Friedrich M12YG Скачать руководство пользователя страница 7

1.

Check if the piping connections are secure.

2.

Check that the stems of 2-way valve and 3-way valve are closed
fully.

3.

Connect the gauge manifold charge hose to the charging port
of the 3-way valve (side with the projection for pushing in the
valve core).

4.

Open the low pressure side valve of the gauge manifold fully.

5.

Operate the vacuum pump and start pump down.

6.

Slowly loosen the flare nut of the 3-way valve and check if air
enters, then retighten the flare nut.
(When the flare nut is loosened the operating sound of the
vacuum pump changes and the reading of the compound
pressure gauge goes from minus to zero.)

OUTDOOR UNIT

OUTDOOR UNIT INSTALLATION

AIR PURGE

Always use a vacuum pump to purge the air.
Refrigerant for purging the air is not charged in the
outdoor unit at the factory.

Close the high pressure side valve of the gauge manifold fully and do
not operate it during the following work.

Set the unit on a strong stand, such as one made of concrete blocks
to minimize shock and vibration.

Do not set the unit directly on the ground because it will cause trou-
ble.

Connector cover removal

Remove the tapping screw.

Installing the connector cover

(1) After inserting the four hooks, then push upward.
(2) Tighten the tapping screw.

10. Fully open the valve stems of the 2-way valve and 3-way valve

using a hexagon wrench. (After the valve stem begins to turn,
turn it with a torque of less than 2.17ft

lbs (30 kgf

cm) until it

stops turning.)

11. Firmly tighten the 2-way valve and 3-way valve blank cap and

the charging port cap.

7.

Pump down the system for at least 15 minutes, then check if the
compound pressure gauge reads -0.1 MPa (-76 cmHg, -1 bar).

8.

At the end of pump down, close the low pressure side gauge of
the gauge manifold fully and stop the vacuum pump.

9.

Slowly loosen the valve stem of the 3-way valve. When the
compound pressure gauge reading reaches 0.1-0.2 MPa,
retighten the valve stem and disconnect the charge hose
from the 3-way valve charging port.
(If the stem of the 3-way valve is opened fully before the
charge hose is disconnected, it may be difficult to disconnect
the charge hose.)

WARNING

(1) Install the unit where it will not be tilted by more

than 5°.

(2) When installing the outdoor unit where it may ex-

posed to strong wind, fasten it securely.

Fig. 9

Tapping screw

Rear hook

Connector cover

Always use the screws as shown above.
Do not select the top and bottom screws incorrectly.

LO

HI

Flare nut

3-way valve

-0.1 MPa
(-76 cmHg
-1 bar)

High
pressure
side valve
(closed)

2-way valve

Gauge manifold

Compound pressure gauge

Pressure gauge

Low pressure
side valve

Blank cap

Charge
hose

Vacuum pump

Valve stem

Charge hose

Charging port cap

Charging port

Fig. 10

CAUTION

(1) Refrigerant must not be discharged into atmos-

phere.

(2) After connecting the piping , check the joints for

gas leakage with gas leak detector.

(3) When adding refrigerant, add the refrigerant from

the charging port at the completion of work.

(4) The maximum length of the piping is 66 ft (20 m).

If the units are further apart than this, correct
operation can not be guaranteed.

Table 7

Tightening torque

Blank cap

14.47 to 18.08 ft

lbs (200 to 250 kgf

cm)

Charging port cap

9.04 to 11.57 ft

lbs (125 to 160 kgf

cm)

Содержание M12YG

Страница 1: ...tightly Loose wiring may cause overheating at con nection points and a possible fire hazard When Transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help...

Страница 2: ...8 bar for low pressure To increase pressure resistance the hose material and base size were changed A conventional vacuum pump can be used by installing a vacuum pump adapter Special gas leakage detec...

Страница 3: ...ELAY FUSE OR HACRTYPE CIRCUIT BREAKER Cut each pipe to the appropriate length 12 30 cm to16 40 cm to dampen vibration between units B Foamed polyethylene insulation for copper pipes as required to pre...

Страница 4: ...he danger of com bustible gas leakage 2 Do not install near heat sources 3 If children under 10 years old may approach the unit take preventive measures so that they can not reach the unit 4 Install t...

Страница 5: ...ozen under low tempera ture environment When installing indoor unit s drain hose outdoors necessary measure for frost protection should be taken to prevent drain water frozen Under low temperature env...

Страница 6: ...ut the connection pipe to the nec essary length with a pipe cutter 2 Hold the pipe downward so that cuttings will not enter the pipe and remove the burrs 3 Insert the flare nut onto the pipe and flare...

Страница 7: ...ve blank cap and the charging port cap 7 Pump down the system for at least 15 minutes then check if the compound pressure gauge reads 0 1 MPa 76 cmHg 1 bar 8 At the end of pump down close the low pres...

Страница 8: ...erminal to over heat or result in unit malfunction A fire hazard may also exist Therefore be sure all wiring is tightly connected Connect wires to the matching numbers of terminals NOTE Connector trad...

Страница 9: ...ws to install the cord clamp A For solid core wiring or F cable 1 Cut the wire end with a wire cutter or wire cutting pliers then strip the insulation to about 15 16 25 mm to expose the solid wire 2 U...

Страница 10: ...ulation Vinyl tape Pipe Drain hose Cloth tape Wrap with cloth tape Left piping Connection cord Pipe Drain hose For connection from the left rear Connection cord Drain hose Wall pipe Connection pipe Dr...

Страница 11: ...al branch circuit and install a special receptacle to supply power to the room air conditioner 4 Use a circuit breaker and receptacle matched to the capacity of the air conditioner 5 Do not extend the...

Страница 12: ...djusting inter unit wire harness To connect inter unit wire harness to the terminal correctly please refer to Fig 19 to adjust the length of the part of Inter unit Wire harness ahead from conduit hold...

Страница 13: ...e remote con trol unit check that it operates positively Install the remote control unit holder to a wall pillar etc with the tapping screw Fig 20 Remote control unit holder fixing Remote control unit...

Отзывы: