Friedrich Uni-Fit US10B10A Скачать руководство пользователя страница 11

- 11 -

Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes

LGE Internal Use Only

— Replacement of the refrigeration cycle.

1. When replacing refrigeration components, be sure

to discharge the refrigerant system using a Freon

TM

recovery System.
Install a valve for the recovery, before venting the
Freon, remove the valve when finished.

2. After discharging the unit completely, remove the

desired component, and unbrace the pinch-off
tubes.

3. Solder service valves into the pinch-off tube ports,

leaving the valves open.

4. Solder the pinch-off tubes with Service valves.
5. Evacuate as follows.

1) Connect the vacuum pump, as illustrated Fig.

17A.

2) Start the vacuum pump, slowly open manifold 

valves A and B with two full turns
counterclockwise and leave the valves closed.
The vacuum pump is now pulling through valves
A and B up to valve C by means of the manifold

and entire system.

3) Operate the vacuum pump for 20 to 30 minutes, 

until 600 microns of vacuum is obtained. Close 
valves A and B, and observe vacuum gauge for 
a few minutes. A rise in pressure would 
indicate a possible leak or moisture remaining in
the system. With valves A and B closed, stop 

the vacuum pump.

4) Remove the hose from the vacuum pump and

place it on the charging cylinder. See Fig. 17B.
Open valve C.
Discharge the line at the manifold connection.

5) The system is now ready for final charging.

6. Recharge as follows :

1) Refrigeration cycle systems are charged from the

High-side. If the total charge cannot be put 
in the High-side, the balance will be put in the 
suction line through the access valve which you 
installed as the system was opened.

2) Connect the charging cylinder as shown in Fig. 17B.

With valve C open, discharge the hose at the
manifold connection.

3) Open valve A and allow the proper charge to 

enter the system. Valve B is still closed.

4) If more charge is required, the high-side will not 

take it. Close valve A.

5) With the unit running, open valve B and add the 

balance of the charge.

a. Do not add the liquid refrigerant to the Low-

side.

b. Watch the Low-side gauge; allow pressure to 

rise to 30 lbs.

c. Turn off valve B and allow pressure to drop.
d. Repeat steps B and C until the balance of the 

charge is in the system.

6) When satisfied the unit is operating correctly, 

use the pinch-off tool with the unit still running 
and clamp on to the pinch-off tube. Using a tube 
cutter, cut the pinch-off tube about 2 inches from 
the pinch-off tool. Use sil-fos solder and solder 
pinch-off tube closed. Turn off the unit, allow it to 
set for a while, and then test the leakage of the 
pinch-off connection.

NOTES

If high vacuum equipment is used, just crack
valves A and B for a few minutes, then open
slowly with the two full turns counterclockwise.
This will keep oil from foaming and being
drawn into the vacuum pump.

CAUTION

Содержание Uni-Fit US10B10A

Страница 1: ...US08 US10 US12 05 05 Thru the Wall Series Thru the Wall Series Service and Parts Manual 115 Volts US08B US10B US12B 230 Volts US10B US12B...

Страница 2: ...REFACE This SERVICE MANUAL provides various service information including the mechanical and electrical parts etc This room air conditioner was manufactured and assembled under a strict quality contro...

Страница 3: ...MENSION inch W x H x D mm SLEEVE DIMESION inch W x H x D mm SLEEVE DEPTH inch WITH FRONT GRILLE mm 1 115V 60Hz 8 000 9 800 11 700 830 1 110 1 250 7 5 10 2 11 4 9 6 8 8 9 4 540g 19 1OZ 475g 16 8OZ 485g...

Страница 4: ...T GRILLE mm 1 230 208V 60Hz 10 000 9 800 11 700 11 400 1 060 1 040 1 250 1 210 4 7 5 2 5 8 6 2 9 4 9 4 480g 16 9OZ 475g 16 8OZ 26 7 DB 19 4 WB 35 DB 23 9 WB 2 ROW 12STACKS 3 ROW 12STACKS 2 ROW 17STACK...

Страница 5: ...TIME You will usually use shut off time while you sleep If unit is running use Timer to set number of hours until shut off For your sleeping comfort once Time is set the Temperature setting will rais...

Страница 6: ...Keep these for later use 2 1 3 CONTROL BOX 1 Remove the front grille Refer to section 2 1 1 2 Remove the screw which fasten the control box See Fig 3 3 Pull the control box from the barrier See Fig 3...

Страница 7: ...See Fig 5 8 Using handheld pliers remove the clamp which secures the turbo fan See Fig 6 9 Remove the turbo fan with pliers or your hand without touching blades See Fig 7 10 Re install the components...

Страница 8: ...ing to the removal procedures above 2 3 2 COMPRESSOR 1 Remove the cabinet Refer to section 2 1 2 2 Discharge the refrigerant system using a FreonTM Recovery System Install a valve for recovery before...

Страница 9: ...the power cord See Fig 13 7 Re install the components by referring to the removal procedure above Use only one ground marked hole for ground connection 8 If the supply cord of this appliance is damage...

Страница 10: ...nt completely into a FreonTM Recovery System 3 Remove the 2 screws which fasten the evaporator at the left side and the right side 4 Move the evaporator sideward carefully and then unbraze the interco...

Страница 11: ...the line at the manifold connection 5 The system is now ready for final charging 6 Recharge as follows 1 Refrigeration cycle systems are charged from the High side If the total charge cannot be put i...

Страница 12: ...Brazing equipment Pinch off tool capable of making a vapor proof seal Leak detector Tubing cutter Hand Tools to remove components Service valve A COMPOUND GAUGE EVAPORATOR LOW PRESSURE SIDE COMPRESSOR...

Страница 13: ...onents and their functions in the refrigeration system Refer to Fig 18 to follow the refrigeration cycle and the flow of the refrigerant in the cooling cycle MOTOR COMPRESSOR OIL LIQUID REFRIGERANT CA...

Страница 14: ...ing Check outdoor coil heat exchanger the fan operation Check gas leakage Repair gas leak Replacement of unit if the unit is beyond repair Satisfactory operation with temperature difference of inlet o...

Страница 15: ...apacitor Irregular motor resistance Irregular motor insulation Replacement of fan motor Regular but fails to start Replacement of compressor locking of rotor metal Improper thermostat setting Loose te...

Страница 16: ...m of the fan motor with mounting screw s Check fan motor bearings if motor shaft will not rotate replace the motor Check voltage See limits on page 27 If not within limits call an electrician Test cap...

Страница 17: ...inal identification Replace the switch if circuit is open Check the position of knob If not at the coldest setting advance the knob to this setting and restart unit Check continuity of the thermostat...

Страница 18: ...e coil surface head pressures will increase causing the compressor to cycle Straighten the fins or replace the coil Test capacitor Check the terminals If loose repair or replace Check the system for a...

Страница 19: ...WER CORD 67300012 67300012 67300013 67300015 67300015 1 346811 FAN MOTOR 67303021 67303022 67303023 67303024 67303025 1 W0CZZ CAPACITOR 67300710 67300717 67300717 67300708 67300708 1 554160 COMPRESSOR...

Страница 20: ...EXPLODED VIEW MODEL US10B10A US12B10A US12B30A 567480 268711B 268711A W6631 267110 W0CZZ 554160 550140 349600 359012 W48602 559011 352380 346811 147900 554031 149980 352115 35211A 130410 435301 43530...

Страница 21: ...ernal Use Only MODEL US08B10A US10B30A 567480 268711B 268711A W6631 267110 W0CZZ 554160 550140 359012 W48602 559011 352380 346811 147900 554031 149980 352115 35211A 130410 435301 435300 435300A 238310...

Страница 22: ...05 Printed in the U S A Post Office Box 1540 4200 N Pan Am Expressway San Antonio Texas 78295 1540 210 357 4400 FAX 210 357 4480 FRIEDRICH AIR CONDITIONING CO Visit our web site at www friedrich com...

Отзывы: