit still running 
and clamp on to the pinch-off tube. Using a tube 
cutter, cut the pinch-off tube about 2 inches from 
the pinch-off tool. Use sil-fos solder and solder 
pinch-off tube closed. Turn off the unit, allow it to 
set for a while, and then test 

for any leaks at

 the 

pinch-off connection.

NOTES

If high vacuum equipment is used, just crack
valves A and B for a few minutes, then open
slowly with the two full turns counterclockwise.
This will keep oil from foaming and being
drawn into the vacuum pump.

2.4.3 CAPILLARY TUBE

1. Remove the cabinet. (Refer to section 2.1.2)
2. After discharging the refrigerant completely,

unbraze the interconnecting tube at the capillary
tube.(See caution 

on previous page

)

3. Remove the capillary tube.

4. Re-install the components by referring to notes.

CAUTION

Содержание Z-Star ZQ10C10

Страница 1: ...Room Air Conditioner Service and Parts Manual ZQ08 CP12 05 06 ZQ08C10 ZQ10C10 CP08C10 CP10C10 CP12C10...

Страница 2: ...al and electrical parts etc This room air conditioner was manufactured and assembled under a strict quality control system The refrigerant is charged at the factory Be sure to read the safety precauti...

Страница 3: ...E CTE D TYPE DR AIN PIPE OR S PLAS HE D BY FAN S LINGE R 62 28 203 32 x 13 29 32 x 193 8 510 x 354 x 490 POWE R S UPPLY COOLING CAPACITY Btu h INPUT W R UNNING CUR R E NT A E E R BTU W h OPE R ATING I...

Страница 4: ...counter clockwise OPERATION Fig A OFF Turns the air conditioner off MED FAN Medium fan speed without cooling LOW FAN Low fan speed without cooling HIGH COOL Cooling with the high fan speed MED COOL C...

Страница 5: ...oom OPERATION MODE SELECTION BUTTON Push this button it will shift operation between COOL ENERGY SAVER FAN and DRY modes Energy Saver If Energy Save mode is selected the fan stops when the compressor...

Страница 6: ...hannel 5 Remove the 1 screw which fastens the control box cover 6 Remove the housing which connects PCB the control panel CP 08 10 12 or connector ZQ 08 10 and motor wire in the control box 7 Remove t...

Страница 7: ...by pushing the tabs and remove it See Figure 6 11 Using pliers remove the clamp which secures the turbo fan 12 Remove the turbo fan 13 Remove the 2 screws which fasten the air guide to the base pan 14...

Страница 8: ...o the removal procedure above 2 3 2 COMPRESSOR 1 Remove the cabinet Refer to section 2 1 2 2 Discharge the refrigerant system using a FreonTM Recovery System If there is no valve to attach the recover...

Страница 9: ...connect the front panel from the control box See Figure 12 4 Disconnect the 2 receptacles and remove the grounding screw 5 Pull out the power cord 6 Re install the component by referring to the remova...

Страница 10: ...onnecting tube at the condenser connections 5 Remove the condenser 6 Re install the components by referring to notes See Figure 14 2 4 2 EVAPORATOR 1 Remove the control box Refer to section 2 1 3 2 Re...

Страница 11: ...e put in the High side the balance will be put in the suction line through the access valve which you installed as the system was opened 2 Connect the charging cylinder as shown in figure 16B With val...

Страница 12: ...proof seal Leak detector Tubing cutter Hand Tools to remove components Service valves A COMPOUND GAUGE EVAPORATOR LOW PRESSURE SIDE COMPRESSOR CAPILLARY TUBE CONDENSER HIGH PRESSURE SIDE SEE INSETS B...

Страница 13: ...1 5 32 18 23 32 126 5 4 31 32 32 510 20 3 32 13 3 TROUBLESHOOTING GUIDE 3 1 OUTSIDE DIMENSIONS unit mm inch DEFROST HEAT COOL INDOOR DESIRED ENERGY SAVER AIR PURYFIER AUTO RESTART FAN FAN DRY 380 14 3...

Страница 14: ...OIL LIQUID REFRIGERANT CAPILLARY TUBE OUTSIDE COOLING AIR FOR REFRIGERANT PASS THROUGH SUCTION LINE COOL LOW PRESSURE VAPOR COOLED AIR COMPLETE LIQUID BOIL OFF POINT LIQUID PRESSURE DROP ROOM AIR HEAT...

Страница 15: ...insulation Replacement of fan motor Regular but fails to start Replacement of compressor locking of rotor metal Improper thermostat setting Loose terminal connection Improper wiring Irregular motor r...

Страница 16: ...If not replace fan motor Pay attention to any change from high speed to low speed If the speed does not change replace the motor If cracked out of balance or partially missing replace it If cracked o...

Страница 17: ...ush Clean the interior base before reassembling If condenser fins are closed over a large area on the coil surface head pressures will increase causing the compressor to overload Comb the fins or repl...

Страница 18: ...TOR CN PWR ZNR01J RY COMP 3 4 FUSE 250V T2A 115V T2A RY LOW RY MED RY HI CN AC DC POWER TRANS CN AC DC CN TH1 BL RD BL R S C OLP YL OR YL F C H WH BL Ribbed BK BR Plain GN YL GN GN YL GN BK RD OR BR 1...

Страница 19: ...5500 147581 147582 2 559011 349480 352113 352113 W48602 148000 354210 152302 264110 249950 149410 266003 269310 130410 550140 35211A 554160 567502 135312 135313 554031 352115 552111 268714 W0CZZ 13550...

Страница 20: ...lay R 268714 67307613 PWB PCB Assy Main R 346811 67303031 67303032 67303018 Motor Assy Single R 349480 Orifice R 352390 1 Air Guide Assy Upper R 352390 2 Air Guide Assy Lower R 550140 Isolator Comp R...

Страница 21: ...8714 PWB PCB Assy Display R 268712 PWB PCB Assy Main R 346811 67303030 67303035 Motor Assy Single R 349480 Orifice R 352390 1 Air Guide Assy Upper R 352390 2 Air Guide Assy Lower R 550140 Isolator Com...

Страница 22: ...22 MEMO...

Страница 23: ...23 MEMO...

Страница 24: ...ost Office Box 1540 4200 N Pan Am Expressway San Antonio Texas 78295 1540 210 357 4400 FAX 210 357 4490 FRIEDRICH AIR CONDITIONING CO Visit our web site at www friedrich com Use Factory Certified Part...

Отзывы: