Refrigerant Charging

 

NOTE:  Because The RAC System Is A Sealed System, 

Service  Process  Tubes  Will  Have  To  Be  Installed.  First 

Install A Line Tap And Remove Refrigerant From System.  

Make  Necessary  Sealed  System  Repairs  And  Vacuum 

System.  Crimp Process Tube Line And Solder End Shut.  

Do  Not  Leave  A  Service  Valve  In  The  Sealed  System.  

Proper  refrigerant  charge  is  essential  to  proper  unit 

operation.  Operating  a  unit  with  an  improper  refrigerant 

charge  will  result  in  reduced  performance  (capacity)  and/or 

efficiency.  Accordingly,  the  use  of  proper  charging  methods 

during  servicing  will  insure  that  the  unit  is  functioning  as 

designed  and  that  its  compressor  will  not  be  damaged.

 

Too much refrigerant (overcharge) in the system is just as bad 

(if not worse) than not enough refrigerant (undercharge). They 

both can be the source of certain compressor failures if they 

remain uncorrected for any period of time. Quite often, other 

problems  (such  as  low  air  flow  across  evaporator,  etc.)  are 

misdiagnosed as refrigerant charge problems. The refrigerant 

circuit  diagnosis  chart  will  assist  you  in  properly  diagnosing 

these systems. 

An  overcharged  unit  will  at  times  return  liquid  refrigerant 

(slugging) back to the suction side of the compressor eventually 

causing  a  mechanical  failure  within  the  compressor.  This 

mechanical failure can manifest itself as valve failure, bearing 

failure,  and/or  other  mechanical  failure.  The  specific  type  of 

failure will be influenced by the amount of liquid being returned, 

and the length of time the slugging continues. 

Not enough refrigerant (undercharge) on the other hand,  will 

cause the temperature of the suction gas to increase  to the point 

where it does not provide sufficient cooling for  the compressor 

motor. When this occurs, the motor winding temperature will 

increase causing the motor to overheat  and possibly cycle open 

the compressor overload protector.  Continued overheating of 

the motor windings and/or cycling of the overload will eventually 

lead to compressor motor or overload failure. 

Unplug and/or disconnect all electrical power 

to the unit before performing inspections, 

maintenances or service. 

 

 

Failure to do so could result in electric shock, 

serious injury or death.

Sealed Refrigeration System contains refrigerant 

and oil under high pressure.

Proper safety procedures must be followed, 

and proper protective clothing must be worn 

when working with refrigerants.

Failure to follow these procedures could 

result in serious injury or death. 

WARNING

WARNING

RISK OF ELECTRIC SHOCK 

HIGH PRESSURE HAZARD 

SeAleD RefRIGeRATION SYSTeM RePAIRS

ANY SEALED SYSTEM REPAIRS TO COOL-ONLY MODELS REQUIRE THE INSTALLATION OF A LIQUID LINE DRIER. 

ALSO, ANY SEALED SYSTEM REPAIRS TO HEAT PUMP MODELS REQUIRE THE INSTALLATION OF A SUCTION LINE DRIER.

IMPORTANT

EQUIPMENT REQUIRED:

  1.  Voltmeter
  2.  Ammeter
  3.  Ohmmeter
  4.   E.P.A. Approved Refrigerant Recovery System
  5.  Vacuum  Pump  (capable  of  200  microns  or  less 

vacuum.)

  6.  Acetylene Welder
  7.  Electronic Halogen Leak Detector (G.E. Type H-6 or 

equivalent.)

  8.  Accurate refrigerant charge measuring device such 

as:

    a.  Balance Scales - 1/2 oz. accuracy
    b.  Charging Board - 1/2 oz. accuracy

9.      High Pressure Gauge - (0 - 400 lbs.)
10.  Low Pressure Gauge - (30 - 150 lbs.)
 11.  Vacuum Gauge - (0 - 1000 microns)

EQUIPMENT MUST BE CAPABLE OF:

  1.  Recovery CFC’s as low as 5%.
  2.   Evacuation from both the high side and low side of the 

system simultaneously.

  3.  Introducing  refrigerant  charge  into  high  side  of  the 

system.

  4.  Accurately  weighing  the  refrigerant  charge  actually 

introduced into the system.

  5.  Facilities for flowing nitrogen through refrigeration tubing 

during all brazing processes.

 

14

Содержание CP14E10

Страница 1: ...Service Manual Compact Programmable CP 14 18 24 ServMan 04 09 Models 2009 2008...

Страница 2: ...IONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4490 www friedrich com Printed in the U S A TECHNICAL SUPPORT...

Страница 3: ...se 10 How to Operate the Friedrich CP Room Air Conditioner 11 12 Refrigeration Sequence of Operation 13 Sealed Refrigeration System Repairs 14 17 Method of Charging Repairs 15 Metering Device 18 Compr...

Страница 4: ...sistant if possible Capacitors even when disconnected from the electrical power source retain an electrical charge potential capable of causing electric shock or electrocution Handle discharge and tes...

Страница 5: ...contact with liquid refrigerant can result in minor to moderate injury Be extremely careful when using an oxy acetylene torch Direct contact with the torch s flame or hot surfaces can cause serious b...

Страница 6: ...e to allow water to drain from the unit Do not drill holes in the bottom of the drain pan or the underside of the unit Failure to follow these instructions can result in result in damage to the unit a...

Страница 7: ...ul K Oct B Feb E May H Aug L Nov C Mar F Jun J Sept M Dec 3rd and 4th Digit Approximate BTU HR Cooling Heating BTU Hr capacity listed in the Specification Performance Data Section 7th Digit Options 0...

Страница 8: ...electrical ratings on unit s rating plate Proper circuit protection is the responsibiity of the homeowner Grounding Unit MUST be grounded from branch circuit through service cord to unit or through se...

Страница 9: ...ed grounding method To test your power supply cord 1 Plug power supply cord into a grounded 3 prong outlet 2 Press RESET 3 Press TEST listen for click Reset button will trip and pop out 4 Press and re...

Страница 10: ...tube Fan Type Piece Axial fan 1 Axial fan 1 Axial fan 1 Fan Diameter inches 15 59 15 59 15 59 900 780 730 1000 900 800 1060 970 820 205 297 320 1 78 1 29 1 39 15 7 7 300 300 300 150 150 150 17 X 26 X...

Страница 11: ...Axial fan 1 Fan Diameter inches 15 59 15 59 15 59 900 780 730 900 780 730 1000 900 800 200 200 190 3 1 45 1 35 15 7 7 300 300 300 150 150 150 17 X 26 X 27 17 X 26 X 27 17 X 26 X 29 121 141 165 R22 26...

Страница 12: ...e operation of the fan motor and the compressor or to turn the unit off For troubleshooting refer to the wiring diagrams and schematics in the back of this service manual Fan Motor Dual shafted fan mo...

Страница 13: ...a1 to 24 hourdelayuntilthe air conditioner turns on keeping previous settings 1 Turn off air conditioner 2 Press TIMER Indicator light will flash 3 Press the plus or minus button to change the delay t...

Страница 14: ...panel will flash 2 Press the plus or minus button to change the delay time from 1 to 24 hours 3 Press TIMER again or wait 10 seconds Indicator light on air conditioner control panel will remain on To...

Страница 15: ...changed to a Liquid before leaving the condenser coil The refrigerant leaves the condenser Coil through the liquid line as a warm high pressure liquid It next will pass through the refrigerant drier i...

Страница 16: ...g for the compressor motor When this occurs the motor winding temperature will increase causing the motor to overheat and possibly cycle open the compressor overload protector Continued overheating of...

Страница 17: ...FREEZE HAZARD Proper safety procedures must be followed and proper protective clothing must be worn when working with a torch Failure to follow these procedures could result in moderate or serious inj...

Страница 18: ...evaporator will not be encountered because the refrigerant will boil later if at all Gauges connected to system will usually have higher head pressure depending upon amount of over charge Suction pres...

Страница 19: ...a partial restriction there may be gurgling sounds at the metering device entrance to the evaporator The evaporator in a partial restriction could be partially frosted or have an ice ball close to th...

Страница 20: ...Failure to do so could result in serious injury or death Amperage L R A Test The running amperage of the compressor is the most impor tant of these readings A running amperage higher than that indicat...

Страница 21: ...un connections S to R The next highest resistance is from the start to the common connections S to C The lowest resistance is from the run to common C to R Before replacing a compressor check to be su...

Страница 22: ...by proper connection of the running capacitor terminals From the supply line on a typical 230 volt circuit a 115 volt potential exists from the R terminal to ground through a possible short in the ca...

Страница 23: ...system will need to be cleaned up following proper procedures 7 Install the replacement compressor 8 Pressurize with a combination of R 22 and nitrogen and leak test all connections with an electronic...

Страница 24: ...ll refrigerant and oil from the system Remove compressor capillary tube and filter drier from the system Flush evaporator condenser and all connecting tubing with dry nitrogen or equivalent Use approv...

Страница 25: ...sh and compressed air or vacuum If using a pressure washer be careful not to bend the aluminium fin pack Use a sweeping up and down motion in the direction of the vertical aluminum fin pack when press...

Страница 26: ...r and ensure that the drain outlets are operating correctly Check the sealant around the sleeve and reseal areas as needed FRONT COVER Clean the front cover when needed Use a mild detergent Wash and r...

Страница 27: ...Inoperative system switch Test switch replace if inoperative Broken loose or incorrect wiring Refer to applicable wiring diagram Open capacitor Test capacitor replace if inoperative Fan speed switch...

Страница 28: ...ck temp differential delta T across coil Touch test coil return bends for same temp Test for low running current n o i t c A e s u a C e l b i s s o P m e l b o r P Compressor runs continually does no...

Страница 29: ...k if unit operates If unit operates replace t stat Loose or broken parts in t stat Check as above Incorrect wiring Refer to appropriate wiring diagram Defective thermistor Replace thermistor or electr...

Страница 30: ...ycles Defective thermistor Replace thermistor or electronic control board T stat differential too narrow Replace t stat Plenum gasket not sealing allowing discharge air to short cycle t stat Check gas...

Страница 31: ...29 ELECTRONIC CONTROL WIRING DIAGRAM 2009 MODEL CP24E30 CP14E10 CP18E30...

Страница 32: ...30 ELECTRONIC CONTROL WIRING DIAGRAM 2008 MODEL CP24N30 CP14N10 CP18N30...

Страница 33: ...EXPLODED VIEW AND LIST OF PARTS 2009 MODEL CP14E10 CP18E30 AND CP24E30 31...

Страница 34: ...2009 PARTS 32...

Страница 35: ...2009 PARTS Continued 33...

Страница 36: ...EXPLODED VIEW AND LIST OF PARTS 2008 MODEL CP14N10 CP18N30 AND CP24N30 34...

Страница 37: ...r d e i r F y t Q n o i t p i r c s e D o N 2 3 1 0 0 7 7 6 1 y s s A r e t r o p p u S 1 4 5 1 0 0 7 7 6 7 2 2 x 2 4 T S w e r c S g n i d a e r h t f l e S 2 3 1 1 0 0 7 7 6 2 t e k c a r B g n i k...

Страница 38: ...r i A h s e r F 5 3 3 4 2 0 0 7 7 6 1 l e e h W r e w o l B 6 3 8 0 1 0 0 7 7 6 1 t n o r F r e w o l B 7 3 Model CP24N30 6 0 1 0 0 7 7 6 1 e u l F r i A f o e t a l P e s a B 8 3 3 0 1 0 0 7 7 6 1 y...

Страница 39: ...llation wiring electrical current characteristics or maintenance or caused by accident misuse or abuse fire flood alterations and or misapplication of the product and or units installed in a corrosive...

Страница 40: ......

Страница 41: ......

Страница 42: ......

Страница 43: ...IONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4490 www friedrich com Printed in the U S A TECHNICAL SUPPORT...

Страница 44: ...CONDITIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4490 www friedrich com Printed in the U S A CP 14 18 24...

Отзывы: