Vacuum pumping
Leakage detection
1. Remove the valve caps on
the liquid valve and gas
valve and the nut of refri-
gerant charging vent.
2. Connect the charging hose
@,%
to the refri-
gerant charging
of gas
valve and then connect the
other charging hose to the
vacuum pump.
3. Open the
@,%
com-
pletely and operate for
10-15min to check if the
pressure of
@,%
re-
mains in -0.1MPa.
4. Close the vacuum pump
and maintain for
1-2min to
check if the pres-
sure of
@,%
remains
in -0.1MPa. If the pressure decreases, there may be leakage.
5. Remove the
@,%
, open the valve core of liquid valve and gas
valve
completely with
:#!
6. Tighten the screw caps of valves and refrigerant charging
.
7. Reinstall the handle.
Use vacuum pump
liquid valve
gas valve
refrigerant
charging
nut of refrigerant
charging
vacuum pump
@,%
valve cap
Lo
Hi
:#
open
close
1. With leakage detector:
Check if there is leakage with leakage detector.
2. With soap water:
If leakage detector is not available, please use soap water for leakage detection.
Apply soap water at the suspected position and keep the soap water for more
than 3min.
$/// F*!