Friedrich VERT-I-PAK B-SERIES Скачать руководство пользователя страница 14

14

920-164-02 (10-04)

Figure 11
Thermostat Wiring

 

G  R Y B W2 E C

 Fan 

 Compressor   Auxiliary 

  Common

 

     

Heat

  

24V 

 Reversing  Emergency

  

 

  Valve   

Heat

 

G  R Y B W2 E X

100 ft. from the unit (as measured along the control voltage 
wires), use No. 18 AWG color-coded wires to avoid excessive 
voltage drop.

1.  In replacement applications, check the existing ther-

mostat wiring for cracked or frayed insulation.  Replace 
any wiring in poor condition.  All wiring must comply 
with local codes and ordinances.

2.  Run wiring (if necessary) to the location. Connect the 

wires to the terminals on the back of the thermostat.  
(See Figure 11.)

3.  Push the excess wire back through the hole and plug 

any opening with packing material to prevent drafts that 
may affect thermostat performance. 

4.  Loosely secure the thermostat to the wall with screws 

through the two mounting holes in the middle of the 
thermostat.

5.  Level the thermostat.  Tighten the two mounting  

screws. 

6.  Replace the thermostat cover.

C. Wire Thermostat Cable to Unit Terminal Strip

Attach thermostat wires to low-voltage terminal block on left 
side of control box .

4)  Condensate Drain Line

The condensate drain exits the unit 2" above fl oor level at the 
right side front corner of the unit. 

Install a condensate drain line of the same size as the drain 
fi tting on the unit.  PVC plastic pipe (3/4 in. I.D.) makes an 
ideal condensate line (if local codes allow).

Run condensate drain line from unit to fl oor drain or outside 
perimeter of building per local codes.

The condensate line must have a minimum drop of 1/4" per 
running foot as it leaves the unit.  When a horizontal run of 
15 ft. or longer is required, it may be necessary to install a 
vent tee in the drain line near the unit or use a larger diameter 

drain line. This is to eliminate air trapping and allow proper 
condensate drainage.

Heat pumps generate condensate during both cooling and 
heating modes.  Condensate drain line must be protected 
from freezing to prevent condensate from backing up in 
unit during freezing outdoor conditions.  See page 4 for 
Cold Climate accessories.

NOTE: 

 If the unit is to be installed in an attic or furred space 

where damage may result from condensate overfl ow, it may 
be necessary to provide a fi eld-supplied secondary drain 
pan.  Always refer to local and national codes.

Installation - Final Checklist

   

Is power to the unit ON

?

   Are circuit breakers/power disconnect inside 

of the unit ON?

   

Is ductwork sealed for an airtight fi t?

   

Is the condensate drain line installed and run 

to an appropriate disposal site.

?

   

Is the thermostat level and properly installed?

   

Is the heat anticipator indicator set to the 

correct setting

?

Test Run

Test run in Heating, Cooling, and Emergency Heat mode:

a. 

Set fan control to ON.  If fan runs, return control to 
AUTO setting.  This verifi es fan is working properly.

b.  Set system control from OFF to COOL.  Lower 

temperature selector to 50°F or lower.  The compressor 
should energize and cool air should fl ow  from  room 
registers.  Once cooling test is complete, return system 
control to OFF setting.  Wait 5 minutes.

c. 

Set system control to HEAT and raise temperature 
selector to 80°F or higher.  Compressor should energize, 
and warm air should fl ow from room registers.

Содержание VERT-I-PAK B-SERIES

Страница 1: ...920 164 02 10 04 VERT I PAK B SERIES SINGLE PACKAGE VERTICAL AIR CONDITIONINGSYSTEM 18 000 60 000 BTU h INSTALLATION OPERATION GUIDE ...

Страница 2: ... Supply Air System 10 Outdoor Fan Performance 10 Indoor Fan Performance 11 2 Electrical A Grounding 12 B Power Supply 12 3 Thermostat Mounting and Wiring A Thermostat Location 13 B Thermostat Mounting Wiring 13 C Wire Thermostat Cable to Unit Terminal 14 4 Condensate Drain Line 14 Installation Final Checklist 14 Test Run 14 IV Owners Manual Operating Information Identifying your System 15 Importan...

Страница 3: ... for ducted return units This could cause a refrigerant leak DO handle unit with care DO provide minimum installation and service clearances DO build closet so that unit may be removed if necessary DO follow all guidelines for indoor and outdoor air system DO NOT substitute any components without checking with your dealer or distributor If you do substitute get approval in writing Substitutions wi...

Страница 4: ...WP5 plenums Recommended for use with 60 000 Btu h units DIMENSIONS 341 4 high x 40 wide CUTOUT DIMENSIONS 341 2 high x 401 4 wide Architectural louver for VPBWP6 plenums Custom colored architectural louver for VPBWP6 plenums WALL PLENUM Used when chassis is positioned against an exterior wall for outdoor air infiltration ARCHITECTURAL LOUVER Extruded aluminum outdoor louver that attaches to wall sl...

Страница 5: ...7 Cabinet B 68 Cabinet NOMINAL CAPACITY A Series Btu h 09 9 000 12 12 000 18 18 000 24 24 000 VOLTAGE K 208 230V 1Ph 60Hz ELECTRIC HEATER SIZE A Series B Series 00 No electric heat 00 No electric heat 25 2 5 KW 05 5 0 KW 34 3 4 KW 10 10 0 KW 50 5 0 KW 15 15 0 KW 75 7 5 KW 20 20 0 KW 10 10 0 KW 25 25 0 KW ENGINEERING CODE OPTIONS RT Standard Remote Operation SP Seacoast Protected B Series Btu h 18 ...

Страница 6: ...H B49 BACK VIEW 2 00 23 25 14 00 2 00 19 00 12 00 16 25 21 00 OUTDOOR AIR INTAKE OUTDOOR AIR EXHAUST 1 5 2 0 9 5 11 6 22 5 11 6 19 1 22 5 OUTDOOR AIR INTAKE OUTDOOR AIR EXHAUST 38 00 INDOOR AIR RETURN 19 x 27 NOM SERVICE PORT ACCESS 68 00 CONTROL BOX ACCESS 11 10 2 00 14 50 5 50 INDOOR AIR SUPPLY 13 25 2 00 13 87 11 75 INDOOR AIR SUPPLY TOP VIEW ...

Страница 7: ... contained system the Vert I Pak unit requires an adequate supply of outdoor air to exchange heat Figure4 UnitConfiguration from the outdoor air coil The outdoor air intake and discharge openingsarelocatedonthebacksideoftheunit Theunitmay be installed where the outdoor air path runs through the wall of the building directly behind the unit or where the outdoor air intake and discharge paths are duc...

Страница 8: ...8 920 164 02 10 04 Figure6 VPBWP4 8 14WallPlenum Figure5 VPBWP3 8 14WallPlenum For Models VE VHB18 VE VHB24 For Models VE VHB18 VE VHB24 VE VHB30 VE VHB36 ...

Страница 9: ...9 920 164 02 10 04 Figure7 VPBWP5 8 14WallPlenum Figure8 VPBWP6 8 14WallPlenum For Models VE VHB42 VE VHB49 For Model VE VHB60 ...

Страница 10: ...TSIDE WALL Table1 Outdoor Blower Air Flow SCFM ESP 0 0 0 1 0 2 0 3 VEB18 VHB18 Outdoor 1160 1080 990 920 VEB24 VHB24 Outdoor 1160 1080 990 920 VEB30 VHB30 Outdoor 1300 1227 1131 1026 VEB36 VHB36 Outdoor 1600 1550 1480 1420 VEB42 VHB42 Outdoor 2100 2000 1900 1800 VEB49 VHB49 Outdoor 2400 2300 2200 2100 VEB60 VHB60 Outdoor 2600 2550 2450 2350 Italics numbers indicate performance outside the required...

Страница 11: ... front of the RA opening a minimum of 7 in clearance is required between the front of the unit and the back side of the door The minimum net free open area required for the RA louver or grille is listed in Table 2 Front Free Return Front Ducted Return Figure10 ReturnAirOptions NOTE Ducted return air configuration requires field fabrication of a duct mounted filter box IndoorFanPerformance Table2 Indo...

Страница 12: ...Range MCA HACR Max Breaker Size Wire Size field Groung Wire Size field MCA HACR Max Breaker Size Wire Size field Groung Wire Size field Ckt 1 Ckt 2 Ckt 1 Ckt 2 Ckt 1 Ckt 2 Ckt 1 Ckt 2 Ckt 1 Ckt 1 Ckt 1 Ckt 1 VEB18K 00 1 230 208 60 1 198 253 14 N A 20 N A 12 N A 12 N A 14 20 10 12 05 2 230 208 60 1 198 253 14 27 20 30 12 10 12 10 27 30 10 10 75 2 230 208 60 1 198 253 14 39 20 40 12 8 12 10 40 40 6 10 1...

Страница 13: ... 10 10 N A N A N A N A Unit Wiring with VPDB1 Distribution Block Heat Pump Field Wiring Auxiliary Heater 1 Field Wiring Ground Field Wiring Ground Lug Auxiliary Heater 2 Field Wiring Auxiliary Heater 2 Auxiliary Heater 1 Heat Pump Line Voltage And Ground Connections 3 ThermostatMountingAndWiring A ThermostatLocation Locate the thermostat about 5 ft above the floor in an area with good circulation a...

Страница 14: ...s The condensate line must have a minimum drop of 1 4 per running foot as it leaves the unit When a horizontal run of 15 ft or longer is required it may be necessary to install a vent tee in the drain line near the unit or use a larger diameter drain line This is to eliminate air trapping and allow proper condensate drainage Heatpumpsgeneratecondensateduringbothcoolingand heatingmodes Condensatedr...

Страница 15: ...re variations within the home Dehumidification Duringthecoolingseason theVert I Pakalsodehumidifiesthe air in the home while is it cooling the air After a few minutes of operation water should run freely from the condensate drain line extended to the outside of your home If condensate is not runningfromthedrainline checktobesurethatthedrainhose or pipe is properly connected to the drain fitting locat...

Страница 16: ...onsforcontrollingtheindoor air blower AUTO and ON When the FAN control is set to AUTO the blower will operate only while the thermostat operates the cooling or heating equipment When the FAN control is set to ON the blower will operate continuously regardless of whethercoolingorheatingequipmentisoperating Thissetting allows for continuous air circulation and filtration SystemControl The SYSTEM or M...

Страница 17: ... dirt on the indoor air coil can damage your unit and void the warranty The air filter should be replaced as it becomes dirty To replace the filter front air return units 1 Slide the filter to the right until it clears the filter rails See Figure 12 2 Remove the filter 3 Install new disposable filter CAUTION Do not operate your system without a filter in place nor block the front of the unit return air o...

Страница 18: ...18 920 164 02 10 04 ...

Страница 19: ...19 920 164 02 10 04 ...

Страница 20: ...tory Certified Parts FRIEDRICH AIR CONDITIONING CO INC Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4480 www friedrich com Printed in the U S A ...

Отзывы: