All units shall be factory assembled, piped, wired and fully charged with R-22. All units shall be certified in accordance with

ARI Standard 310 for air conditioners and ARI Standard 380 for heat pumps.  Units shall be UL listed and carry a UL label.

All units shall be factory run-tested to check operation and be Friedrich WallMaster® or equivalent.

The basic unit shall not exceed 16" high x 42" wide.  Overall depth of the unit from the rear of the Friedrich wall sleeve to the

front of the decorative front cover shall not exceed 21¼".  The unit shall be designed so that room intrusion may be as little

as 7¼".  Installations in walls deeper than 13 ¼" may be accomplished with the use of a wall sleeve extension (PXWE). Unit

shall draw in ambient air through both sides of an outdoor architectural louver or grille measuring 42" wide x 16" high and

shall exhaust heated air out the middle portion of the louver.  The architectural louver and wall sleeve shall be designed so

that the louver may be installed from the inside of the building.

REFRIGERATION SYSTEM -

 The refrigeration system shall consist of a hermetically sealed rotary compressor that is

externally mounted on vibration isolators no smaller than 1 ¾" dia. X 1 ½" high; condenser and evaporator coils constructed

of copper tubes and aluminum plate fins; and capillaries as expansion devices.  Unit shall have a fan slinger ring to increase

efficiency and condensate disposal and have a drain pan capable of retaining 1½ gallons of condensate.  A tertiary condensate

removal system shall also be incorporated for back up and shall overflow through the wall sleeve and to the outside of the

building as a safeguard against damage to the interior room.

AIR HANDLING SECTION -

 The evaporator and condenser fans shall be driven by a single, totally enclosed, ball bearing,

permanently lubricated split capacitor, "clam-shell" style fan motor.  Airflow shall be directed into the room by a single,

injection molded, high-impact polystyrene discharge grille.  The grill shall have openings no larger than 3/8" high x 3" wide

to prevent personal injury or damage to the PTAC unit, and will be reversible to allow air to be directed upward or outward as

determined by the installer.

The chassis shall have a built-in damper capable of providing at least 60 CFM of fresh air into the conditioned area.  A fine

mesh screen shall filter the incoming fresh air.  There must be a provision for locking the damper closed to ensure a proper

seal.

CONTROLS 

- Covered controls shall be accessible in a compartment at least 9" wide with the controls no deeper than 1¼" in

the opening to facilitate easy operation of the unit.  Controls shall include dual rotary knobs for setting of the thermostat and

for mode control.  The knobs will be tamper proof to prohibit the removal of knobs by the user and shall feature a temperature-

limiting device adjustable by the owner.  The control panel shall be clearly marked and easy to read.  Universal symbols shall

be used with markings no smaller than 12-point type.  The chassis may be ordered with the option of remote thermostat

control.

Other controls accessible without removal of the chassis shall include fan cycle switch, fresh air vent control and emergency

heat override switch (heat pump only).

GENERAL CONSTRUCTION -

 The wall sleeve shall be constructed of 18 gauge G90 zinc-coated steel.  It shall be prepared

by a process where it is zinc phosphate pretreated and sealed with a chromate rinse, then powder coated for maximum

coverage and protection.  The sleeve shall be shipped with a protective weatherboard and a structural center support, and be

insulated for thermal efficiency.  The grille or louver shall be shipped separately and made from stamped or extruded

anodized aluminum.  All louvers shall be in the horizontal plane.

The front panel shall lock to the chassis by means of two factory-supplied thumbscrews to prevent tampering.  The front

panel will feature a contoured discharge with no sharp corners. The air filters shall be reusable and be accessible without

removal of the front cover.

All 265V units shall possess an integral, over-current time-delay protective device.

The unit shall have a plastic fan, fan shroud and drain pan for corrosion protection and to help prevent rust on the side of the

building below the outdoor louver.

A complete line of accessories shall be available from Friedrich to equip the PTAC for a multitude of applications.

Friedrich Installation/Start-Up Specialists shall be available to answer questions regarding proper installation practices and

in some cases for on-site start-up inspections.

 

WallMaster

® 

PTAC/PTHP Engineering Specifications

Содержание WallMaster PACKAGED TERMINAL AIR CONDITIONERS AND HEAT PUMPS

Страница 1: ...T PROFILE Available in heat pump or electric heat Front cover fastens to chassis with thumbscrews hidden from user Emergency heat compressor override switch on all heat pumps Single totally enclosed c...

Страница 2: ...9 26 3 5 1 1 10 230 208 253 198 6 6 0 9 38 6 8 1 10 265 292 239 3 0 0 9 18 3 1 15 265 292 239 3 9 0 9 22 2 3 9 1 12 265 292 239 5 1 0 9 26 3 5 1 1 10 265 292 239 6 6 0 9 38 6 8 1 10 250 60 250 60 325...

Страница 3: ...0 54 0 81 0 92 17640 16965 15705 16800 15840 14610 16140 14700 13275 15120 13425 11835 13455 11580 10230 1288 1309 1323 1404 1418 1435 1579 1581 1579 1707 1705 1710 1862 1862 1870 5 5 5 5 5 6 5 9 5 9...

Страница 4: ...2 3 20 3 27 8 30 6 30 3400 2780 230 208 11600 9500 3500 2880 15 3 13 9 19 20 6 20 2500 2050 8500 7000 2600 2150 11 4 10 4 14 1 15 6 15 5000 4090 17000 13900 5210 4300 22 3 20 3 27 8 30 6 30 2500 8500...

Страница 5: ...l Opening 10 Maximum Insulation 50 Max 13 Main Studs Jack Stud LINTEL Mounting Screw Holes No holes are permitted in the top or bottom of the sleeve Exception PXDR10 Drain Kit Typical Wall Sleeve Inst...

Страница 6: ...e be attached to the louver and an anchor point inside the building during installation When using an external drain system the condensate is removed through either of two drain holes on the back of t...

Страница 7: ...hall have a built in damper capable of providing at least 60 CFM of fresh air into the conditioned area A fine mesh screen shall filter the incoming fresh air There must be a provision for locking the...

Страница 8: ...vy gauge 6063 T5 aluminum alloy Clear extruded aluminum Dark bronze acrylic enamel Also available in custom colors PXDR10 CONDENSATE DRAIN KIT Attaches to the bottom of the wall sleeve for internal dr...

Страница 9: ...for wall mounted thermostat control of the unit REPLACEMENT FILTER PACK These are original equipment return air filters They are reusable and can be cleaned by vacuuming washing or blowing out and are...

Страница 10: ...ment parts can be new or remanufactured Replacement parts and labor are only warranted for any unused portion of the unit s warranty We will not be responsible for and the user will pay for 1 Service...

Страница 11: ...setting Front cover fastens to chassis easily with thumbscrews hidden from user Thermostat limiter switch Emergency heat switch heat pump models Easy access easy to clean filter Made in the U S A UL...

Страница 12: ...Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4480 www friedrich com Printed in the U S A PTACBW02 04 02 Multiplesolutions Onetrustedname Fri...

Отзывы: