ERROR CONTENTS
(outdoor unit)
1. Make a TEST RUN in accordance with the in-
stallation instruction sheet for the indoor unit.
2. OUTDOOR UNIT LEDS
Error contents
Communication error
(Indoor unit - Outdoor unit)
Discharg pipe temperature sensor
Outdoor heat exchanger temperature sensor
Outdoor temperature sensor
Compressor temperature sensor
Heat sink temperature sensor
Pressure switch abnormal
IPM error
Compressor rotor position cannot detect
Compressor cannot operate
Outdoor fan abnormal (upper fan)
Outdoor fan abnormal (lower fan)
No error
LED
1 flash
2 flash
3 flash
4 flash
7 flash
8 flash
9 flash
12 flash
13 flash
14 flash
15 flash
16 flash
lighting
When a malfunction occurs in the outdoor unit, the LED on
the circuit board lights to indicate the error. Refer to the fol-
lowing table for the description of each error according to the
LED.
SPECIAL INSTALLATION
SETTING
PUMP DOWN (Refrigerant collecting operation)
1. When the product is stopped:
Perform the following procedures to collect the refrigerant
when moving the indoor unit or the outdoor unit.
1
2
3
4
Press the PUMP DOWN switch on the outdoor unit.
(The LED on the outdoor unit circuit board lights.)
The pump down operation (cooling operation) be-
gins right away. After oparation starts, close the
three-way valve (liquid).
After 2 - 3 minutes, operation stops. Close the three-
way valve (gas) within one minute after operations
stops.
The LED will go out three minutes after it stops.Dis-
connect the power supply after confirming that the
LED has gone out.
*When the pump down operation is repeated, temporarily disconnect
the power supply after opening the closed valves (both liquid and gas).
Reconnect the power supply after 2 - 3 minutes and perform the pump
down operation.
*When the start of the operation after pump down operation has been
completed, temporarily disconnect the power supply after opening the
closed valves (both liquid and gas).
Reconnect the power supply after 2-3 minutes and be sure to perform
a test operation for cooling.
2. When the product is operating:
1
2
3
4
Press the PUMP DOWN switch on the outdoor unit.
The LED on the outdoor unit circuit board lights, and
operation stops. At this point, recovery has not been
completed, so do not close the two- and three-way
valves.
The pump down operation (cooling operation) be-
gins after three minutes. Close the three-way valve
(liquid) after operation starts.
After 2 - 3 minutes, operation stops. Close the three-
way valve (gas) within one minute after operations
stops.
The LED will go out three minutes after it stops. Dis-
connect the power supply after confirming that the
LED has gone out.
3-way valve
(Liquid)
3-way valve
(Gas)
12
2006.02.14
DANGER
This part (Choke coil) generates high voltages.
Never touch this part.
PUMP DOWN SW (SW2)
Содержание MR24UY3F
Страница 8: ...CONTROLLER PCB ASSY K01AL 050SHSE C1 I N DO OR P C B CI R CU I T DI AG RAM 7 2006 05 25...
Страница 10: ...600 450V x 4 OUTDOOR UNIT CONTROLLER PCB ASSEMBLY K04AW 0502HUE C1 9 2006 05 25...
Страница 15: ...14 2006 05 25 INDOOR UNIT 196 1 184 1 470 764 577 127 124 235 124 108 68 578 418 160 439 138 68 187...
Страница 16: ...15 2006 05 25 983 983 INDOOR UNIT...
Страница 17: ...416 417 385 771 488 472 473 443 8 1 16 2006 05 25 INDOOR UNIT...
Страница 18: ...17 2006 05 29 800 652 1 735 146 OPTIONAL PARTS INDOOR UNIT...
Страница 19: ...18 2006 06 13 INDOOR UNIT 982...
Страница 21: ...1 6 3 4 5 2 20 2006 05 29 OUTDOOR UNIT...
Страница 22: ...17 18 10 13 11 9 15 14 8 OUTDOOR UNIT 2006 06 13 21...
Страница 23: ...22 23 31 20 29 12 28 12 19 24 26 27 25 30 22 2006 05 29 OUTDOOR UNIT...
Страница 24: ...37 38 33 34 36 35 23 2006 05 29 OUTDOOR UNIT...
Страница 29: ...0605G3090...