13

 10. 

Evacuate system to maximum absolute holding pres-
sure of 200 microns or less. NOTE:  This process can 
be speeded up by use of heat lamps, or by breaking 
the vacuum with refrigerant or dry nitrogen at 5,000 
microns. Pressure system to 5 PSIG and leave in 
system a minimum of 10 minutes. Release refriger-
ant, and proceed with evacuation of a pressure of 
200 microns or less.

 11. 

Break vacuum by charging system from the high side 
with the correct amount of refrigerant specifi ed. This 
will prevent boiling the oil out of the crankcase.

 

 

NOTE:  If the entire charge will not enter the high 
side, allow the remainder to enter the low side in 
small increments while operating the unit.

 12. 

Restart unit several times after allowing pressures 
to stabilize. Pinch off process tubes, cut and solder 
the ends. Remove pinch off tool, and leak check the 
process tube ends.

SPECIAL PROCEDURE IN THE CASE OF MOTOR
COMPRESSOR BURNOUT

  1. 

Recover all refrigerant and oil from the system.

  2. 

Remove compressor, capillary tube and fi lter drier 
from the system.

  3. 

Flush evaporator condenser and all connecting 
tubing with dry nitrogen or equivalent, to remove 
all contamination from system. Inspect suction and 
discharge line for carbon deposits. Remove and 
clean if necessary.

  4. 

Reassemble the system, including new drier strainer 
and capillary tube.

  5. 

Proceed with processing as outlined under hermetic 
component replacement.

ROTARY COMPRESSOR SPECIAL 
TROUBLESHOOTING AND SERVICE

Basically, troubleshooting and servicing rotary compres-
sors is the same as on the reciprocating compressor with 
only a few exceptions.

  1. 

Because of the spinning motion of the rotary, the 
mounts are critical. If vibration is present, check the 
mounts carefully.

  2. 

The electrical terminals on the rotary are in a differ-
ent order than the reciprocating compressors. The 
terminal markings are on the cover gasket. Use your 
wiring diagram to insure correct connections.

REFRIGERANT CHARGE

  1. 

The refrigerant charge is extremely critical. Mea-
sure charge carefully - as exact as possible to the 
nameplate charge.

  2. 

The correct method for charging the rotary is to 
introduce liquid refrigerant into the high side of the 
system with the unit off. Then start compressor and 
enter the balance of the charge, gas only, into the 
low side.

 

 

The introduction of liquid into the low side, without 
the use of a capillary tube, will cause damage to 
the discharge valve of the rotary compressor.

 

 

NOTE:   All inoperative compressors returned to 
Friedrich must have all lines properly plugged with 
the plugs from the replacement compressor.

Содержание WE10B33A-A

Страница 1: ...WS08B10A A WS10B10A A WS14B10A A WS10B30A A WS13B30B A WS16B30A A WE10B33A A WE13B33B A WE16B33A A WY10B33A A WY13B33A A WM Svc Prts 06 5 06 Service Parts Manual WallMaster Thru the Wall 72...

Страница 2: ...Data 6 Electrical Data 7 Functional Component De nitions 8 Electronic Controls 9 Rotary Controls 10 Refrigeration Sequence of Operation 11 Sealed Refrigeration Repairs 12 13 Refrigerant Charging 13 G...

Страница 3: ...nada This warranty is not applicable to 1 Air filters or fuses 2 Products on which the model and serial numbers have been removed 3 Products which have defects or damage which results from improper in...

Страница 4: ...s and debris Clean both areas with an antibacterial and antifungal cleaner Rinse both items thoroughly with water and ensure that the drain outlets are operating correctly Check the sealant around the...

Страница 5: ...R 6th DIGIT VOLTAGE 1 115 Volts 3 230 208 Volts 7th DIGIT 0 Straight Cool Heat Pump Models ELECTRIC HEAT MODELS 3 3 KW Heat Strip Nominal 8th DIGIT Major Change Serial Number Decade Manufactured L 0 C...

Страница 6: ...00 230 208 6 3 6 7 1404 1379 16 0 14 7 3550 2950 8 9 8 7 3 3 280 111 WE16B33A 15800 15000 11000 9100 230 208 7 8 8 5 1756 1705 16 0 14 7 3550 2950 9 0 8 8 4 2 290 121 WY10B33A 10100 9800 8100 7800 230...

Страница 7: ...ord and be within reach of service cord Do NOT alter the service cord or plug Do NOT use an extension cord Refer to the table above for proper receptacle and fuse type ELECTRIC SHOCK HAZARD Turn off e...

Страница 8: ...ing diagrams and schematics in the back of this service manual Capacitor Reduces line current and steadies the voltage supply while greatly improving the torque characteristics of the fan motor and co...

Страница 9: ...els LED for the TIMER ON OFF will ash 1bps while Error Code Mode is active Pressing the TEMP HR button will display 00 Consecutive presses will scroll through all error codes logged Press the TEMP HR...

Страница 10: ...tion as indicated on decorative control panel in Figure 7 Wait three minutes before restarting Warmer Cooler Fan Only Low Heat Med Heat High Heat Low Cool Med Cool High Cool MODE TEMPERATURE Figure 7...

Страница 11: ...ore a change in state can occur 3 Flow is always from a higher pressure area to a lower pressure area 4 The temperature at which a liquid or gas changes state is dependent upon the pressure The refrig...

Страница 12: ...Compressor condenser evaporator capillary tube refrigerant leaks etc 1 Recover the refrigerant from the system at the pro cess tube located on the high side of the system by installing a line tap on...

Страница 13: ...d discharge line for carbon deposits Remove and clean if necessary 4 Reassemble the system including new drier strainer and capillary tube 5 Proceed with processing as outlined under hermetic componen...

Страница 14: ...roke or not enough ow to maintain pressure differential Check unit for correct operating pressures and charge Raise head pressure If no shift use valve with smaller port Body damage Replace valve Hot...

Страница 15: ...t run Inoperative system switch Test switch replace if inoperative Broken loose or incorrect wiring Refer to applicable wiring diagram Open capacitor Test capacitor replace if inoperative Fan speed sw...

Страница 16: ...y tube De ice coil Check temp differential delta T across coil Touch test coil return bends for same temp Test for low running current Problem Possible Cause Action Compressor runs continually does no...

Страница 17: ...bulb Place jumper across t stat terminals to check if unit operates If unit operates replace t stat Loose or broken parts in t stat Check as above Incorrect wiring Refer to appropriate wiring diagram...

Страница 18: ...hort cycles T stat differential too narrow Replace t stat Plenum gasket not sealing allowing discharge air to short cycle t stat Check gasket Reposition or replace as needed Restricted coil or dirty l...

Страница 19: ...lace defrost control Defrost control contacts stuck If contacts remain closed between terminals 2 3 of the defrost control after preselected time interval has passed replace control Defrost control bu...

Страница 20: ...r continuity of system switch Problem Possible Cause Action Cooling adequate but heating insuf cient Heating capillary tube partially restricted Check for partially starved outer coil Replace heating...

Страница 21: ...21 WIRING DIAGRAM MODELS WS08B10A A B WS10B10A A B WS14B10A A B WS10B30A A B WS13B30B A...

Страница 22: ...22 WIRING DIAGRAM MODELS WS16B30A A B...

Страница 23: ...23 WIRING DIAGRAM MODELS WE10B33A A WE13B33B A...

Страница 24: ...24 WIRING DIAGRAM MODELS WE16B33A A...

Страница 25: ...25 WIRING DIAGRAM MODELS WY10B33A A WY13B33A A...

Страница 26: ...ES CHASSIS PARTS 47 48 46 46A 31 12 32 30 7 16 17 14 20 18 19 27 25 13 8 For Heat Cool Models Only 5 45 26 1 41 43 39 Electronic Control Box and Controls 2 41 39 43 6 1 44 Electro Mechanical Control B...

Страница 27: ...61871456 1 1 1 110 7 FAN MOTOR 61871457 1 1 110 7 FAN MOTOR 61871458 1 1 1 110 7 FAN MOTOR 61871459 1 1 110 8 HEATER 62101210 1 1 1 1 1 210 9 COIL SOLENOID 25063600 1 1 240 REFRIGERATION SYSTEM PARTS...

Страница 28: ...1 1 1 1 1 1 1 1 1 1 1 999 43 ESCUTCHEON COOL 62101106 1 1 1 1 1 1 760 43 ESCUTCHEON HTG COOL 62101102 1 1 1 1 1 760 44 KNOBS CRTL 61911600 2 2 2 2 2 761 HOLDER AIR FILTER 60865900 2 2 2 2 2 2 2 2 2 2...

Страница 29: ...PART NO DESCRIPTION APPLICATION CHASSIS PARTS Cont 1 616 036 01 Sleeve Assembly 1 1 1 1 1 1 1 1 1 1 1 2 616 032 00 Panel Weather Inner 1 1 1 1 1 1 1 1 1 1 1 3 616 030 01 Grille Louvered 1 1 1 1 1 1 1...

Страница 30: ...06 5 06 Friedrich Air Conditioning Co Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4480 www friedrich com Printed i...

Отзывы: