Refrigerant Charging

 

NOTE:    Because  The  HazardGard  System  Is  A  Sealed 

System, Service Process Tubes Will Have To Be Installed. 

First  Install  A  Line  Tap  And  Remove  Refrigerant  From 

System.    Make  Necessary  Sealed  System  Repairs  And 

Vacuum System.  Crimp Process Tube Line And Solder End 

Shut.  Do Not Leave A Service Valve In The Sealed System.  

Proper  refrigerant  charge  is  essential  to  proper  unit 

operation.  Operating  a  unit  with  an  improper  refrigerant 

charge  will  result  in  reduced  performance  (capacity)  and/or 

efficiency.  Accordingly,  the  use  of  proper  charging  methods 

during  servicing  will  insure  that  the  unit  is  functioning  as 

designed  and  that  its  compressor  will  not  be  damaged.

 

Too much refrigerant (overcharge) in the system is just as bad 

(if not worse) than not enough refrigerant (undercharge). They 

both can be the source of certain compressor failures if they 

remain uncorrected for any period of time. Quite often, other 

problems  (such  as  low  air  flow  across  evaporator,  etc.)  are 

misdiagnosed as refrigerant charge problems. The refrigerant 

circuit  diagnosis  chart  will  assist  you  in  properly  diagnosing 

these systems. 

An  overcharged  unit  will  at  times  return  liquid  refrigerant 

(slugging) back to the suction side of the compressor eventually 

causing  a  mechanical  failure  within  the  compressor.  This 

mechanical failure can manifest itself as valve failure, bearing 

failure,  and/or  other  mechanical  failure.  The  specific  type  of 

failure will be influenced by the amount of liquid being returned, 

and the length of time the slugging continues. 

Not enough refrigerant (undercharge) on the other hand,  will 

cause the temperature of the suction gas to increase  to the point 

where it does not provide sufficient cooling for  the compressor 

motor. When this occurs, the motor winding temperature will 

increase causing the motor to overheat  and possibly cycle open 

the compressor overload protector.  Continued overheating of 

the motor windings and/or cycling of the overload will eventually 

lead to compressor motor or overload failure. 

Unplug and/or disconnect all electrical power 

to the unit before performing inspections, 

maintenances or service. 

 

 

Failure to do so could result in electric shock, 

serious injury or death.

Sealed Refrigeration System contains refrigerant 

and oil under high pressure.

Proper safety procedures must be followed, 

and proper protective clothing must be worn 

when working with refrigerants.

Failure to follow these procedures could 

result in serious injury or death. 

WARNING

WARNING

RISK OF ELECTRIC SHOCK 

HIGH PRESSURE HAZARD 

SeAleD RefRIGeRATION SYSTeM RePAIRS

ANY SEALED SYSTEM REPAIRS TO COOL-ONLY MODELS REQUIRE THE INSTALLATION OF A LIQUID LINE DRIER. 

ALSO, ANY SEALED SYSTEM REPAIRS TO HEAT PUMP MODELS REQUIRE THE INSTALLATION OF A SUCTION LINE DRIER.

IMPORTANT

EQUIPMENT REQUIRED:

  1.  Voltmeter
  2.  Ammeter
  3.  Ohmmeter
  4.   E.P.A. Approved Refrigerant Recovery System
  5.  Vacuum  Pump  (capable  of  200  microns  or  less 

vacuum.)

  6.  Acetylene Welder
  7.  Electronic Halogen Leak Detector (G.E. Type H-6 or 

equivalent.)

  8.  Accurate refrigerant charge measuring device such 

as:

    a.  Balance Scales - 1/2 oz. accuracy
    b.  Charging Board - 1/2 oz. accuracy

9.      High Pressure Gauge - (0 - 400 lbs.)
10.  Low Pressure Gauge - (30 - 150 lbs.)
 11.  Vacuum Gauge - (0 - 1000 microns)

EQUIPMENT MUST BE CAPABLE OF:

  1.  Recovery CFC’s as low as 5%.
  2.   Evacuation from both the high side and low side of the 

system simultaneously.

  3.  Introducing  refrigerant  charge  into  high  side  of  the 

system.

  4.  Accurately  weighing  the  refrigerant  charge  actually 

introduced into the system.

  5.  Facilities for flowing nitrogen through refrigeration tubing 

during all brazing processes.

 

12

Содержание Hazardgard SH15L30-C

Страница 1: ...Service Manual Room Air Conditioners HG ServMan 04 09 Model SH15L30 C SH15L30 D SH20L30 C SH20L30 D...

Страница 2: ...IONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4490 www friedrich com Printed in the U S A TECHNICAL SUPPORT...

Страница 3: ...n Data 6 Electrical Data 7 HazardGard Special Features 8 Control Panel 8 Component Definitions 9 Component Testing 10 11 Sealed System Refrigeration Repairs 12 Refrigerant Charging 12 15 Compressor Ch...

Страница 4: ...sistant if possible Capacitors even when disconnected from the electrical power source retain an electrical charge potential capable of causing electric shock or electrocution Handle discharge and tes...

Страница 5: ...contact with liquid refrigerant can result in minor to moderate injury Be extremely careful when using an oxy acetylene torch Direct contact with the torch s flame or hot surfaces can cause serious b...

Страница 6: ...rty Insure that the unit has a sufficient pitch to the outside to allow water to drain from the unit Do not drill holes in the bottom of the drain pan or the underside of the unit Failure to follow th...

Страница 7: ...g L Nov C Mar F Jun J Sept M Dec 1st Digit Function S Straight Cool Value Series H HazardGard 3rd and 4th Digit Approximate BTU HR Cooling Heating BTU Hr capacity listed in the Specifi cation Performa...

Страница 8: ...t Locked Rotor Amps Charge in OZ 60 Hertz Amps SH15L30 C 54 26 206 129 61 16 98 76 258 8 2 43 28 5 208 230 15 SH15L30 D 54 26 206 129 61 16 98 76 258 8 2 43 28 5 208 230 15 SH20L30 C 46 34 125 196 52...

Страница 9: ...PA 70 ARTICLE 501 THE FIELD PROVIDED CIRCUIT PROTECTION DEVICE HACR CIRCUIT BREAKER OR TIME DELAY FUSE MUST NOT EXCEED THE AMPACITY INDICATED ON THE PRODUCT NAMEPLATE IMPORTANT Before you begin the ac...

Страница 10: ...it Condensate drain with exclusive mosquito trap 15 amp circuit with time delay fuse required Accommodates direct wiring Long lasting 3 8 10mm thick air filter germicidally treated easily removed for...

Страница 11: ...diagrams and schematics in the back of this service manual Solid State Relay Used to energize the compressor and fan motor Each unit has 2 50 amp 208 230 volt relays Capacitor Reduces line current and...

Страница 12: ...n or shorted It will tell whether the capacitor is within its micro farads rating and it will show whether the capacitor is operating at the proper power factor percentage The instrument will automati...

Страница 13: ...valve to open and bypass hot gas from the high pressure side to the low pressure side of the system The hot gas entering the compressor mixes with the cool gas returned through the suction line thus...

Страница 14: ...for the compressor motor When this occurs the motor winding temperature will increase causing the motor to overheat and possibly cycle open the compressor overload protector Continued overheating of...

Страница 15: ...EZE HAZARD Proper safety procedures must be followed and proper protective clothing must be worn when working with a torch Failure to follow these procedures could result in moderate or serious injury...

Страница 16: ...evaporator will not be encountered because the refrigerant will boil later if at all Gauges connected to system will usually have higher head pressure depending upon amount of over charge Suction pres...

Страница 17: ...a partial restriction there may be gurgling sounds at the metering device entrance to the evaporator The evaporator in a partial restriction could be partially frosted or have an ice ball close to th...

Страница 18: ...Test NOTE Consult the specification and performance section for running amperage The L R A can also be found on the rating plate Select the proper amperage scale and clamp the meter probe around the w...

Страница 19: ...inals common to run C to R Add values C to S and C to R together and check resistance from start to run terminals S to R Resistance S to R should equal the total of C to S and C to R In a single phase...

Страница 20: ...tem will need to be cleaned up following proper procedures 7 Install the replacement compressor 8 Pressurize with a combination of R 22 and nitrogen and leak test all connections with an electronic or...

Страница 21: ...se a biodegradable cleaning agent and degreaser to prevent damage to the coil and or base pan NOTICE NOTICE Inspect the indoor blower housing evaporator blade condenser fan blade and condenser shroud...

Страница 22: ...yearly or bi yearly and clean of all obstructions and debris Clean both areas with an antibacterial and antifungal cleaner Rinse both items thoroughly with water and ensure that the drain outlets are...

Страница 23: ...or runs continually Does not cycle off Excessive heat load Test cooling performance of unit Unit undersized Restriction in line Check for partially iced coil Check temperature split across coil Refrig...

Страница 24: ...motor runs Thermostat contacts not closing Check continuity of thermostat at coldest setting If compressor runs replace thermostat Low voltage supply Check for nameplate voltage Provide proper voltage...

Страница 25: ...or blower wheel clearance Compressor vibrating Check for deteriorated compressor grommets Replace as needed Loose cabinet parts improperly mounted components tubing rubbing Adjust and tighten as requ...

Страница 26: ...24 ELECTROMECHANICAL CONTROL COOL ONLY MODELS SH15L30 C SH15L30 D SH20L30 C SH20L30 D...

Страница 27: ...Room Air Conditioner that has been subject to a accident misuse flood fire or neglect b repairs or alterations outside of the Friedrich Authorized Dealer or Service Center so as to affect adversely i...

Страница 28: ......

Страница 29: ......

Страница 30: ......

Страница 31: ...IONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4490 www friedrich com Printed in the U S A TECHNICAL SUPPORT...

Страница 32: ...AIR CONDITIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4490 www friedrich com Printed in the U S A HG Serv...

Отзывы: