FAN MOTOR 

(Figure 4)

A 230 volt single phase permanent split capacitor motor 
is used to drive the evaporator blower and condenser 
fan.  A running capacitor is wired across the start and 
run terminals of the motor.

The motor is totally enclosed and is protected with a line 
voltage overload located internally of the motor.  The 
motor shaft is stainless steel to resist corrosion.

CHECKING COMPRESSOR EFFICIENCY

The reason for compressor ineffi ciency is normally 
due to broken or damaged suction and/or discharge 
valves, reducing the ability of the compressor to pump 
refrigerant gas.

This condition can be checked as 

follows:

1.  Install a piercing valve on the suction and 

discharge or liquid process tube.

2.  Attach gages to the high and low sides of 

the system.

3.  Start the system and run a "cooling or 

heating performance test."

   

If test shows:

A.  Below normal high side pressure. 
B.  Above normal low side pressure.
C. Low temperature difference across the coil.

 The 

compressor 

valves 

are 

faulty 

- replace the compressor.

GROUND TEST

Use an ohmmeter set on its highest scale.  Touch one 
lead to the compressor body (clean point of contact, 
as a good connection is a must) and the other probe 
in turn to each compressor terminal.  (See Figure 3.)  
If a reading is obtained, the compressor is grounded 
and must be replaced.

FIGURE 3 TYPICAL GROUND TEST

FAN MOTOR – TEST

Disconnect power to the unit.

 

1.  Determine that the capacitor is serviceable.

 

2.  Disconnect the black lead from the circuit 

board.

 

3.  Apply "live" test cord leads to the common 

terminal of the capacitor and the black lead.  
The motor should run at high speed.

SOLID STATE RELAY 

(Figure 5)

Two 50 amp rated 208/230 volt solid state relays 
are used to energize the compressor and fan motor. 
Terminals 3 and 4 are the 208/230 volt line side. 
Terminals 1 and 2 are load side contacts.

FIGURE 4  FAN MOTOR

FIGURE 5  SOLID STATE RELAY

LED indicates 

contacts closed 

when lit

Line side

Load side

Содержание Hazardgard SH15L30-A

Страница 1: ...SH15L30 A SH20L30 A SH20L50 A HG SVC PRTS 05 4 05 Service Parts Manual Room Air Conditioners 50 60 Hz Models 2005...

Страница 2: ...ontrol Switch 6 Run Capacitor 6 Thermostat 6 Low Ambient Bypass Valve 8 Sealed Refrigeration System Repairs 8 Hermetic Component Replacement 9 Special Procedure in the case of Compressor Motor Burn Ou...

Страница 3: ...del Dimensions Inches Window Width Inches Thru The Wall Finished Hole Inches Circuit Rating Breaker or T D Fuse Weight Lbs Height Width Depth Overall Depth Hood to Louvers Minimum Extension Into Room...

Страница 4: ...to high temperatures caused by 1 A locked rotor 2 Excessive running amps 3 High discharge temperature 4 Low refrigerant charge FIGURE 1 INTERNAL OVERLOAD LINE BREAK INTERNAL OVERLOAD OHMMETER FIGURE 2...

Страница 5: ...side pressure B Above normal low side pressure C Low temperature difference across the coil The compressor valves are faulty replace the compressor GROUND TEST Use an ohmmeter set on its highest scale...

Страница 6: ...in relation to the evaporator see Figure 8 FIGURE 8 SENSING BULB LOCATION CAPACITOR TEST 1 Remove the capacitor from the unit 2 Check for visual damage such as bulges cracks or leaks 3 For dual rated...

Страница 7: ...n in this manual for additional information on thermostat testing TEST Remove the wires from the thermostat Turn the thermostat to its coldest position Check to see if there is continuity between the...

Страница 8: ...t the bypass valve outlet which connects to the suction process tube When the low side pressure reaches approximately 50 psig the valve will begin to open and the tube will get hot This method will de...

Страница 9: ...th processing as outlined under hermetic component replacement HERMETIC COMPONENT REPLACEMENT The following procedure applies when replacing components in the sealed refrigeration circuit or repairing...

Страница 10: ...y into the low side The introduction of liquid into the low side without the use of a capillary tube will cause damage to the discharge valve of the rotary compressor ROTARY COMPRESSOR SPECIAL TROUBLE...

Страница 11: ...ive fan motor Test and replace if inoperative COMPRESSOR RUNS CONTINUALLY DOES NOT CYCLE OFF Excessive heat load Test cooling performance of unit Unit undersized Restriction in line Check for partiall...

Страница 12: ...OR DOES NOT START FAN MOTOR RUNS Thermostat contacts not closing Check continuity of thermostat at coldest setting Jump contacts if compressor runs replace thermostat Low voltage supply Check for name...

Страница 13: ...blade and blower wheel clearance Compressor vibrating Check for deteriorated compressor grommets or missing mounting parts Loose cabinet parts improperly mounted components tubing rubbing Adjust and t...

Страница 14: ...14 WIRING DIAGRAM MODELS SH15L30 A SH20L30 A SH20L50 A...

Страница 15: ...15 HAZARDGARD CABINET PARTS...

Страница 16: ...16 HAZARDGARD CHASSIS PARTS...

Страница 17: ...399 RELAY SOLID STATE 61108800 2 2 2 399 6 THERMOSTAT 61825502 1 1 1 120 7 CAPACITOR 20 7 5 440 V 61080546 1 1 1 150 7 CAPACITOR 25 7 5 440 V 61080547 1 1 1 150 HARNESS WIRE COMP 61821308 1 1 1 399 R...

Страница 18: ...1 772 LATCH INTAKE GRILLE 61989000 2 2 2 752 FILTER AIR 60865808 1 754 FILTER AIR 60865809 1 1 754 HOLDER FILTER 61823000 2 2 2 756 8 HOLDER THERMOSTAT 61829800 1 1 1 999 25 FAN MOTOR MOUNT 61802500 1...

Страница 19: ...19...

Страница 20: ...actory Certi ed Parts FRIEDRICH AIR CONDITIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4480 www friedrich...

Отзывы: