TROUBLESHOOTING (Continued)

PROBLEM

POSSIBLE CAUSE

TO CORRECT

COMPRESSOR 
ATTEMPTS TO 
START, OR RUNS 
FOR SHORT 
PERIODS ONLY. 

CYCLES ON 
OVERLOAD.

Compressor attempts to start 
before system pressures are 
equalized.

Allow a minimum of two (2) minutes to allow pressures to 
equalize before attempting to start.

Low or fl uctuating voltage.

Check voltage with unit operating. Check for other 
appliances on the circuit. Unit should be on separate circuit 
for proper voltage, and be fused separately.

Incorrect wiring.

Connect per wiring diagram.

Shorted or incorrect capacitor.

Check by substituting a known good capacitor of correct 
rating.

Restricted or low air fl ow through 
condenser coil.

Check for proper fan speed or blocked condenser.

Compressor running abnormally 
hot.

Check for kinked discharge line or restricted condenser. 
Check amperage.

Overload opens too soon.

Change compressor if all other corrections above are 
normal.

COMPRESSOR DOES 
NOT START - FAN 
MOTOR RUNS.

Thermostat contacts not closing.

Check continuity of thermostat at coldest setting. Jump 
contacts, if compressor runs, replace thermostat.

Low voltage supply.

Check for nameplate voltage.

Switch (On-Off) inoperative.

Test for continuity.

Open capacitor.

Check by substituting a known good capacitor of correct 
rating.

Internal overload open.

Check voltage at compressor terminals. If voltage is 
satisfactory, replace compressor.

Relay open

Replace relay

Open or shorted compressor 
windings

Check windings for continuity and resistance. Direct test 
compressor. If direct test fails, replace compressor.

DOES NOT COOL, 
OR COOLS ONLY 
SLIGHTLY.

Thermostat open or inoperative.

Set to coldest position. Test thermostat and replace if 
necessary.

Dirty air fi lter.

Clean as recommended in Owner’s Manual.

Dirty or plugged condenser or 
evaporator coil.

Use steam or detergents to clean.

Poor air circulation in area being 
cooled.

Adjust air louvers.

Low capacity - undercharge.

Clean, check for leak and make repair.

Compressor not pumping properly.

Check amperage draw against nameplate. If not conclusive, 
make pressure test.

Содержание HazardGard 60 Hz

Страница 1: ...SH15L30 B SH20L30 B HG SVC PRTS 07 3 07 Room Air Conditioners 60 Hz Models 2007 Service Parts Manual...

Страница 2: ...ntrol Switch 5 Run Capacitor 5 Thermostat 5 Low Ambient Bypass Valve 6 Sealed Refrigeration System Repairs 6 Hermetic Component Replacement 7 Special Procedure in the case of Compressor Motor Burn Out...

Страница 3: ...TING FOR CLASS I DIVISION 2 GROUPS A B C D Model Dimensions Inches Window Width Inches Thru The Wall Finished Hole Inches Circuit Rating Breaker or T D Fuse Weight Lbs Height Width Depth Overall Depth...

Страница 4: ...hell of the compressor continuity grounded motor replace compressor 5 Should continuity exist between terminals R and S but not between terminals C and S and C and R the internal overload may be open...

Страница 5: ...can be used for each motor or a dual rated capacitor can be used for both The capacitor s primary function is to reduce the line current while greatly improving the torque characteristics of a motor...

Страница 6: ...ressure reaches 50 psig This pressure setting cannot be altered The system can be operated at outdoor temperatures as low as 45 F before the evaporator coil will begin to accumulate frost To determine...

Страница 7: ...pump to the high side and low side of the system with deep vacuum hoses or copper tubing Do not use regular hoses 10 Evacuate the system to an absolute holding pressure of 200 microns or less 12 Resta...

Страница 8: ...ive fan motor Test and replace if inoperative COMPRESSOR RUNS CONTINUALLY DOES NOT CYCLE OFF Excessive heat load Test cooling performance of unit Unit undersized Restriction in line Check for partiall...

Страница 9: ...SOR DOES NOT START FAN MOTOR RUNS Thermostat contacts not closing Check continuity of thermostat at coldest setting Jump contacts if compressor runs replace thermostat Low voltage supply Check for nam...

Страница 10: ...blade and blower wheel clearance Compressor vibrating Check for deteriorated compressor grommets or missing mounting parts Loose cabinet parts improperly mounted components tubing rubbing Adjust and t...

Страница 11: ...11 WIRING DIAGRAM MODELS SH15L30 B and SH20L30 B...

Страница 12: ...12 HAZARDGARD CABINET PARTS...

Страница 13: ...13 HAZARDGARD CHASSIS PARTS...

Страница 14: ...1 399 RELAY SOLID STATE 61108800 2 2 399 6 THERMOSTAT 61822502 1 1 120 7 CAPACITOR 20 7 5 440 V 61080546 1 150 7 CAPACITOR 25 7 5 440 V 61080547 1 150 HARNESS WIRE COMP 61821308 1 1 399 REFRIGERATION...

Страница 15: ...4905 1 743 30 SCROLL 61817505 1 743 32 BASE PAN 61803444 1 1 730 34 BOLT COMP MOUNT 91400400 3 3 791 35 PLENUM ASSEMBLY 61831006 1 1 753 36 OUTER SHELL 61825708 1 770 36 OUTER SHELL 61825709 1 770 37...

Страница 16: ...rranty period providing the unit is returned to an authorized Friedrich Repair Station located within the Continental United States The Friedrich warranty does not cover 1 Any charges for removal tran...

Отзывы: