RT7

 Manual  Thermostat

The Friedrich RT7 is a non-

programmable electronic thermostat, 

which can be used with the following 

heating/cooling applications: 

•  Single Stage Heat - Cool PTAC Units

•  Singe Stage Heat Pump PTAC Units 

with or without Electric Heat

Installation and Operation Guide

•  Input Voltage: 19 to 30 VAC
•  Output Rating: Max. 1.5A per terminal (3A total)
•  Temperature Control: 45°F to 90°F (7°C to 32°C)
•  Temperature Accuracy: ± 1°F (± 0.5°C)

Specifications

•  This thermostat is for LOW voltage applications only.
•  Turn OFF electricity to all heating and cooling components.
•  All wiring must conform to applicable local and national building and electrical codes 

and ordinances.

Safety Information

•  Thermostat
•  J-Box mounting plate/  

decorative trim plate

•  J-box mounting screws

•  Dry wall anchors and mounting screws
•  Wiring labels
•  GL to GH Jumper wire

Included in Package

Parts Diagram

Opening 

notch 

(underneath)

Up button

Fan 

Slide 

Switch

Down button

Mode 

Slide 

Switch

Mounting directly on wall with trim plate

•  If new mounting holes are needed, mark 

the placement of the new horizontal 

mounting holes through the trim plate 

base. Using a 3/16" drill bit, drill the 

holes you have marked and insert the 

supplied wall anchors.

•  Feed the wires through the back housing 

of the thermostat and then snap the 

back housing to the trim plate

•  Your thermostat base should now be 

securely fixed to the wall 

•  Feed the wires through the hole in the 

trim plate and screw the trim plate to the 

wall 

•  Use a flat head screw driver to separate 

the front and back housing of the 

thermostat 

•  If painting or construction is still ongoing, cover the thermostat completely or wait until 

work is complete before mounting thermostat.

•  Mount the thermostat on an inside wall about five feet above the floor in an area that 

has good circulation but is not directly affected by a vent or duct.

•  Ensure power is switched OFF at the PTAC unit

Installing the Thermostat

Mounting directly on the wall

•  Use a flat head screw driver to separate 

the front and back housing of the 

thermostat 

•  If new mounting holes are needed, mark 

the placement of the new mounting holes 

through the thermostat base. Using a 

3/16" drill bit, drill the holes you have 

marked and insert the supplied wall 

anchors.

F

C

COOL HEAT

WAIT

OFF

E

RESET

Air Temp

Thermostat 

mode

Fan status 

indicator

Half degree for Celsius

Electric / Auxiliary Heat

Set temp

Lock 

Status

Minimum off 

time indicator

Heating/cooling 

indicator

53624

Installing the Thermostat (continued)

•  Feed the wires through the hole in the 

back housing of the thermostat and then 

screw the back housing to the wall

Mounting on Junction Box

•  Install junction box

•  Insert mounting screw into top of 

junction box until there is approximately 

1/8" gap between the screw head and 

the wall

•  Use a flat head screw driver to separate 

the front and back housing of the 

thermostat

•  Feed the wires through the hole in the 

trim plate and hang the trim plate on the 

top screw

•  Feed the wires through the back housing 

of the thermostat and then snap the back 

housing to the trim plate

•  Your thermostat base should now be 

securely fixed to the wall

•  Insert and tighten the lower screw
•  Ensure that trim plate is securely fitted to 

the wall. If not, release lower screw and 

tighten top screw.